E4.2N 4000 with Ekip trip unit R4000 — R4000 means the rated current of the electronic trip unit is 4000A
✅ Modellaufschlüsselung
E4.2: Rahmengröße (Emax2 series, maximum frame rating 4000A)
N: Kurz-Stromkreisunterbrechung capacity grade N, Icu=66kA @400V AC
4000: Frame rated current Iu=4000A
R4000: Rated current In of Ekip electronic trip unit (Trip unit options: Dip / Berühren / Hi-Touch / G Touch; protection types: LSI / LSIG / LI)
✅ Key Electrical Specifications
Frame rated current Iu: 4000 A
Trip unit rated current In: 4000 A
Bemessungsbetriebsspannung Ue: Wechselstrom 690 V
Bemessungsisolationsspannung Ui: Wechselstrom 1000 V
Stoßspannungsfestigkeit Uimp: 12 kV
Icu (Ultimate short-circuit breaking capacity): 66 Die (400~690V)
ICs (Service short-circuit breaking capacity): 66 Die
Icw (Kurzzeitiger Stromwiderstand): 66 kA for 1s; 50 kA for 3s
Mechanische Ausdauer: 15,000 Operationen
Elektrische Ausdauer: 5,000 operations at ≤440V; 4,000 operations at 500~690V
✅ Construction & Abmessungen (Fixed type F, rear horizontal terminals HR, 3P)
3P: W384 × H371 × D270 mm, Nettogewicht 56 kg
4P: W510 × H371 × D270 mm, Nettogewicht 70 kg
Terminal options: Rear horizontal HR; optional rear vertical VR; withdrawable W version
Serienmäßig ausgestattet: 4 sets of auxiliary contacts, position contacts (Offen / Geschlossen)
✅ Trip Unit Comparison (Key for selection)
- Ekip Dip: Basisversion, no display, LSI/LSIG
- Team Touch: Color display, Dosierung, communication support, LSI/LSIG
- Ekip Hi-Touch: Advanced color display, Energiemessung, Oberwellenüberwachung, waveform recording
- Ekip G Touch: Integrated gateway, eingebaut ABB Ability remote communication
LSIG: Long-time L, Short-time S, Momentan I, Erdschluss G; LSIG includes ground fault protection
✅ Cross-reference & Ersatzoptionen
Same frame variants: E4.2S (Icu 85kA), E4.2H (100Die), E4.2V (150Die)
Inländische alternative Referenz: Chint NA8-4000, Delixi CDW3-4000, Changshu CW3-4000 (match breaking capacity 66kA)
Upgrade from legacy model: Replaces old-generation Emax E4N 4000
✅ Common Order Codes (3P Fixed HR)
Ekip Dip LSI R4000: 1SDA071192R1
Ekip Touch LSI R4000: 1SDA071195R1
Ekip Hi-Touch LSIG R4000: 1SDA071199R1
ABB Emax2 Ekip (E4.2) Fehlercodeliste & Communication Commissioning Guide
Applicable to Ekip Dip / Berühren / Hi-Touch / G Touch; Ekip Dip has no screen, only LED alarms; Touch/Hi-Touch support text & numeric fault codes and event logging
Preliminary note: Protection trips (L/S/I/G) are protection events, not hardware faults; 3xxxx numeric codes indicate internal trip unit hardware faults
- LED Alarm Indications (Common to all Ekip units, for on-site quick diagnosis)
Gelb (Warnung)
Ständig AN: Pre-alarm, protection pre-warning, auxiliary signal alarm
2 flashes per 0.5s: Parameter configuration error
Schnelles Blinken: Rating plug mismatched or not properly fitted
Rot (Alarm/Auslösung)
Ständig AN: Protection activated & gestolpert, trip command issued
Schnelles Blinken: Sensor disconnection, trip coil open circuit, BF trip failure, protection timing fault
2 flashes every 2s: Rating plug damaged
Gelb + Red fast flashing: Communication lost between main trip board and protection timing module
Gelb + Red slow flashing: Critical internal trip unit fault, contact ABB service
- On-screen Alarm & Fehlercodeliste (Touch/Hi-Touch)
🔹 Protection Trip Events (Trip log, check first)
| Display Label | Beschreibung | Bemerkungen |
| L | Long-time overload trip ANSI49 | Überlast, thermisches Gedächtnis, reset after cooling |
