Schneider XY2CH13250 Latching Emergency-Stop Rope-Pull Switch

شرح النموذج: XY2CH series, booted push-button reset, 1نك + 1 نو, without indicator lamp; XY2CH13250H29 = cable entry thread changed to M20; standard version is Pg13.5. Comparison with XY2CH13290: 13250 features only one safety NC contact; 13290 adopts dual-channel safety with two NC contacts — this is the core difference. Basic Specifications Item Parameter Contact Configuration 1NC (أمان) ...

  • تفاصيل المنتج

شرح النموذج: XY2CH series, booted push-button reset, 1نك + 1 نو, without indicator lamp; XY2CH13250H29 = cable entry thread changed to M20; standard version is Pg13.5.

Comparison with XY2CH13290: 13250 features only one safety NC contact; 13290 adopts dual-channel safety with two NC contacts — this is the core difference.

المواصفات الأساسية

غرضالمعلمة
تكوين الاتصال1نورث كارولاينا (أمان) +1لا (إشارة), slow‑break positive‑opening contacts
وضع إعادة الضبطDust‑protected manual booted push‑button reset; latches after actuation, no auto‑reset
الأعلى. Rope Length30 م
فئة الحمايةIP65
مواد الإسكانZamak die‑cast zinc‑alloy body, stainless‑steel cover
Cable Entries3 × Pg13.5; H29 suffix variant: 3 × M20
Terminal Tightening Torque0.8‑1.2 N·m, conductor size 0.5‑1.5 mm²
التحمل الميكانيكي800 000 operations; B10d = 4 000 000
درجة حرارة التشغيل‑25 ℃ ~ +70 ℃
Safety Note (single‑channel hardware)To achieve PL e / القطة 4 / SIL3, safety‑relay contact‑short‑circuit monitoring is mandatory. Direct single‑contact wiring max. achieves PL c only.

مهمة المحطة

رقم المحطة.اتصالحالة (non‑actuated)After rope‑pull actuation
21‑22NC Safety Normally‑ClosedClosedيفتح (positive opening)
13‑14NO Signal Normally‑OpenيفتحClosed

⚠️ Critical: Only one safety NC contact; no second hardware safety channel.

الحالة الطبيعية: 21-22 مغلق, 13-14 يفتح. Pulling the rope triggers mechanical latching: 21-22 opens, 13-14 يغلق. Restore by pressing the blue reset push-button.

Wiring Schemes

Scheme 1: High-Safety Level (PL e requires safety-relay monitoring)

  1. سلك 21-22 (نورث كارولاينا) to one input channel of safety relay.
  2. سلك 13-14 (لا) to PLC DI for alarm feedback signal.

Since the hardware provides only one NC channel, Category 4 / PL e can only be achieved when the safety relay implements contact short-circuit monitoring. Without monitoring, max achievable safety level is PL c.

❗Do NOT externally parallel contacts; hardware only supplies one safety contact.

Scheme 2: Low-risk general-purpose equipment (PL e not satisfied)

سلك 21-22 in series into equipment emergency-stop circuit; 13-14 for alarm feedback.

Suitable for light-duty general-purpose conveyors. Strictly prohibited for high-risk conveyor systems.

احتياطات الأسلاك

  1. Use only one cable entry; fit sealing plugs on the remaining two unused entries, otherwise IP65 protection is lost.
  2. Connect metal housing reliably to PE protective earth.
  3. Tighten terminals strictly to 0.8-1.2 N·m to avoid loose connections.

التركيب الميكانيكي

Mechanical installation requirements are identical to XY2CH13290. Refer to the full installation manual below:

  1. Max rope span 30 m; use φ3-5 mm plastic-coated steel wire rope.
  2. End-position tension spring is mandatory. Rope breakage shall also trigger emergency stop.
  3. First deflection pulley shall be mounted 100 mm away from switch body. Install rope clamps/support points every 5 m.
  4. Mount onto rigid metal brackets only; allow slight rope sag — do not over-tension nor allow excessive slack.

Pre-power-on Commissioning (de-energised, multimeter test)

  1. Reset completed: 21-22 مغلق, 13-14 يفتح.
  2. Pull rope to trigger latching: 21-22 يفتح, 13-14 مغلق.
  3. Press reset push-button to restore contact states.
  4. Test actuation at multiple positions all along the rope path to confirm reliable triggering even at far-end positions.

