CJX2-3210 is a 3-pole 32A AC-Schütz from CHINT CJX2 series, mit 3 NO main poles + 1 KEIN Hilfskontakt.
It is suitable for controlling 15kW motors at AC-3 380V. Coil voltages include 220V/380V and others.
Direct replacement models include Schneider LC1N3210, Siemens 3RT6035-1AN20, usw.
- Modellerklärung & Basic Positioning
| Modellteil | Bedeutung |
| CJX2 | CHINT AC contactor series (equivalent to Schneider LC1‑D series) |
| 32 | Rated operational current 32A (AC‑3 utilization category at 400V) |
| 10 | Hilfskontakte: 1 NEIN + 0 NC |
Produktpositionierung:
Industrial‑grade general‑purpose AC contactor, suitable for frequent starting and control of AC motors.
Can form a magnetic starter with thermal overload relays for motor protection.
- Wichtige technische Parameter
| Artikel | Spezifikation |
| Nennbetriebsspannung | Bis zu 690 V Wechselstrom (50/60Hz) |
| Bemessungsbetriebsstrom | 32A (AC‑3 400V), thermal current Ith = 50A |
| Controlled power | 15kW (AC‑3 380V), 21A (AC‑3 660V) |
| Hilfskontakt | 1 NEIN, rated 5A/220V AC |
| Coil voltage | Optional: 220V/380V/110V/36V/24V AC |
| Insulation characteristics | UI = 660V, compliant with GB14048.4 / IEC60947‑4‑1 |
| Mechanisch / elektrische Lebensdauer | 10 Millionen Mal / 1 Millionen Mal (AC‑3) |
| Abmessungen (L×W×H) | 83×58×101 mm |
| Montage | Standardmäßige 35-mm-DIN-Schiene |
- Strukturelle Merkmale & Materialien
- Silver alloy contacts: Excellent conductivity and arc resistance, ensuring reliable switching.
- 32‑sheet silicon steel core: Reduces hysteresis loss, smoother pull‑in, stable operation.
- Flame‑retardant housing: Meets V0 flame rating, verbessert die Sicherheit.
- Clear side marking: Modell, Stromspannung, CCC-Zertifizierung, usw.
- Anwendungen
- Industrielle Automatisierung: Motorsteuerung, Fans, Pumps, Kompressoren.
- Gebäudeelektrik: HVAC, Feuerlöschpumpen, exhaust fans.
- Agricultural machinery: Irrigation, feed processing equipment.
- Energiesysteme: Remote circuit control in distribution panels.
- Typical matching: Long‑running oil station motors, unidirectional equipment (no NC auxiliary required).
- Comparison Within CJX2 Series
| Modell | Nennstrom | Aux. Kontakte | AC‑3 380V Power | Abmessungen (mm) |
| CJX2‑0910 | 9A | 1 NEIN | 4kW | 73×47×82 |
| CJX2‑1810 | 18A | 1 NEIN | 7.5kW | 73×47×82 |
| CJX2‑2510 | 25A | 1 NEIN | 11kW | 83×58×96 |
| CJX2‑3210 | 32A | 1 NEIN | 15kW | 83×58×101 |
| CJX2‑4011 | 40A | 1 NEIN + 1 NC | 18.5kW | 128×79×116 |
| CJX2‑6511 | 65A | 1 NEIN + 1 NC | 30kW | 128×79×116 |
- Cross‑Brand Replacements
| Marke | Ersatzmodell | Kompatibilität |
| Schneider | LC1N3210M7N / LC1R3210M5N | Gleiche Abmessungen & Parameter |
| Siemens | 3RT6035‑1AN20 (domestic type) | Funktionell gleichwertig, mounting compatible |
| ABB | A145‑30‑11 (32A class) | Aux. can be configured as 1 NEIN |
| Lecker | CJX2‑3210 | Fully interchangeable |
| Changshu-Schalter | CK3‑3210 | Same performance & Parameter |
- Auswahl & Anwendungshinweise
- Coil voltage: Selected per control circuit (commonly 220V / 380V).
- Ladeabgleich: 32A ≈ 15kW at AC‑3 380V; avoid overload.
- Aux. contact expansion: F4‑11 or similar modules can be added.
- Protection coordination: Used with NR2 series thermal relays (z.B. NR2‑36) for overload protection.
- Umfeld: Operating temperature ‑5°C ~ +40°C; avoid dust & ätzendes Gas.
Packing: 4 pcs/box, 32 pcs/carton
Comparison of CHINT Contactor Series
Overview:
CHINT contactors are divided into:
Classic (CJX2/CJ20/CJX8), Upgraded (NXC/NC5), High‑Power (NC8), DC Special (CJZ8/NCZ5).
NXC fully replaces CJX2 with better performance; NC5 focuses on intelligence & modularity; NC8 covers ultra‑high current; CJZ8 is for DC control.
Priorität: NXC / NC5; use special series for special applications.
- Series Positioning & Ersatz
| Serie | Positionierung | Replaced By / Replaces | Hauptmerkmale |
| CJX2 | Classic general | Fully replaced by NXC | Cost‑effective, simple structure, flexible aux. Kontakte |
| NXC | New generation | Replaces CJX2, upgraded | Hohe Effizienz, long life, standard 1NO+1NC, strong modularity |
| NC5 | Smart & Prämie | High‑end market | Wide temp ‑25°C~+55°C, Kommunikation, complex automation |
| NC8 | High‑power heavy‑duty | Independent, up to 1000A | Up to 1000A AC‑3 415V, for large motors & heavy industry |
| CJX8 | Traditional heavy‑duty | Partially replaced by NC8 | Direct‑operated double break, suitable for legacy retrofits |
| CJ20 | Traditional general | Replaced by NXC/NC5 | Mature structure, niedrige Kosten, civil & light industry |
| NXC‑XMG | Special load | Independent | For fans & Pumps, high energy saving |
| CJZ8/NCZ5 | DC dedicated | Independent | Enhanced arc extinguishing, new energy & Energiespeicher |
- Wichtige technische Parameter
2.1 Basic Electrical Data
| Serie | Aktueller Bereich | Nennspannung | AC‑3 380V Power | Standard Aux. Kontakte |
| CJX2 | 9A~95A | Up to 690V | 0.75kW~45kW | Below 32A: 1NO/1NC; ≥40A:1NO+1NC |
| NXC | 6A~630A | Up to 690V | 0.37kW~315kW | Volles Sortiment: 1NO+1NC |
| NC5 | 6A~630A | Up to 690V | 0.37kW~315kW | 1NO+1NC, expandable to 6NO+6NC |
| NC8 | 6A~1000A | Up to 690V | 0.37kW~500kW | 2NO+2NC, expandable to 6NO+6NC |
| CJX8 | 9A~250A | Up to 660V | 4kW~110kW | 3NO+1NO/1NC or 4NO |
| CJ20 | 10A~630A | Up to 660V | 5.5kW~315kW | 1NO+1NC |
2.2 Life & Umfeld
| Serie | Mechanisches Leben | Elektrisches Leben (AC‑3) | Operating Temp | Montage |
| CJX2 | 10 million | 1 million | ‑5°C~+40°C | 35mm DIN / screw |
| NXC | 12 million | 1.2 million | ‑25°C~+55°C | 35mm DIN / screw |
| NC5 | 15 million | 1.5 million | ‑25°C~+55°C | 35mm DIN / screw |
| NC8 | 10 million | 0.8 million (hoher Strom) | ‑25°C~+55°C | Mainly screw |
| CJ20 | 8 million | 0.8 million | ‑5°C~+40°C | Screw |
- Struktur & Functional Differences
3.1 CJX2 (Classic)
Struktur: Direct‑operated single break, modular; F4 aux., F5 timer, NCF1 side aux. verfügbar.
Kontakte: Silberlegierung, 3P main, flexible aux. (10/01/11).
Spule: AC/DC, 24V~380V.
3.2 NXC (Upgraded)
Optimized magnetic system, coil power ≈ 30% lower than CJX2.
Improved silver alloy contacts, better arc extinguishing.
Standard 1NO+1NC; supports aux., timer, mechanical interlock.
3.3 NC5 (Smart Premium)
Optional communication module (Modbus, usw.) for IIoT.
Wide temperature, suitable for outdoor & raue Umgebungen.
