ABB HPA24/612C 24kV indoor SF6 medium voltage circuit breaker

ABB HPA24/612C is a 24kV indoor SF6 medium voltage circuit breaker with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.

ABB HPA24/612C is a 24kV indoor SF6 Mittelspannungs-Leistungsschalter with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.

  1. Erklärung des Modellcodes
CodesegmentBedeutungBeschreibung
HPAProduktseriencodeABB indoor SF6 medium voltage circuit breaker series, sharing the same platform with HD4 series, applicable for SafeSix switchgear
24Rated voltage level24kV (IEC-Standard, matching domestic 24kV power system)
612Combination of current and breaking capacity6 stands for 630A rated current; 12 stands for 12.5kA rated short-circuit breaking current
CStruktur & configuration codeStandardkonfiguration, fixed type or withdrawable type (depends on switchgear type)
  1. Technische Kernparameter (2026 Official Manual Version)
ParameterWertStandard BasisBemerkungen
Nennspannung (Un)24kVIEC 62271-100Maximale Betriebsspannung: 27.5kV
Nennstrom (Und)630AIEC 62271-100Continuous operation at ambient temperature 40℃
Rated Short-circuit Breaking Current (Isc)12.5DieIEC 62271-1003-second short-circuit withstand
Bewerteter Kurzzeitstrom (Icw)12.5kA/3sIEC 62271-100Thermal stable current
Rated Peak Withstand Current (Ipk)31.5DieIEC 62271-100Dynamic stable current
BetriebsmechanismusSpring energy storageIEC 62271-100Handbuch / electric operation optional
Insulating MediumSF6 gasIEC 62271-100Rated pressure: 0.45MPa @20℃
SchutzgradIP4XIEC 60529Cabinet installation condition
Mechanische Ausdauer10,000 OperationenABB technical specificationStandard operation cycle
Elektrische Ausdauer100 malIEC 62271-100Rated short-circuit breaking times
GewichtCa. 85kgABB technical specificationExcluding accessories
Order Number1VYN400551-XXXOfficial ABBSubject to actual configuration
  1. Cross-brand Compatibility Comparison (MV SF6 Circuit Breaker)
ABB ModelSchneiderSiemensEatonTechnical Differences
HPA24/612CMVnex 24/630-12.53AH4 24kV/630A/12.5kAPower Xpert 24kV/630A/12.5kAABB HPA series adopts SF6 insulation and spring mechanism, fits SafeSix switchgear
Ersatz: VD4-24/630-16HVX 24/630-163AH5 24kV/630A/16kAPower Xpert 24kV/630A/16kAVD4 adopts vacuum insulation with 30,000 mechanical operations and superior environmental performance
  1. Full HPA Series Model List
ModellNennspannungNennstromBruchkapazitätAnwendungsszenarien
HPA12/616C12kV630A16DieIndustrielle Stromverteilung, substation
HPA12/620C12kV630A20DieSchwerindustrie, large factories
HPA12/1225C12kV1250A25DieRegional substation, power plant
HPA12/1631C12kV1600A31.5DieLarge industrial users, hub substation
HPA24/612C24kV630A12.5Die24kV power distribution system, small substation
HPA24/616C24kV630A16Die24kV power distribution system, medium-sized factories
HPA24/1220C24kV1250A20Die24kV regional substation
HPA24/1625C24kV1600A25Die24kV large industrial projects
HPA36/616C36kV630A16Die36kV power distribution system
  1. Häufige Fehler & Wartungsrichtlinien
FehlerphänomenMögliche UrsachenSchritte zur FehlerbehebungWartungsvorschläge
Fehler beim Schließen1. Incomplete energy storage1. Check energy storage indicator1. Test manual energy storage
2. Abnormal control voltage2. Measure control circuit voltage (DC220V/AC220V)2. Repair control circuit fault
3. Interlock not released3. Inspect mechanical interlock status3. Adjust interlock device
Failure to open1. Burnt trip coil1. Measure coil resistance (Normal: approx.100Ω)1. Replace trip coil
2. Tripping mechanism stuck2. Test manual opening operation2. Clean and lubricate tripping mechanism
3. Low SF6 gas pressure3. Check SF6 pressure gauge (≥0.4MPa)3. Refill gas or inspect air leakage
SF6 gas leakage1. Aging sealing parts1. Detect leakage with SF6 leak detector1. Replace sealing components
2. Loose connectors2. Check all connecting parts2. Fasten connectors
3. Shell crack3. Observe shell appearance3. Replace shell for severe damage
Excessive contact resistance1. Contact wear1. Kontaktwiderstand messen (≤50μΩ)1. Replace contacts
2. Dirty contact surface2. Inspect contact surface2. Clean contact surface
3. Loose connecting bolts3. Check bolt tightening torque3. Fasten bolts per standard torque
  1. Anwendungsumgebung & Branchenfälle

6.1 Anwendbare Szenarien

24kV industrial power distribution system (chemisch, Metallurgie, mining industry)

Secondary substation of urban power grid

Commercial buildings and infrastructure (airport, hospital, data center)

Renovation projects matching SafeSix switchgear

6.2 Nicht anwendbare Szenarien

Altitude above 2000m (derating required, Derating-Faktor: 0.9 per 1000m)

Severe corrosive environment (seaside, chemical zone, special anti-corrosion treatment required)

Frequent short-circuit breaking operation (überschreiten 10% of rated breaking times)

Areas with strict environmental requirements (SF6 has strong greenhouse effect, VD4 vacuum circuit breaker is preferred)

6.3 Typische Anwendungsfälle

Fall 1: 24kV Power Distribution Renovation for Chemical Plant

Anwendung: Replace old oil-minimum circuit breakers to improve power supply reliability

Lösung: 8 sets HPA24/612C matched with ABB REF542 protection relay

Effect: Fault outage duration reduced by 80%, maintenance cost cut by 50%

Fall 2: 24kV Traction Substation for Urban Rail Transit

Anwendung: Protection for traction transformer and feeder line

Lösung: 4 sets HPA24/612C with withdrawable structure for quick replacement

Effect: Meet high reliability requirements of rail transit, MTTR<30 minutes

  1. Luftfracht-Compliance & Zertifizierungsinformationen

7.1 Luftfracht-Compliance

Hazard Classification: Non-dangerous goods (no lithium battery, no explosive materials)

IATA Shipping Category: Stückgut

Packaging Standard: Comply with ISTA 3A standard to avoid SF6 seal damage caused by transportation vibration

Notiz: Close SF6 inflation valve during transportation to prevent gas leakage

7.2 Zertifizierungsdokumente

CE Certificate No.: 1YHA000091 (universal for HPA series)

IEC Standard Approval: IEC 62271-100:2017

China National Standard Approval: GB 1984-2014 High-voltage Alternating Current Circuit-breakers

Environmental Certification: SF6 gas recovery complies with IEC 62271-4

  1. Modellauswahl & Replacement Suggestions
  2. Modellbestätigung: HPA series is fully discontinued. It is recommended to contact ABB customer service 400-810-8888 and provide nameplate photos to confirm detailed configuration.
  3. Ersatzlösungen

Erste Wahl: VD4-24/630-16 (vacuum type, 30,000 mechanische Operationen, SF6-free eco-friendly design)

Alternative choice: HD4-24/630-16 (SF6 type, same platform as HPA, direct replacement without switchgear modification)

  1. Ersatzteilbeschaffung: Limited stock of HPA series spare parts. Pre-order via authorized ABB distributors in advance or plan overall equipment upgrading.

ABB HPA24/612C is a 24kV indoor SF6 medium voltage circuit breaker with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.