ماركة: Telemecanique أجهزة الاستشعار (formerly شنايدر OsiSense XM series, now part of YAGEO)
يكتب: Diaphragm type, adjustable differential pressure switch with dual setpoints, local scale indicator, 1 الاتصال التحول (1شركة)
✅ Pressure Specifications
Rising pressure setting range: 0.7~10 bar
Falling pressure reset range: 0.13~9.15 bar
Minimum differential: 0.57 حاجِز; maximum differential: 7.5 حاجِز
Instantaneous overload pressure: 22.5 حاجِز; continuous maximum working pressure: 12.5 حاجِز
ضغط الانفجار: 45 حاجِز
Sensing element: غشاء; wetted materials: FPM/FKM fluoroelastomer + zinc alloy
Compatible media: الهواء المضغوط, clean water, الزيت الهيدروليكي; medium temperature: 0~70 ℃
✅ Process & التوصيل الكهربائي
اتصال العملية: G1/4 internal thread (ISO228)
Electrical entry: Pg13.5 cable gland, cable OD 9–13 mm; محطات المسمار, wire size 0.5~2.5 mm²
اتصال: 1شركة (13-14-11-12) silver contact, snap-action
تصنيف الاتصال: AC-15 120V/3A; 240فولت/1.5 أمبير; DC-13 250V/0.1A
جهد العزل واجهة المستخدم: 500V(اللجنة الانتخابية المستقلة); دفعة تحمل الجهد Uimp: 6 كيلو فولت
فئة الحماية: IP66
التكرار: ±2%; maximum switching frequency: 120 دورات / دقيقة
عمر الخدمة الميكانيكية: 5 مليون دورة
درجة الحرارة المحيطة: -25~70 ℃; درجة حرارة التخزين: -40~70 ℃
✅ الأبعاد & وزن
عرض 35 mm × Height 113 mm × Depth 75 مم; الوزن الصافي 0.705 كجم; mounting in any orientation
✅ Approvals & المعايير
م, UL508, وكالة الفضاء الكندية, IEC60947-5-1; marine classification approval; origin: الجمهورية التشيكية / المغرب; ضمان: 18 شهور
✅ التطبيقات النموذجية
ضواغط الهواء, hydraulic power packs, water supply pumps, أنظمة التشحيم, التدفئة والتهوية وتكييف الهواء, general industrial pressure start/stop, high/low pressure interlock protection
✅ مرجع استبدال السلاسل المتقاطعة
XMLB shares the same platform with XMLA/XMLC/XMLD. Please distinguish pressure ranges (0.25/10/16/25 حاجِز), contact quantity and indicator versions. Legacy models XM2JM, XMJ can be replaced with XMLB.
Telemecanique XMLB010A2S11 Pressure Switch Installation Manual
Applicable series: XMLA / XMLB / XMLC / XMLD same-platform electromechanical pressure switches. نموذج: XMLB010A2S11, 10 bar range, تفاضلية قابلة للتعديل, 1CO changeover contact, G1/4 internal thread, Pg13.5 gland, IP66
⚠️ Precautionary Safety Warnings (Read First)
- Do NOT disassemble, wire or adjust under pressure or live power. Depressurize the system and isolate control power before any work.
- Approved media: الهواء المضغوط, clean water, standard hydraulic oil. Strong corrosive media or high-temperature media are prohibited (max medium temperature 70 درجه مئوية).
- Pressure must not exceed instantaneous overload 22.5 bar or burst pressure 45 حاجِز. Overpressure will permanently damage the diaphragm and void protection function.
- Contacts are designed for control circuits only. Do not switch main motor power directly. AC-15 120V 3A / 240الخامس 1.5 أ, DC-13 250V 0.1A.
- IP66 rated. For outdoor installation, avoid direct sunlight and continuous heavy spray. Tighten the cable gland fully for sealing.
- التكليف, calibration and maintenance must be performed by qualified pneumatic/hydraulic and low-voltage electrical personnel.
- Unpacking Inspection
التحقق من النموذج: XMLB010A2S11
Check housing and thread for cracks or damage; confirm scale plate intact, gland and sealing washer supplied
مُكَمِّلات: الوحدة فقط, fitted with Pg13.5 cable gland; no adapter included
التحقق من لوحة الاسم: 0.7~10 bar range, 1CO contact, G1/4 ISO228 internal process thread
- التركيب الميكانيكي
2.1 متطلبات التركيب
اتجاه التركيب: أي موقف (XMLB has no mandatory upright requirement). Prioritize easy visibility of the scale.