مقارنة النماذج: XY2CH13250 vs XY2CH13290

نموذجتكوين الاتصالSafety Channelتطبيق نموذجي
XY2CH132501نك + 1 نوSingle‑channelLow‑risk equipment, cost‑optimised; safety‑relay monitoring required for high‑level safety
XY2CH132902نك + 1 نوDual‑channel on‑boardسيور ناقلة, high‑risk material‑handling lines; industry‑preferred variant for direct dual‑channel safety‑relay input

Selection Reminder: Prefer 13290 for belt conveyors and heavy-duty lines; 13250 is acceptable for light-duty general-purpose machines.

Equivalent Replacement Models

  1. إبداعي شنايدر variant: XY2CH13250H29 (M20 thread version)
  2. البدائل المحلية:

ELCO SR1-SN (1نك + 1 نو)

Schmersal ZQ700-11

استكشاف الأخطاء وإصلاحها الشائعة

  1. Unintended nuisance tripping: Excessive rope tension, bracket vibration. Reduce tension via turnbuckle; reinforce mounting structure.
  2. No actuation from far-end pull: Insufficient rope tension, seized deflection pulleys. Adjust tension; service pulleys.
  3. Cannot reset after tripping: Persistent tensile load remains on rope. Release rope residual tension before pressing reset button.

نوع المنتج: Latching emergency-stop rope-pull safety switch. Pulling the steel wire rope triggers emergency stop with mechanical latching; manual reset is mandatory. Applied to long-run conveyors, خطوط التجميع, آلات التعبئة والتغليف, belt conveyors and other machinery safety protection.

General Core Specifications

غرضالمعلمة
فئة الحمايةIP65
الأعلى. Rope Length30 م
التحمل الميكانيكي800 000 operations
Body MaterialZamak die‑cast zinc alloy, stainless‑steel cover
Cable Entries3 × Pg13.5 (M20 for certain variants), محطات المسمار
Terminal Torque0.8‑1.2 N·m
تصنيف السلامةPL e / القطة 4 / SIL3 (requires compatible safety relay and correct wiring)
Contact CharacteristicsSlow‑break, positive‑opening safety contacts
Housing ColourRed RAL 3000

Model Naming & Main XY2CH Variants

XY2CH + numeric suffix. Suffix defines contact configuration, reset type, pilot-lamp option and thread specification.

  1. Reset Types

131xx: Flat push-button reset

132xx: Booted dust-protected push-button reset (most common industrial type)

134xx: Key-operated reset

  1. Contact Configurations

XY2CH13250: 1نك + 1 نو, booted push-button reset

XY2CH13270: 2نورث كارولاينا, dual safety normally-closed contacts

XY2CH13290: 2نك + 1 نو (most popular; 2 safety NC + 1 signal NO)

XY2CH13450: 1نك + 1 نو, key-reset

XY2CH13293: 2نك + 1 نو, with 24 V pilot lamp

Suffix H29 = cable-entry thread changed to M20; default = Pg13.5.

مبدأ التشغيل

  1. Pull steel wire rope → internal mechanism latches mechanically; safety NC contacts positive-open.
  2. Machine shuts down; no automatic reset.
  3. After fault clearance, reset via push-button / key; contacts restore for machine restart permission.

⚠️ Note: Rope-run ends must be fitted with tension springs, rope clamps and deflection pulleys. Avoid over-tightening or excessive slack. Rope-clamp spacing ≤ 5 m recommended.

التطبيقات النموذجية

سيور ناقلة, خطوط الإنتاج, packaging lines, sorting systems, long workstations, mining conveying equipment. Operators can trigger emergency stop by pulling the rope anywhere along the protected span.

XY2C Family Series Differentiation

XY2CH: Zamak zinc-alloy body, stainless-steel cover, max 30  m rope length, IP65, high mechanical endurance.

XY2CE: Plastic housing, economy-grade, max 2 × 50  m bidirectional rope pull.

XY2CJ: Higher-grade IP66/IP67 protection for heavy-dust and wash-down environments.

