The ACS580-01-087A-4 is a standard wall-mounted single drive unit from ABB’s ACS580 series, rated for three-phase 380–480V AC input. This drive series features user-friendly operation, high reliability and superior energy efficiency as core advantages. Multiple standard built-in functions eliminate the need for extra optional components, enabling rapid commissioning and deployment. Widely compatible with general industrial loads such as pumps, Fans, conveyors and mixers, it is the preferred solution for light industry, Gebäude-HLK, water treatment and other applications.
Breakdown of Model Code
Per ABB official naming convention, each segment of the model designation is defined as follows:
ACS580: Kennung der Produktserie, representing ABB’s general-purpose standard drive series covering power ratings from 0.75kW to 500kW
-01: Construction type, standing for wall-mounted standard single drive. Standard equipment includes IP21 enclosure rating, Assistant Control Panel, built-in Class C2 EMC filter, Sicher abgeschaltetes Drehmoment (STO), braking chopper and triple-protection coated circuit boards
-087A: Rated output current marking, indicating the nominal rated output current of the drive is 87A
-4: Spannungsklasse, denoting three-phase 380V–480V AC input, compatible with 50/60Hz mains power grids
Grundlegende technische Spezifikationen
Electrical Ratings
| Parameter | Spezifikation | Bemerkungen |
| Eingangsspannungsbereich | 3-phase AC 380V ~ 480V | Toleranz: +10% / -15% |
| Eingangsfrequenz | 50/60Hz | Toleranz: ±5 % |
| Nennausgangsstrom | 87A | Nominal value for light-duty applications |
| Passende Motorleistung (Leichte Beanspruchung) | 45kW | For variable-torque loads (Fans, Wasserpumpen) |
| Passende Motorleistung (Robust) | 37kW | For constant-torque loads (vermitteln, mixing) |
| Ausgangsfrequenzbereich | 0 ~ 500Hz | Supports high-speed motor operation |
| Input Power Factor | ≥0.98 | High power factor across full power range |
| Overall Efficiency | ≥98% | At rated operating conditions |
| Überlastfähigkeit | 150% Nennstrom für 60s | One overload cycle permitted every 10 Minuten |
| 110% rated current continuously |
Kontrolle & Interface Specifications
Motor Control Modes: Scalar V/F control, sensorless vector control; compatible with induction motors, permanent magnet synchronous motors and synchronous reluctance motors
Physikalische Dimensionen & Umweltspezifikationen
Rahmengröße: R5
Gesamtabmessungen (H × W × D): 896mm × 345mm × 293mm
Nettogewicht: Ca. 23kg
Enclosure Rating: IP21 (Standard); IP55 high-protection version available as option
Montageart: Wandmontage, side-by-side compact installation supported
Betriebsumgebungstemperatur: -15℃ ~ +50℃ (Über 40℃ ist eine Leistungsreduzierung erforderlich)
Lagerung & Transport Temperature: -40℃ ~ +70℃
Relative Luftfeuchtigkeit: 5% ~ 95%, nicht kondensierend
Altitude Rating: Full power output up to 1000m; 1% power derating per additional 100m above 1000m
HS-Code: 85044088
Standardkonfiguration & Optionales Zubehör
Factory Standard Equipment
- ACS-AP-S Assistant Control Panel (Chinese language supported)
- Built-in Class C2 EMC Filter
- Integrated Braking Chopper
- Sicher abgeschaltetes Drehmoment (STO) Funktion
- Triple-protection Coated Printed Circuit Boards
- Bottom Cable Entry Compartment
- Multilingual Quick Installation & Inbetriebnahmehandbuch
Common Optional Accessories
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus TCP
Electrical Options: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, temperature sensor interface cards, NETA-21 remote monitoring module
Software Tools: Drive Composer professional commissioning software
Typische Anwendungsszenarien
Wasseraufbereitungsindustrie: Clean water pumps, sewage pumps, aeration fans, sludge mixers
Building HVAC: Chilled water pumps, cooling water pumps, supply & exhaust fans for central air conditioning
Leichte Fertigung: Bandförderer, packaging production lines, mixing & Mischgeräte, Luftkompressoren
Metallurgie & Bergbau: Dust extraction fans, material transport belts, mine drainage pumps
Kommunalingenieurwesen: Water supply pumping stations, ventilation systems for wastewater treatment plants
Common Troubleshooting Matrix
| Fehlerphänomen | Grundursachen | Step-by-Step Remedial Actions |
| Overcurrent Trip (Fehlercode 0001) | Short circuit in motor/cables, sudden load surge, overly short acceleration time | 1. Cut power and test insulation & wiring of motor and power cables |
| 2. Appropriately extend acceleration time parameter | ||
| 3. Verify consistency between motor rated parameters and drive settings | ||
| DC Overvoltage Trip (Fehlercode 0002) | Excessively high mains voltage, overly short deceleration time, faulty braking circuit | 1. Measure input mains voltage to confirm it falls within allowable range |