Keep away from high heat sources and heavy vibration (excessive vibration causes false tripping and shortens service life).
It is recommended to fit an isolation valve + drain valve at the tapping point for future calibration and replacement without full system shutdown.
Tapping point: Take pressure from the side wall of pipe runs. Avoid high points (air accumulation) and low points (sediment build-up).
2.2 Thread Connection (G1/4 Internal BSP)
- Clean male thread, remove burrs and metal debris to prevent particles entering the diaphragm chamber.
- ختم: Use PTFE tape only on the male thread. Do not push tape residue into the switch internal thread as debris may jam the diaphragm.
- Tightening: Use a spanner on the bottom hexagonal process base only. Never clamp the plastic housing — this will damage the internal mechanism.
- Torque moderately until leak-tight; do not force over-tightening.
ملحق اختياري: G1/4 to NPT1/4 adapter for NPT piping systems.
2.3 Piping Recommendations
Keep impulse tubing short and large bore to reduce response lag. Long tubing may cause slow response and chattering.
Install a pre-filter for media with solids to protect the FKM fluoroelastomer diaphragm.
Drain water-filled systems in cold environments to prevent freezing; ice expansion ruptures the diaphragm.
- التمديدات الكهربائية
3.1 مواصفات الكابل
القطر الخارجي للكابل: 9~13 mm (matches Pg13.5 gland)
المقطع العرضي للموصل: 0.5~2.5 مم² (AWG20~AWG14); ferrules are recommended for stranded conductors.
3.2 تعريف المحطة (1CO dry contact)
| صالة | تعريف | وصف |
| 11 | كوم | شائع |
| 12 | نورث كارولاينا | مغلقة عادة: Conducts below set pressure, opens at trip pressure |
| 14 | لا | مفتوحة عادة: Closes at trip pressure, opens at low pressure |
وضع العلامات 13: Some versions mark 13 alongside 14 for the same NO circuit; follow housing marking.
3.3 إجراءات الأسلاك
- Isolate power, remove top cover screws and open the lid.
- Loosen Pg13.5 gland nut, feed cable through and strip to suitable length.
- Insert wires into terminals and tighten screws securely to avoid loose connections.
- Route cables clear of the internal spring adjustment assembly. Refit cover and tighten screws evenly.
- Tighten gland and compress rubber seal to maintain IP66 integrity. Poor gland sealing causes water ingress and failure.
Wiring note: This is a passive dry contact. No supply voltage is carried by the switch. PLC or relay control power must be supplied externally.
- Pressure Setting & معايرة (XMLB dual setpoint: trip point + التفاضلي)
XMLB operation: Two adjustment screws: high setpoint (trip pressure) and differential (التباطؤ). The low reset point is not independently adjusted.
Specification range for this model:
Rising trip pressure: 0.7~10 bar
Falling reset pressure: 0.13~9.15 bar
Minimum differential 0.57 حاجِز, maximum differential 7.5 حاجِز
Calibration Steps
- Fully depressurize the line.
- Open the front scale cover to access the two adjustment screws with graduated scale.
- Connect a reference pressure gauge (accuracy ≥0.5 class). The built-in scale is only for rough setting.
- Raise pressure slowly while monitoring the reference gauge:
Main adjustment screw: Sets trip pressure. At this pressure, contact state reverses (لا يغلق, يفتح NC).
Differential screw: Sets the pressure gap between trip and reset. Larger differential means greater pressure drop before reset.
- Cycle pressure up and down 2–3 times to confirm stable trip and reset points with no drift.
- Refit protective cover after setting to prevent accidental adjustment. Record values and apply identification label.
✅ Typical example (بدء تشغيل المضخة):
Start at 3 حاجِز, stop at 5 bar → differential = 2 حاجِز. Pump stops at 5 حاجِز, restarts at 3 حاجِز.
ملحوظة: The built-in scale is approximate. Safety interlock applications must be calibrated against a certified reference gauge; accuracy ±2%.
- Commissioning Check
- Confirm no leakage, secure wiring and intact housing sealing.