Domestic-brand Reference Replacements

ELCO: SR-series rope-pull E-stop switches

اومرون: D4A-N rope-pull switches

Contrinex / Schmersal: ZQ-series rope-pull safety switches

General Fault-Finding

  1. Frequent nuisance tripping: Excessive rope tension, seized pulleys, deformed mounting brackets.
  2. فشل إعادة الضبط: Mechanism jammed; residual rope tension not released.
  3. Open-circuit safety loop: Loose terminals; verify tightening torque 0.8-1.2 N·m.

Schneider XY2CH13290 (Telemecanique Rope-Pull Emergency-Stop Switch)

اتصالات: 2نك + 1 نو, booted push-button reset, no pilot lamp; max rope length 30  m; IP65; Pg13.5 cable entries. Suffix H29 = M20 thread.

  1. مهمة المحطة
رقم المحطة.Contact Propertyغاية
21‑22NC#1 (Safety Normally‑Closed 1)Safety‑loop channel 1, positive‑opening
31‑32NC#2 (Safety Normally‑Closed 2)Safety‑loop channel 2, positive‑opening
13‑14لا (Normally‑Open)PLC alarm / status feedback signal

Non-actuated state: 21-22 مغلق, 31-32 مغلق, 13-14 يفتح.

Rope-pull latching: 21-22 و 31-32 open simultaneously; 13-14 يغلق. Reset only via blue local push-button.

  1. Wiring Schemes

Scheme A: Safety-relay connection (achieve PL e / القطة 4 / SIL3 — Recommended)

  1. Feed independent dual NC channels 21-22 و 31-32 separately into dual-channel safety-relay inputs. Never externally short-circuit the two NC contacts — this invalidates safety rating.
  2. سلك 13-14 NO contact to PLC digital input for rope-pull-triggered alarm.
  3. عزم الدوران الطرفي: 0.8-1.2 ن · م. موصل: 0.34-1 mm² single-wire / max 0.75 mm² for two-wire parallel.
  4. Cable glands: 3 × Pg13.5; use one only; seal remaining two with blanking plugs to preserve IP65.

Scheme B: Simplified stand-alone wiring (PL e not satisfied, for basic stop-function only)

Wire both NC contacts in series into emergency-stop circuit; NO for alarm output. Cannot reach Category 4; only for low-hazard machinery.

⚠️ هام: This is a mechanically latched device. It will NOT auto-reset after rope-pull actuation; manual push-button reset is required.

  1. Mechanical Installation Key-Points
  2. Steel wire rope: φ3-5 mm plastic-coated; max total length 30  m; fit tension springs at both ends.
  3. Rope clamps: install every ≤ 5  m; add deflection pulleys to prevent rope-to-housing friction.
  4. Rope tension: avoid over-tightening (nuisance tripping) and excessive slack; permit minor sag.
  5. قوس التثبيت: rigid metal construction; no flexible supports. Switch can accept rope entry from left or right side.
  6. درجة الحرارة المحيطة: −25 ℃ ~ +70 ℃.
  7. الأبعاد الشاملة (مم)

جسم: W 68 × H 95 × D 201 (including reset button and rope-pull lever mechanism)

فتحات التركيب: two M8 mounting holes on both sides.

  1. Original Schneider Equivalent-variant Selection Table
نموذجاتصالاتإعادة ضبطCable‑entry Threadملاحظات
XY2CH132702نورث كارولايناBooted push‑buttonPg13.5Pure dual‑safety‑channel, no NO signal contact
XY2CH132501نك + 1 نوBooted push‑buttonPg13.5Single safety channel
XY2CH132932نك + 1 نوBooted push‑buttonPg13.5With 24 V pilot lamp
XY2CH134902نك + 1 نوKey‑resetPg13.5Key‑unlock required for reset
XY2CH13290H292نك + 1 نوBooted push‑buttonم20Thread changed to M20
  1. Pin-to-pin Compatible Domestic Replacements
  2. Schmersal ZQ 900-22 (2نك + 1 نو, push-button reset)
  3. ELCO SR2-SN (2نك + 1 نو)
  4. Contrinex SN21-RPL-30M

Replacement reminder: Verify contact configuration, reset type, max rope length and protection rating.