| 2. Extend deceleration time or enable DC braking function | ||
| 3. Check wiring and resistance value of braking resistor for matching | ||
| Unterspannungsauslösung (Fehlercode 0003) | Single-phase power loss, blown input fuses, excessively low mains voltage | 1. Inspect three-phase input power to eliminate phase loss issues |
| 2. Check status of input fuses / Leistungsschalter | ||
| 3. Confirm on-site mains voltage meets equipment requirements | ||
| Motor Overload Alarm (Fehlercode 0005) | Jammed mechanical load, incorrect motor parameters, sustained overload operation | 1. Cut power and rotate motor shaft manually to check mechanical smoothness |
| 2. Re-run motor identification auto-tune | ||
| 3. Evaluate actual load conditions and upsize drive model if necessary | ||
| Overheating Fault (Fehlercode 0009) | Zu hohe Umgebungstemperatur, blocked cooling air ducts, faulty cooling fan | 1. Clear dust buildup on drive air intake cooling grille |
| 2. Verify normal operation of cooling fan | ||
| 3. Improve cabinet ventilation and lower ambient temperature |
Detailed List of Standard Accessories for ABB ACS580-01-087A-4 (Frame R5 / IP21 Version)
This model is a standard wall-mounted unit of ACS580 Frame R5. Factory supply contents are split into built-in onboard functions and physical accessories supplied in carton. Below is a detailed breakdown of the official standard supply scope:
- Standard Built-in Onboard Functions (Integriert, No Extra Fitting Required)
All functions below are factory pre-configured and ready for direct use without purchasing extra options:
- EMC Components: Built-in Class C2 EMC filter to meet industrial site electromagnetic compatibility requirements
- Braking Circuit: Integrated braking chopper allowing direct connection of braking resistors for fast deceleration
- Sicherheitsfunktion: Sicher abgeschaltetes Drehmoment (STO) compliant with PL e / SIL 3 safety level
- Umweltschutz: Full triple-protection coating on control and power boards, resistant to humid, dusty and corrosive gas environments
- Standard Control Interfaces: 6 digitale Eingänge, 2 digitale Ausgänge, 2 analoge Eingänge, 1 Analoger Ausgang
- Basic Communications: Embedded RS-485 hardware port with native Modbus RTU protocol support
- Strukturelles Design: Bottom cable entry compartment supporting standardized wiring and cable ingress protection
- Physical Standard Carton Accessories (Separately Packed Inside Shipment Box)
Independent accessories available upon unpacking for installation and basic commissioning:
- ACS-AP-S Assistant Control Panel (Chinese version): Equipped with LCD screen and full-function keys for parameter setup, status monitoring and fault diagnosis; pluggable onto drive front panel and supplied in separate packaging
- Wall Mounting Template: 1:1 paper drilling positioning template for marking mounting hole positions on-site to reduce drilling errors
- Cable Junction Box Assembly: Standard for Frame R5 IP21 units, including power cable grounding brackets, control cable shielding clamps and assembly fasteners
- Mounting Fastener Kit: M6 bolts, nuts and other metal hardware for wall mounting fixation
- Ground Terminals & Cable Crimp Accessories: Dedicated main circuit grounding terminals and auxiliary crimp fittings for control terminals
III. Supplied Documentation & Identification Labels
- Quick Installation and Startup Guide: Multilingual edition (including Chinese) covering full procedures of wiring, power-up and basic commissioning
- Safety Warning Stickers: Multilingual residual voltage warning labels to be affixed near equipment to alert maintenance personnel
- Product Certificate of Conformity and Warranty Document
Notiz: Full hardware manuals and firmware parameter manuals are not supplied as standard; downloadable via ABB official website or available as separate printed copies upon order.
- Packaging Auxiliary Protection Materials
Standard industrial shipping packaging for logistics protection, not classified as drive accessories:
VCI vapor corrosion inhibitor anti-rust bag
Paper buffer liners and corner protectors
Strapping bands
Shipping pallet (for full carton industrial packaging specifications)
- Non-Standard Optional Components Requiring Separate Ordering
Items below are excluded from standard supply scope and must be purchased separately per project demands:
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus TCP
Electrical Matching Components: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, Encoder-Schnittstellenkarten, temperature sensor interface cards, remote monitoring modules
Software Tools: Drive Composer professional commissioning software, USB commissioning cable
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien