Bussmann 200FEE Hochgeschwindigkeits-Halbleitersicherung - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Bussmann 200FEE Hochgeschwindigkeits-Halbleitersicherung - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

elektrisch/

Bussmann 200FEE Hochgeschwindigkeits-Halbleitersicherung

Grundlegendes Informationsmodell: 200FEE Brand: Eaton Bussmann Type: BS88 Part4 / IEC60269-4 high-speed bolted dual-barrel fuse, aR class (for semiconductor protection only) Nennstrom: 200A Electrical Specifications IEC Rating: 690V und / 500V DC UL Rating: 700V und / 500V DC Breaking Capacity: 200Die (AC rms); 50kA @500V DC Pre-arcing I²t: 1900; Total clearing I²t: ...

  • Produktdetails

Grundlegende Informationen

Modell: 200FEE

Marke: Eaton Bussmann

Typ: BS88 Part4 / IEC60269-4 high-speed bolted dual-barrel Sicherung, aR class (for semiconductor protection only)

Nennstrom: 200A

Elektrische Spezifikationen

IEC Rating: 690V und / 500In DC

UL Rating: 700V und / 500In DC

Bruchkapazität: 200Die (AC rms); 50kA @500V DC

I²t vor dem Lichtbogen: 1900; Total clearing I²t: 7100@415V, 11400@660V

Verlustleistung: 52W

No built-in fuse indicator; external kits TI700, MAI / MBI microswitch assemblies are available

Montagemaße

Befestigungsschraube: M8

Terminal Centre Spacing: 71mm

Konstruktion: Offset dual-barrel, bolt-connected blade terminals (blade end × blade end)

Gesamtgröße: 187mm breit, 100mm long, 22mm high, Nettogewicht: 89.6G

Zulassungen & Standards

CE, RoHS, UL-anerkannt

Standards: BS88 Part4, IEC 60269-4

Typische Anwendungen

Short-circuit protection for frequency converters, Gleichrichter, DC busbars, DC drives, thyristors and IGBT power semiconductors

Reference Models in the Same Series (FEE Series)

100FEE, 125FEE, 160FEE, 200FEE, 250FEE, 315FEE, usw. Same design logic, only rated current differs

Ersatzhinweise

This is a BS88-4 aR high-speed semiconductor fuse. For domestic alternatives, verifizieren: aR classification, I²t value, Ausschaltvermögen, M8 mounting and 71mm centre spacing. Ordinary gG/gL distribution fuses cannot be used as substitutes.

The 200FEE (FEE series BS88 Part4 aR high-speed dual-barrel fuse) has no original standard moulded fuse holder.

It is designed as M8 bolt-on blade terminals (blade end). The standard installation method is direct mounting onto busbars. Holders such as RS200H (Red Spot) are not required (RS200H is for BS88-2 gG distribution fuses and is incompatible with FEE high-speed semiconductor fuses).

Optionales Zubehör (Not Holders – Indicator / Microswitch Kits)

TI700: Fuse indicator kit (indicator flag + clip)

MAI: Microswitch adapter (fuse blown alarm signal)

MBI: Microswitch adapter (alternative construction)

Two Engineering Solutions

  1. Standard Solution (Most common for VFD / DC busbars)

Direct busbar mounting with M8 bolts, 71mm terminal centre spacing. TI700 / MAI / MBI may be fitted for blown-fuse signalling as required.

  1. IP20 Enclosed Holder (Alternative Lösung)

No original Bussmann holder is available. Only third-party bolt-on high-speed fuse holders can be selected. Mandatory selection criteria:

Compatible with M8 terminals, 71mm centre spacing, rated ≥200A, 690V, aR class, breaking capacity ≥200kA

All FEE series models (100FEE /125FEE /160FEE /200FEE /250FEE /315FEE) adopt the same busbar bolt-on design; no original holders are supplied.

200FEE (FEE Series BS88 Part4) Montagedrehmoment & Tightening Specification

Notiz: The manufacturer datasheet does not specify torque for this individual model. The values below are industry standard practice for Eaton BS88 fuses and busbar connections, widely used for VFD and DC bus projects.

Schraubengröße: M8 (coarse pitch 1.25), 8.8 grade galvanized bolts preferred

✅ Recommended Torque: 10 N·m (±1 N·m)

Acceptable Range: 9 N·m (min) ~ 12 N·m (max)

Do not exceed 12 N·m: risk of deforming fuse copper terminals and uneven contact surfaces. Torque below 9 N·m causes high contact resistance, overheating and nuisance blowing.

  1. Washer Stack Order (from busbar outwards)

Busbar → Fuse blade terminal → Plain washer → Spring washer → Nut

Verboten: Spring washer between fuse terminal and copper busbar; stacking multiple lugs on one side of a fuse terminal.

  1. Contact Surface Preparation (Critical – aR high-speed fuses are sensitive to contact resistance)
  2. Clean copper busbar and fuse terminal contact faces: remove oxidation with scouring pad / fine abrasive paper until bright, then wipe with isopropyl alcohol.
  3. A thin layer of conductive grease (joint compound) is permitted. Do not apply thick layers, to avoid creepage risk from excess grease squeezing out.
  4. Contact surfaces must be fully mated, free of burrs, gaps and trapped debris.
  5. Nach der Installation, contact resistance can be checked with a micro-ohmmeter; target per terminal: <50mΩ.
  6. Tightening Procedure
  7. Hand-thread first to align the fuse, keep both terminals parallel and centred.
  8. Tighten with a torque wrench in one smooth movement; avoid repeated back-and-forth adjustment.
  9. Mark the bolt/nut with paint after torque is achieved for tamper/loosening check.
  10. Thermal recheck: after initial energising and 2 hours of load operation, power off and recheck torque. Annual inspection is recommended for long-term service.
  11. Zubehör (TI700 / MAI / MBI)

Microswitches and indicator flags are clip-on accessories. They do not share the main circuit M8 bolts. Do not squeeze or pull the fuse body during fitting; do not alter the compression of the main electrical joint.

  1. Verbotene Praktiken

Do not use A2-70 stainless steel bolts and over-torque (stainless steel has lower yield strength and is prone to thread stripping).

Do not use impact wrenches for final tightening.

Do not force uneven or mismatched busbar thicknesses together.

Do not apply mechanical load or pry on the fuse body.

  1. Common for All FEE Series

100FEE /125FEE /160FEE /200FEE /250FEE /315FEE all use M8 terminals with the same 10 N·m torque specification.

Vorher:

Nächste:

Hinterlassen Sie eine Antwort

Eine Nachricht hinterlassen