| S | Short-time short-circuit ANSI51/50TD | Short-circuit short delay, for selectivity |
| ICH | Instantaneous short-circuit ANSI50 | Instant short-circuit trip |
| G | Ground fault ANSI51N | Only available on LSIG versions |
| 2ICH | Neutral overload protection | For 4P devices |
| IU | Current unbalance protection | Dreiphasige Unsymmetrie |
| UV | Unterspannungsschutz | Voltage below threshold |
| OV | Überspannungsschutz | Voltage above threshold |
| F | Frequency out of range | Frequenz <30Hz or >80Hz |
| Phase | Phasenfolgefehler | Phase sequence protection activated |
| THD V / THD I | Harmonic distortion excess | Hi-Touch harmonic monitoring |
| MCR | Closing short-circuit protection | Short-circuit at closing instant |
🔹 Hardware / Communication Alarms (Fault alarms, not trips)
| Alarm Text | Fehlerbeschreibung | Fehlerbehebung |
| BF Trip failed command | Trip command sent, breaker remains closed with primary current present | Check YO trip coil, Mechanismus blockiert, mechanical blockage; perform iTEST |
| Local bus | Internal Ekip bus W1/W2/W3/W4 communication lost, expansion module offline | Check Ekip Com / Ekip Signalling module power supply, bus terminals, module compatibility |
| Batterie schwach | RTC backup battery depleted | Replace CR2450 battery kit, reset date/time after replacement |
| Invalid date | RTC time lost | Settings → System → Date & Zeit; enable SNTP sync with Com TCP |
| Konfigurationsfehler | Conflict between rating plug and protection settings | Verify rating plug; G / I4 threshold cannot exceed 100A without Vaux auxiliary supply |
| Sensor broken wire | Internal CT signal abnormal | Check connection between trip unit and CT; internal failure requires factory repair |
| Trip coil open circuit | YO loop wiring break | Measure YO coil resistance and external wiring |
| SNTP error | NTP time synchronization failed (Modbus TCP module) | Check gateway, network, NTP server address |
| Ekip Com module missing | Communication module not detected | Check module power, bus connector, model compatibility; replace defective module |
| 30002, 30xxx numeric codes | Trip unit firmware / MCU internal error | Aus- und wieder einschalten; if fault persists replace trip unit, contact ABB |
| Breaker status unknown | Conflicting feedback from auxiliary contacts | Check auxiliary contact wiring and mechanical position |
Event storage: Touch/Hi-Touch stores up to 200 latest events, with timestamp, fault current and voltage exportable; Ekip Dip has no event storage
- Ekip Communication Commissioning Guide (Ekip Com Modbus RTU / Modbus TCP)
Communication module types:
Ekip Com Modbus RTU (RS485, 2-wire W1/W2, Modbus RTU)
Ekip Com Modbus TCP (Ethernet, Modbus TCP)
✅ Ekip Dip has no native communication. Communication requires Touch/Hi-Touch/G Touch plus optional Ekip Com module
3.1 Factory Default Communication Parameters
Modbus RTU: Baudrate 19200, Sogar Parität, 1 Stoppbit, Slave ID 1
Modbus TCP: DHCP enabled by default; fallback static IP: 192.168.1.100, mask 255.255.255.0
Bus wiring: RS485 W1=A, W2=B; 120Ω terminating resistor required at bus ends
Stromversorgung: Ekip Com requires 24V DC auxiliary supply (Vaux). Module will not run without 24V!
3.2 Commissioning Tools
- Ekip Connect (ABB official, bevorzugt): Parameter read/write, bus scan, event export, IP/slave address modification, Firmware-Upgrade, iTEST; supports direct connection via USB T&P test head, independent of field bus
- Modbus master tools: Modscan, Modbus Poll, SPS (Siemens, Schneider etc.)
