Schneider Electric EZ7RCCB-63A Fehlerstromschutz

Catalogue No.: EZ723263G Product positioning: Pure residual current circuit breaker (FI-Schutzschalter, earth leakage only; no overload or short-circuit protection). Belongs to the discontinued Easy7 (DIESES7) economy project series, end-of-life since 30 June 2023. Technische Kernparameter (2P-Version, häufigstes Modell) Nennstrom In: 63 A Poles: 2P (einphasig) Rated voltage Ue: 230 V und, ...

  • Produktdetails

Catalogue No.: EZ723263G

Produktpositionierung: Pure residual current Leistungsschalter (FI-Schutzschalter, earth leakage only; no overload or short-circuit protection). Belongs to the discontinued Easy7 (DIESES7) economy project series, end-of-life since 30 June 2023.

Technische Kernparameter (2P-Version, häufigstes Modell)

Nennstrom In: 63 A

Polen: 2P (einphasig)

Rated voltage Ue: 230 V und, 50 Hz

Restbetriebsstrom: 30 mA, sofortige Reise

Lecktyp: Typ A (detects AC leakage + pulsierende Gleichstromleckage; suitable for variable-frequency loads and switch-mode power supplies)

Reisetyp: Elektronisch (ELE)

Montage: DIN-Schienenstandard, Breite 36 mm (2 Module)

Standards: GB 16916 / IEC 61008‑1

Built-in test button. Must be fitted with an upstream MCB for short-circuit and overload protection (RCCB itself does not protect against short-circuit or overload faults).

Schlüsselunterscheidung

FI-Schutzschalter: Earth leakage protection only; always requires an upstream miniature circuit breaker.

EZ7RCBO: Combined earth leakage + Überlast + Kurzschlussschutz (integrierter RCBO). Do not mix these two types.

Replacement Selections (Original Schneider alternatives)

  1. Economy direct replacement: Easy9 RCCB (EZ9R series), 2P 63A 30mA Type A
  2. High-End-Modell: Acti9 iID (A9R series), 2P 63A 30mA Type A (electromagnetic type, bessere Anti-Interferenz)
  3. Integrated all-in-one option (RCBO): Easy9 RCBO / iC65N Vigi add-on residual current block

Zusätzliche Hinweise

The entire EZ7 range (including EZ7RCCB and EZ7Vigi add-on leakage blocks) was officially discontinued by Schneider on 30 June 2023. No further production runs will be made; stock on the market is leftover inventory. For new projects and long-term maintenance, switch directly to the Easy9 series to avoid future supply shortages.

Application Scope for EZ7RCCB‑63A (2P, 30mA, Typ A, Electronic RCCB)

Voraussetzung: Only earth leakage protection; no overload/short-circuit protection. An upstream MCB is mandatory. Type A detects AC + pulsierende Gleichstromleckage; 63A is the continuous current rating, not the fault trip current.

✅ Empfohlene Anwendungen

  1. Main household residual current protection (single-phase 220V incoming supply)

Main incoming earth leakage protection for residential apartments and homes, with multiple downstream MCBs. Ideal for circuits with inverter air conditioners, variable-frequency washing machines and switch-mode power supply appliances (advantage of Type A). Centralised protection for wet-area circuits (Badezimmer, balcony, kitchen socket circuits).

  1. Single-phase main protection for small shops, convenience stores and retail premises

Mixed lighting + socket circuits with many PCs, Registrierkassen, LED drivers and variable-frequency equipment. Used in low-cost distribution boxes for ground-floor commercial premises to provide collective earth leakage protection.

  1. Branch main RCD for small offices and computer rooms

Large numbers of adapters, UPS, computers and switch-mode power supplies. AC-type RCCBs are prone to nuisance tripping, so Type A is preferred for collective protection of a group of socket circuits.

  1. Small single-phase commercial equipment control panels

Commercial water purifiers, Wärmepumpen, variable-frequency water heaters and small automation control cabinets. Earth leakage protection for metal-cased equipment.