Enhanced insulation & short‑circuit withstand.
3.4 NC8 (High‑Power)
Enhanced arc chamber for high‑current breaking up to 1000A.
Optimized heat dissipation for heavy‑duty continuous operation.
Heavy‑duty mechanical structure, high vibration resistance.
3.5 CJX8 (Traditional Heavy‑Duty)
Direct‑operated double break; front‑connected or rear‑connected versions.
Bis zu 4 Stangen (3 hauptsächlich + 1 aux or 4 hauptsächlich) for special applications.
3.6 DC Contactors
CJZ8: Low‑voltage DC (12V~220V), up to 40A, small DC loads.
NCZ5: High‑voltage DC (up to 1500V), up to 500A, new energy vehicles & Energiespeicher.
Dedicated DC arc extinguishing structure.
- Anwendungsszenarien
| Serie | Best For | Typische Belastung | Nicht empfohlen |
| CJX2 | Legacy retrofit, Budgetprojekte | Small motors ≤15kW, Beleuchtung, Heizung | High‑end automation, raue Umgebungen |
| NXC | Industrielle Automatisierung, new projects | Medium motors ≤315kW, Fans, Pumps | Ultra‑large motors, special DC loads |
| NC5 | Smart factories, complex systems, im Freien | Medium & large motors, Produktionslinien | Cost‑sensitive simple circuits |
| NC8 | Large industry, Leistung, Metallurgie | Large motors ≤500kW, Transformatoren | Small loads, zivile Gebäude |
| CJX8 | Legacy maintenance, special control | Traditional machinery, special circuits | New smart projects |
| CJ20 | Bürgerlich, light industry, temporary power | AC units, Pumps, small machines | Häufiges Wechseln, high‑end automation |
| DC series | New energy, Energiespeicher, Schiene | DC motors, batteries, Ladegeräte | AC loads |
- Auswahlhilfe & Ersatz
5.1 Selection Priority
- Neue Projekte: NXC (replaces CJX2)
- Smart/complex systems: NC5
- Ultra‑high power >315kW: NC8
- DC loads: CJZ8 / NCZ5
- Legacy retrofit: CJX2/CJ20/CJX8 or upgrade to NXC/NC5
5.2 Cross‑Series Replacement
| Original | Empfohlener Ersatz | Vorteil |
| CJX2‑09~95 | NXC‑06~100 | Standard 1NO+1NC, life +20%, power ‑30% |
| CJ20‑10~630 | NXC‑12~630 / NC8‑12~1000 | Better performance, modular, easier maintenance |
| CJX8‑09~250 | NC8‑06~250 | Better arc extinguishing, wide temperature |
5.3 Model Selection Tips
Aktuell: 32A ≈ 15kW; 63A ≈ 30kW; 100A ≈ 45kW at AC‑3 380V.
Aux. Kontakte: NXC has 1NO+1NC standard; CJX2 uses 10/01/11.
Spule: 220V/380V/110V/36V/24V AC/DC.
Montage: 35mm DIN preferred; screw for high power.
- Special Notes: CHINT CJX2‑3210
As a representative model of CJX2 series, CJX2‑3210 is a 3‑pole 32A AC contactor with 3 NO main contacts + 1 KEIN Hilfskontakt, suitable for 15kW motor control at AC‑3 380V.
Common replacements:
CHINT NXC‑3210 (upgraded)
Schneider LC1N3210M7N
Siemens 3RT6035‑1AN20
ABB A145‑30‑11 (32A class)
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien


















![NXC-65 aus der Kunlun-Serie von CHINT Electric ist ein 3-poliger AC-Schütz, Nennstrom 65 A in der NXC-Serie. Das vollständige Modell wird normalerweise als NXC-65 ausgedrückt [Spulenspannung] [Frequenz] NXC-65 from the Kunlun Series by CHINT Electric is a 3-pole AC contactor, rated at 65A in the NXC series. The full model is typically expressed as NXC-65 [Coil Voltage] [Frequency]](https://www.bestcontactor.com/wp-content/uploads/2026/04/ScreenShot_2026-01-30_132315_324-419x560.png)







NH42-63-318x560.png)