- Ramp pressure slowly through working range and verify contact switching matches settings.
- Complete multiple cycles to confirm no chattering or rapid cycling.
- Verify contact load stays within rated limits; fit fuse protection for control circuits.
- سِجِلّ: trip pressure, reset pressure, وسائط, ambient temperature and calibration date.
- صيانة
- Routine inspection: تسرب, تلف الكابل, gland water ingress and housing corrosion.
- Calibration interval: 6–12 months for standard air compressor / water pump service; quarterly calibration for safety interlock duty.
- تنظيف: Wipe housing externally only. Do NOT disassemble the process chamber. Diaphragm removal destroys sealing and accuracy.
- Long-term shutdown: Depressurize and drain the chamber. Drain water circuits to prevent corrosion and freezing.
- الحياة الميكانيكية: 5 مليون دورة. Replace at end of life.
- جدول استكشاف الأخطاء وإصلاحها
| أعراض | السبب المحتمل | علاج |
| Switch does not actuate at set pressure | Diaphragm jammed by debris; differential set too large; broken wiring | Depressurize, inspect or replace unit; reset differential; check wiring |
| Rapid cycling / chattering | Differential set too small; pressure pulsation in piping | Increase differential; fit snubber or accumulator |
| Trip pressure drifts out of tolerance | Overpressure shock; diaphragm aging; الاهتزاز المفرط | Replace switch; add vibration dampening and surge protection |
| Water ingress / internal corrosion | Loose gland, missing cover gasket | Reseal assembly; replace unit if sealing parts are damaged |
| Leakage at thread | PTFE tape misapplied; cracked base from over-tightening | Re-seal thread; replace unit if base is cracked |
Telemecanique XMLB Series Electromechanical Pressure Switch – Fault Troubleshooting Guide
For XMLB010A2S11, diaphragm type, تفاضلية قابلة للتعديل, الاتصال الجاف. Always depressurize and isolate power before troubleshooting; test contacts with multimeter continuity mode.
| أعراض الخطأ | السبب الجذري | خطوات التفتيش | Corrective Action |
| No switching when pressure reaches setpoint | 1. Tapping port / impulse line blocked by sludge, scale or debris2. Diaphragm jammed or ruptured3. Setpoint higher than system working pressure4. Internal adjustment thread stripped or spring seized5. Failed microswitch | 1. Depressurize and inspect tapping port2. Use reference gauge to confirm actual system pressure3. Test COM-NO / COM-NC continuity with multimeter | 1. Clear impulse line and add inlet filter2. Reduce trip setpoint and lock screw3. Replace complete unit if diaphragm or internal mechanism is damaged (diaphragm chamber not serviceable on site) |
| Switch fails to reset below reset pressure, contact stays latched | 1. Excessive differential setting2. الاتصال ملحومة / stuck (inductive load without surge suppression)3. Jammed mechanical linkage or fatigued spring4. Trapped pressure in piping, no pressure relief | 1. Test continuity after full depressurization2. Check differential scale and verify relief valve operation | 1. Reduce differential within published range2. Replace switch; add intermediate relay and RC snubber for inductive loads3. Clear piping to enable free pressure relief |
| Rapid cycling / chattering | 1. التفاضلي (التباطؤ) set too low2. Pulsating pressure from pump / compressor3. Insufficient accumulator volume or failed bladder4. Tapping point located in turbulent flow zone | 1. Observe pressure gauge for small fluctuations2. Check current differential setting | 1. Increase differential (XMLB max differential 7.5 حاجِز)2. Fit pressure snubber or buffer tank on impulse line3. Relocate tapping point to straight pipe side wall |
| Trip pressure inconsistent, drifting between cycles | 1. Spring fatigue from repeated pressure shock2. Permanent diaphragm deformation by overpressure3. Extreme temperature or continuous vibration4. Relying only on built-in scale without reference gauge calibration | 1. Compare trip/reset points over multiple cycles against certified gauge2. Check history of exceeding 22.5 bar instantaneous overload | 1. Recalibrate and log values with reference gauge2. Add vibration bracket and heat shielding3. Replace unit if drift persists |