  1. Single-phase main protection for temporary site distribution boxes (economy projects)

High risk of personnel contact with metal power tools. Notiz: Most construction site codes require time-delayed selective RCDs or site-specified residual current devices. This model is instantaneous 30mA, so verify local regulations before selection.

⚠️ Conditional Applications (with restrictions)

Single-phase AC side of small PV systems: Only for the AC side. Type A cannot be used on the DC side; DC-side protection requires Type B. The AC output of inverters contains pulsating DC components, which Type A can handle properly.

EV charging: Not recommended for standard AC slow chargers. Current national standards require Type B residual current protection for charging circuits.

❌ Not Suitable for These Scenarios

  1. Cannot be used standalone without an upstream MCB; without short-circuit/overload protection, cables will burn out under fault conditions.
  2. Pure resistive loads with no electronic equipment: AC-type RCCBs are cheaper; Type A is unnecessary.
  3. Medical Class 1 locations, swimming pools and fountains: Normally require 10mA high-sensitivity RCDs or Type B / specialised selective residual current devices.
  4. Three-phase circuits: This is a 2P single-phase device; not for three-phase applications.
  5. Selective graded protection (to avoid cascading tripping): This is instantaneous with no time delay. Upstream and downstream 30mA RCDs will trip simultaneously.
  6. Heavy industrial variable-frequency sites with severe harmonic interference: Electronic RCCBs suffer frequent nuisance tripping. Use electromagnetic iID models instead.

📌 Selection Summary (EZ7 discontinued; new projects use EZ9R 2P 63A Type A 30mA directly)

Positionierung: Economy Type A main RCD for collective earth leakage protection of multiple circuits, especially circuits with large numbers of switch-mode power supplies and variable-frequency single-phase loads.

Typical circuit topology: Incoming supply → MCB (Kurzschluss + Überlast) → EZ7RCCB → multiple branch circuits.

Full List of Schneider Residual Current Devices (FI-Schutzschalter / RCBO / Vigi Add-on Blocks)

Classification definition:

✅ RCCB: Pure earth leakage protection; no overload/short-circuit protection, must be fitted with upstream MCB.

✅ RCBO: All-in-one device with earth leakage + Überlast + Kurzschlussschutz (3-in-1).

✅ Vigi: Add-on residual current block, mounted separately onto iC65 / iC60 miniature circuit breakers.

Leakage types:

AC-Typ: Only AC leakage

Typ A: Wechselstrom + pulsating DC (Wechselrichter & Schaltnetzteile)

Typ B: Including smooth DC leakage (EV chargers, PV-Wechselrichter, heavy-duty variable-frequency drives)

SI = Selective time-delay; prevents cascading tripping between upstream and downstream RCDs.

The entire EZ7 series is discontinued.

  1. Acti9 iID (Premium Electromagnetic RCCB, Main Current Stock, A9R / A9Z part numbers)

Type A iID (For inverters, Schaltnetzteile & Haushaltsgeräte)

Catalogue No.SpezifikationBemerkungen
A9R532252P 25A 30mA Type A, SofortMain RCD for homes & Geschäfte
A9R532402P 40A 30mA Type A, Sofort
A9R532632P 63A 30mA Type A, SofortPreferred original replacement for EZ7RCCB‑63A
A9R534254P 25A 30mA Type A, Sofort3-Phase 4-Leiter
A9R534404P 40A 30mA Type A, Sofort
A9R534634P 63A 30mA Type A, Sofort
A9R534914P 100A 30mA Type A, SofortHigh-current model
A9R872632P 63A 300mA Type A-SI SelectiveFire protection, upstream main RCD
A9R874634P 63A 300mA Type A-SI Selective

AC Type iID (Resistive loads only: incandescent lighting, standard sockets)

Catalogue No.Spezifikation
A9R712252P 25A 30mA AC
A9R712402P 40A 30mA AC
A9R712632P 63A 30mA AC
A9R714254P 25A 30mA AC
A9R714404P 40A 30mA AC
A9R714634P 63A 30mA AC