  1. استكشاف الأخطاء وإصلاحها
  2. Frequent nuisance tripping: Excessive rope tension, seized pulleys, deformed brackets, heavy machine vibration. Reduce rope tension; inspect deflection pulleys.
  3. Cannot reset after tripping: Residual rope tension keeps mechanism locked. Release rope tension before pressing reset button.
  4. Intermittent open safety circuit: Under-torqued terminals. Retighten terminals to 0.8-1.2 N·m; re-crimp conductors.
  5. Water ingress damage: Unused cable entries not sealed with blanking plugs.

Complete Installation Operating Guide for Schneider XY2CH-Series Rope-Pull Emergency-Stop Switches

نماذج قابلة للتطبيق: XY2CH13290, XY2CH13270, XY2CH13250 etc. Complies with EN/ISO 13850, IEC 60947-5-5, Machinery-Safety Directives.

⚠️ Safety Precondition: Perform all installation, wiring and commissioning with equipment de-energised under Lock-Out-Tag-Out (قلب). This is a tension-type rope-pull switch; proper pre-tension is required. Rope breakage shall also trigger emergency-stop protection.

  1. التحضير قبل التثبيت

1.1 أدوات & Accessories List

فئةمحتوى
أدواتM8/M6 spanner, cross‑head screwdriver, torque screwdriver, المتر المتعدد, wire cutters
Mandatory Accessoriesφ3‑5 mm plastic‑coated steel wire rope, rope clamps, deflection pulleys, end‑position tension spring (mandatory), turnbuckle, rigid metal mounting brackets, sealing blanking plugs
Electrical Cables0.34‑1 mm² control cables; terminal torque 0.8‑1.2 N·m; PE protective‑earth conductor for metal housing

1.2 Environmental Verification

  1. درجة حرارة التشغيل: −25 ℃ ~ +70 ℃; IP65 rating. Avoid heavily corrosive and high-impact locations.
  2. Max effective rope-protected length 30  m. Install an additional rope-pull switch if span exceeds this limit.
  3. Operating rope height above ground: 0.6-1.1 م, easily reachable by personnel; no obstacles obstructing the rope path.
  4. All mounting brackets must be rigid metal. Thin-sheet / flexible supports are forbidden; vibration will cause false triggering.
  5. Mechanical-body Mounting Procedure
  6. Secure the switch body

Fasten with M8 bolts through the two side mounting holes onto rigid machine frame; tightening torque 4 N·m. Align switch rope-exit direction with rope routing; do not twist the rope-pull lever mechanism.

Maintain 100 mm distance between switch body and first deflection-support point. Larger distance causes insufficient actuation stroke.

  1. Fit deflection pulleys

Fit deflection pulleys wherever the rope changes direction. Total deflection-angle sum ≤ 180°. Sharp bends and hard kinks are prohibited.

Install support / rope-clamp assemblies every 5 m along straight runs to limit rope sag.

Pulleys shall rotate freely without binding. Rope must not rub against machine frames or enclosures.

  1. Steel-wire-rope & end-spring assembly (خطوة حاسمة)

1) Attach one rope end to the XY2CH rope-pull eyelet.

2) Thread rope through all deflection pulleys.

3) Fit end-position tension spring at the far rope end. Anchor the spring’s opposite end to rigid machine frame. Omission of this spring is a major safety hazard — pulling towards the switch will fail to trigger E-stop.

4) Secure rope with at least two rope clamps. Do not clamp over the sheath-stripping transition zone.

5) Adjust total rope tension via turnbuckle: keep rope moderately taut with minor sag. Do not over-tighten; do not allow excessive slack.

Over-tension: vibration-induced nuisance tripping. Under-tension: no reliable actuation from far-end positions.

  1. Mechanical acceptance check

Rope free of twist, kinks and abrasion. Avoid large-area sheath stripping to prevent corrosion.

Full-rope-travel movement is smooth without binding.

يؤكد: rope breakage will cause spring retraction and trigger emergency-stop.

  1. Electrical Wiring Procedure

XY2CH13290 terminals: 21-22 NC1; 31-32 NC2; 13-14 لا. Metal housing includes PE earth terminal. Housing must be reliably connected to PE protective earth.

  1. Remove four cover screws and open housing.
  2. Cable-entry handling:

Standard units: 3 × Pg13.5 threaded entries; H29 variants: م20.

Use only one entry for control-cable feed-through. Tighten original sealing blanking plugs on the other two unused entries (torque 1 N·m). Failure destroys IP65 protection and causes water ingress.