| Intermittent signal loss, unstable contact | 1. Loose terminals or oxidized conductors2. Burned / carbonized microswitch contacts3. Water ingress and terminal corrosion from loose gland4. Internal wiring loose due to vibration | 1. Isolate power, open cover and retighten terminals2. Cycle and test continuity repeatedly | 1. إعادة تشديد المحطات, clean or replace oxidized conductors2. Tighten Pg13.5 gland and check seal for IP663. Replace unit if contacts are burned |
| Media leakage from switch body | 1. PTFE tape trapped inside the thread and scoring diaphragm2. Diaphragm aging / incompatibility with process fluid3. Freeze damage, overtemperature or overpressure4. Cracked base from spanner on plastic housing | 1. Identify leak location: thread joint or housing seam2. Verify process pressure and temperature are within ratings | 1. Re-seal correctly, apply tape only on male thread2. Select wetted material variant compatible with media3. Replace unit if base or diaphragm is damaged |
| Water ingress and internal rusting | 1. Missing or loose gland seal2. Aged cover gasket, unevenly tightened cover screws3. Outdoor installation with direct spray / UV exposure | 1. Open cover and inspect for standing water or oxidation | 1. Replace gasket, tighten cover screws evenly and compress gland seal2. Fit weather shield for outdoor use |
| Repeated contact burnout on power-up | 1. Direct switching of motors / المقاولين, exceeding contact ratingXMLB contact rating: AC-15 240V 1.5A, not for high-power loads2. Unsuppressed inductive arcing | 1. Check load current and separate control circuit from power circuit | 1. Use pressure switch to drive an intermediate relay only; relay switches the load2. Fit RC snubber across inductive coils |
✅ Standard Troubleshooting Sequence
- Process check: Confirm pressure, media and temperature are within rating; verify isolation and relief valves are open and impulse line clear
- Mechanical check: تسرب, اهتزاز, mounting and tapping location
- Setpoint check: Verify trip and differential with certified reference gauge
- Electrical check: Isolate power, test dry contact continuity, check wiring and sealing
- Final decision: Replace complete unit if diaphragm, spring or microswitch fails. No spare internal parts are available for XMLB.
✅ Preventive Guidelines
- Install pre-filter for dirty media to protect diaphragm
- Quarterly calibration for safety interlock circuits; 6–12 months for standard compressor / water pump service
- Never apply spanner force to plastic housing; only grip the hexagonal base
- Use intermediate relay isolation for inductive loads to extend contact life
- Confirm wetted material compatibility: Standard XMLB uses FKM fluoroelastomer; special versions required for aggressive media
Telemecanique Nautilus / OsiSense XM Electromechanical Pressure Switch Series Overview
ملحوظة: XMLA / XMLB / XMLC / XMLD are current main diaphragm / piston pressure and vacuum switches. Legacy XM series (XMJ, XMG, XM2JM, XMP, FYG) are discontinued and only for cross-reference. اتصال قياسي: G1/4 internal ISO228 thread, passive dry contact, control circuit duty, IP66
Model coding rule (XMLB010A2S11 example):
XML [مسلسل] [يتراوح] [Wetted Material] [اتصال / آلية] [Electrical Entry] [إصدار]
S11 = Pg13.5 cable gland, محطات المسمار (XMLB010A2S11); S12=M20 gland; C11=DIN43650 connector
مقارنة السلسلة
| مسلسل | اتصالات | التفاضلي | الميزة الرئيسية | الاستخدام النموذجي |
| XMLA | 1شركة | Fixed differential | Single setpoint, fixed hysteresis, فعالة من حيث التكلفة | ضواغط الهواء, simple alarm, single threshold protection |
| XMLB | 1شركة | Adjustable differential | تحول واحد, adjustable trip+reset, scale plate (النموذج الخاص بك) | Pump start-stop, compressor pressure regulation, lubrication & الأنظمة الهيدروليكية |