3.3 Commissioning Steps for RTU RS485
- Ausschalten, mount Ekip Com Modbus RTU module, connect W1(A) W2(B), feed 24V DC to module; fit 120Ω terminators at bus ends
- Einschalten, on trip unit screen: Settings → Communication → Modbus RTU
Enable bus
Set slave address (1~247, unique per bus segment)
Match baudrate & parity with master
- Connect PC USB-RS485 adapter: A→W1, B→W2; common ground is critical
- Ekip Connect → Scan → Serial → Configure COM port, baudrate, even parity → Start scan
- Device found: Read measurements (I/U/P), breaker status, Alarm; write operations require password authority
- No device found troubleshooting:
Confirm 24V supply; W1/W2 polarity; Gemeinsamkeit; terminator; Konflikte angehen; baud/parity mismatch
Bestätigen “Local bus enabled” on trip unit screen
3.4 Commissioning Steps for Modbus TCP
- Mount Ekip Com Modbus TCP module, supply 24V DC, connect Ethernet to switch
- On trip unit screen: Settings → Communication → Modbus TCP
DHCP: Enable/Disable; set static IP, Subnetz, Tor
Enable Modbus TCP service (Hafen 502)
- Keep PC and module on same subnet, direct cable or via switch
- Ekip Connect → Scan → Ethernet; or open module IP in browser for read-only web page
- PLC/SCADA access: Modbus TCP port 502, refer to ABB Ekip Modbus register map
3.5 Access Rights & Passwort
Read measurements & Alarm: No password required
Modify protection settings, Kommunikationsparameter, clear events: Engineer password (Standard 000000)
iTEST trip test: Local operation only at connected position; remote test trigger blocked
3.6 Common Communication Pitfalls (E4.2N4000R4000)
- Missing 24V auxiliary supply: Com module fails to start. CT self-power only supports protection logic, cannot power Com module
- Ungrounded RS485 bus: Intermittent packet loss and garbled data; single-point grounding for long-distance bus
- Ekip G Touch has integrated gateway. Do not use together with external Ekip Com, bus conflict will occur
- Withdrawable breaker: Bus connection inside the cradle is disconnected in test position; communication only available in connected position
- Modbus register types: Input registers (schreibgeschützt: aktuell, Stromspannung, Status); Holding registers (read/write: settings, Kontrolle). Remote open/close requires additional Ekip Com Actuator module; standard Com module is read-only, cannot execute remote switching
- Reset Rules
- Protection trips (L/S/I/G): Clear fault first, then reset locally (screen reset or remote reset via YR contact)
- Warning alarms (low battery, SNTP error): Auto clear after root cause removed or manual acknowledge
- BF trip failure alarm: Mechanical inspection on-site required, manual confirmation to clear alarm
ABB SACE Emax2 ACB Model Specification + Vollständige Serienliste + Allgemeine Bestellcodes
Serie: Emax2 (successor to legacy Emax E1/E2/E3/E4/E6), IEC-Standard, widely used ACB in China; Breaking grades by Icu@400V:
B=42kA|C=50kA|N=66kA|S=85kA|H=100kA|V=150kA
Trip unit abbreviation:
D = Ekip Dip (no display, dip-switch setting, LSI/LSIG, no native comms)
T = Ekip Touch (Farbdisplay, Dosierung, Com module compatible)
HT = Ekip Hi-Touch (Farbdisplay, harmonisch, recording, power quality)
GT = Ekip G Touch (integrated gateway, ABB Ability)
Protection types: LI / LSI / LSIG (G=ground fault)
Montage: F Fixed; W Withdrawable; Terminals HR Rear Horizontal, VR Rear Vertical; 3P/4P