Type B iID (EV chargers, PV-Anlagen, heavy inverters; A9Z range)

Catalogue No.SpezifikationAnwendung
A9Z512252P 25A 30mA Type B EVAC EV chargers
A9Z512402P 40A 30mA Type B EV
A9Z514404P 40A 30mA Type B EV3-phase PV inverters
A9Z514634P 63A 30mA Type B EV
A9Z612402P 40A 30mA Type B-SI SelectiveGraded selective protection required
A9Z614634P 63A 30mA Type B-SI Selective
A9Z654634P 63A 300mA Type B-SIFire protection for distribution feeders
A9Z654804P 80A 300mA Type B-SI
  1. Einfach9 (EZ9R Series, Economy RCCB, Direct Replacement for Obsolete EZ7, Auf Lager)
Catalogue No.SpezifikationLeckagetyp
EZ9R352252P 25A 30mAWechselstrom
EZ9R352402P 40A 30mAWechselstrom
EZ9R352632P 63A 30mAWechselstrom (AC-type alternative to EZ7RCCB‑63A AC)
EZ9R392252P 25A 30mATyp A (Direct Type A replacement for EZ7RCCB‑63A)
EZ9R392402P 40A 30mATyp A
EZ9R392632P 63A 30mAType A ✅ Core model: EZ7RCCB‑63A economy Type A equivalent
EZ9R394254P 25A 30mATyp A (3-Phase)
EZ9R394404P 40A 30mATyp A
EZ9R394634P 63A 30mATyp A
EZ9R552632P 63A 100mAWechselstrom (Feeder fire protection)
EZ9R652632P 63A 300mAWechselstrom

Easy9 RCBO (Integrated leakage + Leistungsschalter, EZ9C series):

EZ9C45C1630: 1P+N C16 30mA; EZ9C45C2030, EZ9C45C3230, usw.

  1. iC65N Vigi Add-on Residual Current Blocks (Used with iC65 MCBs, Not Standalone RCCBs)

Example part numbers: A9V53240 (2P 40A 30mA Type A Vigi); A9V52240 (AC-Typ).

Montage: iC65N MCB + Vigi add-on block = assembled RCBO.

  1. EZ7 Easy7 (Discontinued Range, Your Model Is Here; EOL 30 June 2023)
Catalogue No.Spezifikation
EZ723263GEZ7RCCB 2P 63A 30mA Type A (Ihr Zielmodell)
EZ713225GEZ7RCCB 2P 25A 30mA AC
EZ713240GEZ7RCCB 2P 40A 30mA AC
EZ723240GEZ7RCCB 2P 40A 30mA Type A
EZ713463GEZ7RCCB 4P 63A 30mA AC
  1. Integrated RCBO (Acti9 iC60N RCBO, A9D Prefix: Leckage + Überlast + Short-circuit All-in-One)
Catalogue No.Spezifikation
A9D148161P+N C16 30mA Type A
A9D148201P+N C20 30mA Type A
A9D148321P+N C32 30mA Type A
A9D348401P+N B40 30mA Type A
  1. Quick Selection Cross Reference (For EZ7RCCB‑63A: 2P 63A 30mA Type A)

Obsolete stock model: EZ723263G (Auslaufmodell)

Economy direct replacement: EZ9R39263 (Easy9 Type A)

Premium electromagnetic alternative: A9R53263 (Acti9 iID Type A)

Supplementary Selection Rules

  1. RCCBs cannot be used without an upstream MCB; RCBOs can be used on individual final circuits without extra breakers.
  2. EV chargers, DC circuits and heavy variable-frequency drives require Type B; circuits with switch-mode power supplies and inverters use Type A; pure resistive lighting can use cheaper AC type.
  3. SI selective models are used on main feeders to prevent simultaneous tripping of upstream and downstream residual current devices.