PHNIX PC4001 is a main controller / control board designed for equipment including air-to-water heat pumps
Conclusion: Yes, but there are two approaches — directly replace the original control board, or use the PC4001 (PLC) to fully rewrite the control program.
The Pentair PASRW130S-U-T3-60 is a 55kW swimming pool / industrial heat pump / water chiller unit (with heat recovery, T3 operating condition, 60Hz model). It comes factory-fitted with a dedicated PC4001 heat pump controller (not the Phoenix Contact RFC 4001 PLC). Your question is: Can the Phoenix Contact RFC 4001 (PLC) be programmed to control this 55kW unit?
- First, distinguish between the two “PC4001” units (critical)
Original PC4001 (dedicated heat pump board)
The factory-installed controller for your unit: dedicated temperature control board for swimming pools and heat pumps
Built-in functions: cooling / heating / defrosting / 4-way valve / fan / water pump / protection logic
Interfaces: temperature probes (NTC/PT1000), high/low pressure switches, water flow switch, compressor, fan, 4-way valve, water pump, alarm output
Cannot be programmed with PLC software; parameters can only be set via the control panel or RS485 communication
Phoenix Contact RFC 4001 (PLC)
General-purpose PLC, requires matching I/O modules
Can fully replace the original PC4001 and control this 55kW unit with custom programming
- Key control requirements for the Pentair PASRW130S-U-T3-60 (55kW)
Compressor: 55kW, 380V/60Hz, star-delta starting (KM1/KM2/KM3)
Operating modes: cooling / heating / automatic / defrosting
Controlled devices:
Compressor (star-delta)
Condenser fans (1–2 units)
Evaporator / water pump
4-way valve (cooling/heating switching)
Water flow switch, high/low pressure protection, oil pressure differential, discharge temperature, anti-freeze protection
Sensors:
Inlet water temperature, outlet water temperature, ambient temperature, discharge temperature, coil temperature (NTC/PT1000)
High pressure switch, low pressure switch (normally closed), water flow switch
- Hardware configuration for Phoenix Contact RFC 4001 (ready for direct use)
Controller: RFC 4001 (PC4001)
Digital Inputs (DI, 10 points): IB IL 24 DI 16
High pressure switch, low pressure switch, oil pressure differential, water flow, phase sequence, emergency stop, local/remote switch, start command, stop command, defrost request
Analog Inputs (AI, 5–6 points): IB IL AI 4/I + IB IL PT4
Inlet water temperature, outlet water temperature, ambient temperature, discharge temperature, evaporation/condensation temperature, high pressure sensor (optional)
Relay Digital Outputs (DO, 8–10 points): IB IL 24 DO 16-R
Compressor KM1, KM2 (star), KM3 (delta), condenser fan 1, condenser fan 2, water pump, 4-way valve, alarm output, defrost valve (optional)
- Control logic (directly programmable in PLC)
- Start conditions
No alarms for high pressure / low pressure / oil pressure differential / water flow / phase sequence / emergency stop
Valid start command received
- Mode control
Cooling: 4-way valve de-energized
Heating: 4-way valve energized
Automatic: auto-switching based on water temperature
- Sequence (standard heat pump)
Start → run water pump / fans first → time delay → star-delta start of compressor
Stop → stop compressor first → time delay to close valves / stop fans / stop water pump
- Protection (immediate shutdown)
High pressure, low pressure, oil pressure differential, loss of water flow, phase sequence error, high discharge temperature, anti-freeze protection, sensor fault
- Defrost logic (heating mode)
Enter defrost based on timer + coil temperature conditions
Reverse 4-way valve, run compressor, stop fans, open defrost valve
Exit defrost when temperature setpoint or timer is reached
- Feasibility and risks
✅ Fully feasible
The RFC 4001 can implement all functions: 55kW star-delta control, I/O quantity, protection logic, mode switching
Ladder Diagram (LD) / Function Block Diagram (FBD) programming in PC Worx, consistent with standard water chiller/heat pump program structure
⚠️ Important notes
60Hz: Adjust program time delays and protection parameters for 60Hz operating conditions
T3 condition: Adapt high pressure protection setpoints and fan control logic for high-temperature environments
Original protocol: Cannot directly read data from the original PC4001; full disconnection and re-wiring of I/O is required
Certifications: CE/UL certifications for the unit will need re-evaluation after replacement (generally acceptable for industrial in-house use)
- Recommended solutions
- Keep the original PC4001
Stable, no programming required, adjustable parameters via control panel
Disadvantage: no customizable logic, only monitoring via RS485
- Rewrite control with Phoenix Contact RFC 4001 (your intended solution)
Advantages: fully customizable logic, integration with upper computers / IoT, multi-unit linkage, advanced protection
Implementation: program according to the above I/O list, wiring and logic; fully capable of controlling this 55kW PASRW130S
- Short answer
Yes.
The Phoenix Contact RFC 4001 (PLC) can be fully programmed to control the Pentair PASRW130S-U-T3-60 (55kW) by programming the unit’s I/O points, star-delta sequence, operating modes and protection logic.
- Core conclusion (clear and definitive)
- The PC4001 installed on your unit
is a Pentair dedicated heat pump controller,
→ cannot be programmed with PLC software; only parameter adjustment via panel and RS485 communication is available.
- If your question is: Can the Phoenix Contact RFC 4001 (PLC) control this 55kW unit?
→ Absolutely yes, with full functionality.
You may remove the original control board and use the Phoenix Contact PC4001 PLC with custom programming to control this Pentair 55kW water chiller / heat pump unit.
Why is it possible? (Key matching points)
The Phoenix Contact RFC 4001 fully meets the control requirements of this PASRW130S 55kW unit:
Controls 55kW compressor star-delta starting ✅
Controls condenser fans, water pump, 4-way valve ✅
Reads high/low pressure switches, water flow, phase sequence, emergency stop ✅
Reads NTC/PT1000 temperature probes (inlet/outlet/discharge/ambient) ✅
Implements cooling/heating/automatic/defrost logic ✅
Implements complete protection logic (high pressure, low pressure, oil pressure differential, anti-freeze, overload) ✅
Supports Modbus remote monitoring ✅
In short:
Sufficient hardware, sufficient I/O, programmable logic, compatible power rating.
Can the original PC4001 be programmed directly?
No.
The original PC4001 is a dedicated fixed-program controller, not a programmable PLC.
It cannot be programmed with software such as PC Worx or Codesys.
One-sentence summary
To use the Phoenix Contact RFC 4001 PLC with custom programming to control this Pentair 55kW unit:
Yes, fully feasible — a common retrofit solution in engineering.
To program the on-board PC4001 panel directly:
No, it is not a programmable logic controller.