| XMLC | 2شركة | Adjustable differential | Two independent changeover contacts, dual adjustable setpoints | Separate low-pressure warning + high-pressure shutdown, التعشيق, pump/fan sequencing |
| XMLD | 2شركة | Fixed differential | Dual independent switch elements, each with fixed hysteresis | Two independent fixed pressure thresholds, safety interlock |
| XMLAM / XMLBM | مكنسة | مُثَبَّت / قابل للتعديل | Negative pressure vacuum switch, -1…0 بار | Vacuum handling, suction lines |
- XMLA (Fixed Differential, 1شركة) قائمة النماذج
| نموذج | يتراوح (حاجِز) | ملاحظات |
| XMLA002A2S11 | 0.25~2.5 | Low pressure air / ماء |
| XMLA004A2S11 | 0.4~4 | إمدادات المياه, التدفئة والتهوية وتكييف الهواء |
| XMLA010A2S11 | 0.7~10 | General air compressor |
| XMLA020A2S11 | 1.2~20 | هيدروليكي, medium pressure pneumatic |
| XMLA035A2S11 | 2.1~35 | Medium pressure hydraulic |
| XMLA070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLA160D2S11 | 9~160 | High pressure hydraulic |
| XMLA300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLA500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLAM01V2S11 | -1~0 | Vacuum switch |
- XMLB (Adjustable Differential, 1شركة, including XMLB010A2S11)
| نموذج | يتراوح (حاجِز) | ملاحظات |
| XMLB002A2S11 | 0.25~2.5 | Low pressure |
| XMLB004A2S11 | 0.4~4 | التدفئة والتهوية وتكييف الهواء & إمدادات المياه |
| XMLB010A2S11 | 0.7~10 | النموذج الخاص بك, popular for compressors & مضخات |
| XMLB020A2S11 | 1.2~20 | Medium pressure pneumatic / hydraulic |
| XMLB035B2S11 | 2.1~35 | Hydraulic power units |
| XMLB070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLB160D2S11 | 9~160 | High pressure hydraulic |
| XMLB300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLB500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLBM02V2S11 | -1~0 | Adjustable vacuum switch |
- XMLC (Adjustable Differential, 2CO Dual Contacts)
| نموذج | يتراوح (حاجِز) | ملاحظات |
| XMLC004B2S11 | 0.4~4 | Dual signal output |
| XMLC010B2S11 | 0.7~10 | 10 bar dual contact, قليل / high pressure alarm |
| XMLC020B2S11 | 1.2~20 | Medium pressure dual output |
| XMLC035B2S11 | 2.1~35 | Hydraulic dual interlock |
| XMLC070D2S11 | 4.5~70 | High pressure dual contact |
| XMLC160D2S11 | 9~160 | High pressure hydraulic |
| XMLC300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLC500D2S11 | 30~500 | Ultra-high pressure hydraulic |
- XMLD (Fixed Differential, 2CO Dual Stage)
| نموذج | يتراوح (حاجِز) | ملاحظات |
| XMLD004B2S11 | 0.4~4 | Dual stage fixed hysteresis |
| XMLD010B2S11 | 0.7~10 | 10 bar dual stage protection |
| XMLD020B2S11 | 1.2~20 | Medium pressure dual stage |
| XMLD035B2S11 | 2.1~35 | Hydraulic safety interlock |
| XMLD070D2S11 | 4.5~70 | High pressure dual stage |
- النماذج القديمة المتوقفة (Cross-reference only, وليس لمشاريع جديدة)
XMJ: Old single setpoint pressure switch, replaced by XMLA
XMG: Old adjustable differential switch, replaced by XMLB
XM2JM: Simple fixed differential auxiliary sensor
XMP / FYG: Old dual setpoint switch, replaced by XMLC
Most legacy XM series discontinued in 2002; stock only available in spare parts market. Prefer XMLB/XMLC for replacement.
- Electrical Suffix Cross Reference (Interchangeable for same range)
S11: Pg13.5 cable gland, محطات المسمار (XMLB010A2S11 standard)
S12: M20×1.5 cable gland, محطات المسمار
ج11: DIN43650 square connector (solenoid valve style)
S13: Special extended housing version
- Wetted Material Code Definition
أ: FKM fluoroelastomer (عام: هواء, clean water, الزيت الهيدروليكي, معيار)
ب: NBR nitrile rubber (mineral oil, not for hot water)
د: الفولاذ المقاوم للصدأ + FKM (الزيت الهيدروليكي, elevated temperature hydraulic)
V: Vacuum grade sealing
- دليل الاختيار السريع
- Single trip point, fixed hysteresis → XMLA
- Adjustable start-stop differential (مضخة / ضاغط) → XMLB (XMLB010A2S11)
- Two independent alarm signals (low warning + high shutdown) → XMLC
- Two independent thresholds, no differential adjustment required → XMLD
- Negative vacuum pressure → XMLAM / XMLBM