Vollständiges Modellbeispiel: E4.2N 4000 Ekip Touch LSIG 3P F HR, matching your E4.2N4000R4000
- Frame Overview (4 Emax2 frame sizes)
| Rahmen | Max Iu | Available Breaking Grades | Available Iu(A) |
| E1.2 | 1600A | B / C / N | 630, 800, 1000, 1250, 1600 |
| E2.2 | 2500A | B / N / S / H | 800, 1000, 1250, 1600, 2000, 2500 |
| E4.2 | 4000A | N / S / H / V | 2000, 2500, 3200, 4000 |
| E6.2 | 6300A | H / V | 4000, 5000, 6300 |
Notiz: Suffix “.2” stands for Emax2; old Emax E1/E2/E4/E6 without “.2” are phased out
- Full Model Description Breakdown
`E4.2 N 4000 Ekip Touch LSIG 3P F HR`
- E4.2: Rahmengröße
- N: Schaltleistungsklasse
- 4000: Frame rated current Iu
- Team Touch: Art der Auslöseeinheit
- LSIG: Protection curve
- 3P: Polzahl
- F: Mounting F Fixed / W Withdrawable
- Personalwesen: Terminal HR Rear Horizontal / VR Rear Vertical / FR Front
Rating Plug Rxx: R4000=In=4000A; R3200=In=3200A, R value ≤ Frame Iu
- Basic Model List
✅ E1.2 (630~1600A)
E1.2B 630 / 800 /1000 /1250 /1600
E1.2C 630 / 800 /1000 /1250 /1600
E1.2N 630 / 800 /1000 /1250 /1600
✅ E2.2 (800~2500A)
E2.2B 800 /1000 /1250 /1600 /2000 /2500
E2.2N 800 /1000 /1250 /1600 /2000 /2500
E2.2S 800 /1000 /1250 /1600 /2000 /2500
E2.2H 800 /1000 /1250 /1600 /2000 /2500
✅ E4.2 (2000~4000A)
E4.2N 2000 /2500 /3200 /4000
E4.2S 2000 /2500 /3200 /4000
E4.2H 2000 /2500 /3200 /4000
E4.2V 2000 /2500 /3200 /4000
✅ E6.2 (4000~6300A)
E6.2H 4000 /5000 /6300
E6.2V 4000 /5000 /6300
- Standard-Bestellcodes (1SDA prefix, 3P Fixed HR, no motor/YO/YC accessories)
Regel: Order code changes with trip unit; separate codes for W withdrawable and 4P versions
E1.2N 1600
Ekip Dip LSI R1600: 1SDA070492R1
Ekip Touch LSI R1600: 1SDA070495R1
Ekip Touch LSIG R1600: 1SDA070496R1
Ekip Hi-Touch LSIG R1600: 1SDA070499R1
E2.2N 2500
Ekip Dip LSI R2500: 1SDA070892R1
Ekip Touch LSI R2500: 1SDA070895R1
Ekip Touch LSIG R2500: 1SDA070896R1
Ekip Hi-Touch LSIG R2500: 1SDA070899R1
E4.2N 4000
Ekip Dip LSI R4000: 1SDA071192R1
Ekip Touch LSI R4000: 1SDA071195R1
Ekip Touch LSIG R4000: 1SDA071196R1
Ekip Hi-Touch LSIG R4000: 1SDA071199R1
E4.2S 4000
Ekip Dip LSI R4000: 1SDA071212R1
Ekip Touch LSI R4000: 1SDA071215R1
Ekip Hi-Touch LSIG R4000: 1SDA071219R1
E6.2H 6300
Ekip Touch LSI R6300: 1SDA071455R1
Ekip Touch LSIG R6300: 1SDA071456R1
Ekip Hi-Touch LSIG R6300: 1SDA071459R1
- Communication Module Order Codes (Ekip Com)
Ekip Com Modbus RTU: 1SDA073440R1
Ekip Com Modbus TCP: 1SDA073441R1
Ekip Com Profibus: 1SDA073442R1
Ekip Com IEC61850: 1SDA073444R1
Ekip Com Actuator (remote switching module): 1SDA073446R1
- Common Accessory Order Codes (Separat erhältlich, not included in breaker body)
Closing coil YC AC220: 1SDA073300R1
Opening coil YO AC220: 1SDA073304R1
Motor operator M AC220: 1SDA073310R1
Auxiliary contacts 4CO: 1SDA073320R1
Signal contacts 2CO: 1SDA073322R1
RTC battery kit: 1SDA073470R1
Rating Plug R4000: 1SDA072944R1
- Wichtige Hinweise
- The above base codes default to 3P, Fixed F, Rear Horizontal HR. Codes change for 4P / W withdrawable / VR vertical terminals
- Quotation is combinational: Breaker body + Motor + YO + YC + communication module are separate line items. Breaker body does not come with motor or coils as standard
- Ekip Dip has no communication. Touch/Hi-Touch need Ekip Com module for Modbus
- Legacy Emax (non .2) order codes start with 1SDA05, parts and trip units are not interchangeable with Emax2