  1. الأسلاك الطرفية (for PL e / القطة 4 / SIL3 safety-loop):

Feed dual safety NC contacts 21-22 و 31-32 into separate safety-relay dual-channel inputs. Never externally short-circuit the two NC contacts — safety rating will be lost.

سلك 13-14 NO contact to PLC input for rope-pull-trigger-alarm signal.

المقطع العرضي للموصل: single-wire 0.34-1 mm²; max 0.75 mm² for two-wire parallel. Terminal tightening torque 0.8-1.2 N·m.

  1. Connect PE protective-earth wire to housing earth terminal for EMC and shock-hazard protection.
  2. Refit cover and evenly tighten four cover screws.

❗Simplified wiring (not for high-hazard machinery): Series-connect both NC contacts into general-purpose emergency-stop circuit. This provides only basic stop-function and does not achieve Category 4 safety rating. For low-risk equipment only.

  1. Pre-power-on Static Commissioning (de-energised, multimeter measurements)
  2. Normal reset-completed state

Multimeter readings: 21-22 مغلق, 31-32 مغلق; 13-14 يفتح.

  1. Manually pull rope to trigger mechanical latching

Multimeter readings: 21-22 يفتح, 31-32 يفتح; 13-14 مغلق.

Latching is maintained; contacts will not auto-recover.

  1. Press blue booted reset push-button; contacts return to initial status.
  2. Simulate actuation at multiple positions along rope path: near switch, mid-span and far-end. Reliable latching actuation must occur at every position.

Poor far-end actuation: reduce rope tension or check for seized pulleys.

  1. Simulate rope breakage: spring retraction must trigger emergency-stop latching.
  2. Live-machine Functional Test
  3. Energise machine and safety-relay system.
  4. Test 1: Pull rope near switch → controlled machine shutdown; safety-relay fault indication. Manual reset at switch body AND safety-relay reset are required before machine restart. No automatic-power-on after supply restoration permitted.
  5. Test 2: Pull rope at mid-span and far-end positions. Confirm controlled emergency-stop at all points.
  6. Test 3: Verify PLC alarm signal (13-14 لا) correctly reports rope-pull-trigger events.
  7. Installation Acceptance Criteria
  8. ميكانيكية: Rigid mounting brackets, free-running pulleys, intact tension springs, correct rope tension, no mechanical interference or friction.
  9. حماية: All unused cable entries sealed with blanking plugs; cover screws tightened; PE-earth connection intact.
  10. كهربائي: Dual-channel NC contacts fed independently to safety-relay inputs (no external short-circuit). Multimeter test sequences fully compliant.
  11. وظيفية: Reliable latching E-stop from any rope-span position; manual-only reset; rope-break triggers emergency-stop.
  12. Installation-related Fault-Finding Table
ظاهرة الخللالسبب الجذريالإجراء العلاجي
Random uncommanded trippingExcessive rope tension; vibrating pulleys / brackets; insufficient bracket rigidityReduce tension via turnbuckle; reinforce supports; service seized pulleys
No actuation from far‑end rope positionsInsufficient rope tension; excessive distance to first support point; seized pulleysAdjust rope tension; set first support at 100  mm; repair pulleys
Cannot reset after trippingPersistent tensile load remains on ropeRelease residual rope tension before pressing reset button
Intermittent safety‑loop continuityUnder‑torqued terminals, loose conductorsRetighten terminals to 0.8‑1.2 N·m; re‑terminate conductors
Water‑induced device damageUnused cable entries without blanking plugsFit original sealing plugs on all unused threaded entries
  1. Periodic-maintenance Requirements (to be documented in machine-maintenance manual)
  2. Weekly visual inspection: rope abrasion, loose rope clamps, deformed springs, loose mounting brackets.
  3. Monthly full-functional test: trigger emergency-stop at multiple rope-span positions.
  4. Quarterly inspection: re-verify terminal torque and PE-earth integrity; inspect rope-sheath wear.
  5. Immediately replace steel-wire rope if wire-strand breakage or sheath damage is observed.

Supplementary note: XY2CH shall not be treated as a general-purpose limit switch. Permanent rope anchoring without end-position tension spring constitutes a serious safety violation.