Chint NA1-3200X-3200M/3P Luftleistungsschalter

  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 Frame rated current: 3200A (maximum current specification of the breaker) X Breaking capacity grade: Class X (100Die); distinguished from standard type (80Die) and Class H (120Die) 3200 Bemessungsbetriebsstrom: 3200A (actual set working current) M Trip unit type: Intelligent trip ...

  • Produktdetails

 

CodesegmentBeschreibung
NA1Series code for Chint air circuit breakers (ACB)
3200Frame rated current: 3200A (maximum current specification of the breaker)
XBreaking capacity grade: Class X (100Die); distinguished from standard type (80Die) and Class H (120Die)
3200Bemessungsbetriebsstrom: 3200A (actual set working current)
MArt der Auslöseeinheit: Intelligente Auslöseeinheit (Mikrologisch); distinguished from standard Type L and high-breaking Type H
3PPolzahl: 3-Pole (3-phase circuit protection, without neutral pole)
  1. Grundlegende technische Spezifikationen
ParameterkategorieTechnical Data
ProdukttypIntelligent low-voltage air circuit breaker (ACB)
NennbetriebsspannungWechselstrom 400 V/690 V, 50Hz
Rahmenstrom (Iu)3200A
Nennbetriebsstrom (In)3200A
Rated Ultimate Short-circuit Breaking Capacity (Icu)100Die (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (ICs)100Die (equal to Icu)
Rated Short-time Withstand Current (Icw)80Die (1S)
AuslöseeinheitType M intelligent trip unit, mit Langzeitverzögerungsüberlastung, kurzzeitverzögerter Kurzschluss- und unverzögerter Kurzschlussschutz
MontageartDraw-out or fixed type (X series is generally draw-out)
BetriebsmodusManual or motorized (motor operating mechanism optional)
SteuerstromkreisspannungAC 220V/380V or DC 220V (optional)
HilfskontakteStandard: 5NEIN + 5NC (expandable)
Schutz vor EindringenIP30 (compliant with GB/T 4942.2)
Anwendbare StandardsGB/T 14048.2, IEC/EN 60947-2
Abmessungen (H×B×T)Draw-out type: ca. 600mm×400mm×1000mm (refer to official manual for exact data)
GewichtCa. 80~100kg (varies by mounting type and accessory configuration)
  1. Kernfunktionen

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Erdschlussschutz: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fehleraufzeichnung: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 High Reliability Design

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Long service life: Mechanical durability up to 10,000 Operationen; electrical durability up to 5,000 Operationen.

Vibration and shock resistance: Konform mit GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Flexible Expandability

Rich optional accessories: Rangierfahrt, undervoltage trip, closing solenoid, motor charging mechanism, Hilfskontakte, Alarmkontakte, key lock, usw.

Erweiterte Kommunikation: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Anwendungsszenarien

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Large motor: Incoming switch for Motor Control Center (MCC)

UPS system: Protection switch for UPS input and output circuits

Anwendungsszenarien

  1. Industrielle Stromverteilung: Main power distribution systems for factories, workshops and production lines.
  2. Stromverteilung für Gewerbegebäude: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Rechenzentren: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infrastruktur: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Modellvergleich
ModellBruchkapazitätNennstromAuslöseeinheitAnwendung
NA1-3200-3200M/3P80Die (Standard)3200AType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100Die (Class X)3200AType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120Die (Class H)3200AType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100Die (Class X)2500AType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100Die (Class X)3200AType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
ChintSiemensSchneiderABBMitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Bruchkapazität100Die100Die100Die85Die
AuslöseeinheitType M IntelligentETU25B IntelligentMikrologisch 5.0 IntelligentStandard Intelligent Trip
MontageartAusziehbar / BehobenAusziehbar / BehobenAusziehbar / BehobenAusziehbar / Behoben
KommunikationOptionaler Modbus / ProfinetOptional Profinet / EtherNet/IPOptionaler Modbus / ProfinetOptionaler CC-Link / Profinet
  1. Auswahl & Application Guidelines
  2. Passende Ausschaltkapazität: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000A, 2500A, 3200A.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Montageart: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Operation mode: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Select shunt trip, undervoltage trip, auxiliary contacts and communication modules as required by control and protection logic.
  8. Wartung: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Shunt-Trip (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TypModellNennspannungStromverbrauchAnwendungSelection Code
Kontinuierlich (Standard)NA1-F-3200XAC220V/230V460VA(AC220V)General industrial control, infrequent operationF-AC220
AC380V/400V400VA(AC380V)F-AC380
DC110V70W(DC110V)F-DC110
DC220V140W(DC220V)F-DC220
Pulse Type (Empfohlen)NA1-FP-3200XAC220V/230V880VA(AC220V)Wind & solar power, ATS system, frequent operationFP-AC220
AC380V/400V1800VA(AC380V)FP-AC380
DC110V850W(DC110V)FP-DC110
DC220V880W(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, max 5 Zeiten/Min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Undervoltage Trip (Q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TypModellNennspannungOperating CharacteristicDelay TimeSelection Code
Instant Suction (Standard)NA1-Q-3200XAC230VTrip at 70% Uns, reliable trip at 35% UnsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230VSame as above1s/3s/5s (Behoben)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230VSame as above0.3s~7.5s (Einstellbar)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (X) / Closing Coil

For remote closing, matched with motor charging mechanism.

TypModellNennspannungStromverbrauchAnwendungSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (M)

Stores energy for breaker closing and provides closing power.

ModellNennspannungLeistungCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. Intelligent Control & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModellMerkmaleAnwendungSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3M
Typ HAdvanced protection with extended parameter settingsComplex power distribution systems & precise protectionH
Type 3HHighest configuration, full 3M+H functions + EreignisprotokollierungCritical circuits & fault analysis3H

2.2 Kommunikationsmodule (Remote Monitoring)

Module TypeModellProtokollFunktionMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUData acquisition & FernbedienungNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetEthernet-KommunikationPSU-1 power moduleCOM-PN+PSU-1
EtherNet/IPNA1-COM-ENIPEtherNet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NameModellFunktionAnwendungSelection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
RelaismodulRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Statusanzeige & Kontrolle)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), expandable.

TypModellKontaktkonfigurationRatingAnwendungSelection Code
3 sets TransferNA1-AX-3Z3NO+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Standard)NA1-AX-4Z4NO+4NCAC230V/5AStandardkonfigurationAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NO+3NCNA1-AX-333NO+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AStandardkonfigurationAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AComplex controlAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Mechanische Verriegelung & Safety Accessories

4.1 Mechanische Verriegelung (Misoperation Prevention)

TypModellFunktionAnwendungSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2MATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TypModellFunktionAnwendungSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NameModellFunktionAnwendungSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
SchalterNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceCT
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montage & Connection Accessories

5.1 Main Circuit Accessories

NameModellRatingAnwendungSelection Code
Horizontal BusbarNA1-BUS-H3200AStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200AVertical installation & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200AFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NameModellFunktionAnwendungSelection Code
Sekundärer AnschlussNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6A, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Beispiel:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / undervoltage trip / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, undervoltage trip, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 