ModellMerkmaleDifferences
H3CR-A8Standard type with DPDT contact outputBasic model
H3CR-A8SWith instantaneous contact outputAdded a set of instantaneous contacts
H3CR-A8EEconomical type with simplified functionsCost-optimized with slightly reduced functions
H3CR-A11-pin modelMore functions including 11 operating modes

  • Produktdetails

The Omron H3CR-A8 is a 1/16 DIN size (48×48mm) 8-pin plug-in multi-functional solid-state timer featuring a wide voltage range, multiple operating modes and reliable double-contact output. It is widely used in the field of industrial automation control.

  1. Core Parameters and Specifications
ParameterSpezifikation
StromversorgungsspannungStandard type: AC100~240V 50/60Hz / DC100~125V
Low-voltage type: AC24~48V / DC12~48V
Time Range0.05s~300h (18 selectable ranges)
Operating Modes5 modes: ON delay, Flicker OFF Start, Flicker ON Start, Interval, One-shot delay
Output TypeDPDT (Double Pole Double Throw) time-delay contact, Rated capacity: 5A 250VAC
Genauigkeit±0.2% FS max. (±0.2%±10ms within the 1.2s range)
Abmessungen48(H)×48(W)×81.6(D)mm
Montagemethode8-pin round socket mounting (P3G-08 socket recommended)
SchutzklasseIP40 for panel surface, IP00 for terminals
StromverbrauchAC-Typ: ca. 3VA; DC type: ca. 3W
  1. Funktionsmerkmale
  2. Multi-functionality: 5 operating modes can be easily switched via the mode selector switch to meet diverse control requirements
  3. Wide Voltage Design: Universal AC/DC power supply reduces inventory types and adapts to global voltage standards
  4. High-Precision Timing: Solid-state circuit design delivers stable timing accuracy, superior to mechanical timers
  5. Double-contact Output: DPDT 5A contacts enable simultaneous control of two independent circuits
  6. Power Reset Function: Minimum power-off reset time of 0.1s ensures reliable restart
  7. Internationale Zertifizierungen: Compliant with EN61812-1 and EN60664-1 standards, certified by UL and CSA

III. Wiring and Operation

  1. Terminal Configuration (8-Stift)

1,3,4,8: Empty pins

2: Power supply (+)

5: Power supply (-) / AC neutral

6: Normalerweise geschlossen (NC) contact

7: Common (COM) Terminal

10: Normalerweise geöffnet (NEIN) contact

  1. Operation Panel

Power indicator: Displays power on/off status

Output indicator: Displays contact operation status

Time unit selector: Switches between seconds/minutes/hours

Time setting knob: Precisely sets the time delay

Operating mode selector switch: Switches between 5 operating modes

  1. Anwendungsszenarien
  2. Sequential control and time-delay start of industrial machinery
  3. Time delay for motor overload protection
  4. Cycle setting for temperature control of heating equipment
  5. Intermittent operation control of production lines
  6. Time-delay triggering of alarm systems
  7. Timing control of lighting systems
  8. Related Models and Differences
ModellMerkmaleDifferences
H3CR-A8Standard type with DPDT contact outputBasic model
H3CR-A8SWith instantaneous contact outputAdded a set of instantaneous contacts
H3CR-A8EEconomical type with simplified functionsCost-optimized with slightly reduced functions
H3CR-A11-pin modelMore functions including 11 operating modes
  1. Vorsichtsmaßnahmen bei der Verwendung
  2. Umweltanforderungen: Avoid use in environments with drastic temperature changes, high humidity, strong vibration or corrosive gas
  3. Anti-interference Measures: In noisy environments, it is recommended to replace input signal lines with shielded cables
  4. Verkabelungsspezifikationen: Strictly follow terminal polarity for wiring to avoid short circuits
  5. Mode Switching: Switching time units or operating modes under power is prohibited, which may cause malfunctions
  6. Power Reset: Ensure a power-off time of ≥0.1s to guarantee reliable reset

VII. Substitution and Upgrading

Direct Substitute Model: H3CR-A8-301 (fully functionally compatible)

Upgraded Models: H3CR-A8S (with added instantaneous contacts), H3CR-AS (transistor output), H5CN series (digital display type)

Cross-Brand Interchangeable Model Guide for Omron H3CR-A8

 

The Omron H3CR-A8 is a 1/16 DIN (48×48mm) 8-pin plug-in multi-functional solid-state timer with core parameters: 5 operating modes (ON delay/Flicker OFF Start/Flicker ON Start/Interval/One-shot delay), DPDT double pole double throw time-delay contact output, 0.05s~300h time range, and wide voltage input (AC100~240V/DC100~125V or AC24~48V/DC12~48V). The following are interchangeable models from mainstream brands, sorted by matching degree:

  1. Omron Internal Substitute Models (Best Match)
ModellMerkmaleInterchangeabilityRemarks
H3CR-A8-301Identical functions with only production batch differences100% direct interchangeableOfficially recommended substitute, fully compatible in pins/dimensions/functions/voltage
H3CR-A8SWith an additional set of instantaneous contactsHoch (95%)8-Stift, DPDT + instantaneous, note the output contact differences
H3CR-A8EEconomical type with simplified functionsHoch (90%)Cost-optimized with slightly reduced performance, suitable for non-critical applications
H5CX-L8-NUpgraded digital display typeMedium (80%)Same dimensions with enhanced functions, requires parameter reconfiguration
  1. Cross-Brand Interchangeable Models from Mainstream Brands
  2. Schneider Electric
ModellSchlüsselparameterInterchangeabilityNotizen
RE48AML12MW48*48mm, 8-Stift, 5 modes, DPDT, 0.02s~300h, 24~240V AC/DCHoch (95%)Higher time accuracy (starting from 0.02s), wider wide voltage range, slight differences in pin definition
RE48AMH13MW48*48mm, 8-Stift, multi-functional, DPDT, 0.05s~300h, 100~240V ACHoch (90%)AC voltage only, no DC input
  1. Eaton Moeller
ModellSchlüsselparameterInterchangeabilityNotizen
DIL08AM-1048*48mm, 8-Stift, 5 modes, DPDT, 0.05s~300h, 100~240V AC/DCHoch (95%)Exact match in functions/dimensions/pins, same contact capacity (5A)
DIL08AM-2448*48mm, 8-Stift, 5 modes, DPDT, 0.05s~300h, 24~48V AC/DCHoch (95%)Low-voltage version, suitable for specific power supply environments
  1. IDEC
ModellSchlüsselparameterInterchangeabilityNotizen
GT3A-2AF2048*48mm, 8-Stift, 5 modes, DPDT, 0.05s~180h, 100~240V ACMedium (85%)Slightly lower upper time range limit (180h vs 300h), suitable for most applications
GT3A-2DF2448*48mm, 8-Stift, 5 modes, DPDT, 0.05s~180h, 24~48V AC/DCMedium (85%)Low-voltage + shorter time range, application scenario evaluation required
  1. Carlo Gavazzi
ModellSchlüsselparameterInterchangeabilityNotizen
FAA08DW2448*48mm, 8-Stift, multi-functional, DPDT, 0.05s~300h, 24~240V AC/DCHoch (90%)Matched in functions/dimensions, larger contact capacity (8A), direct replacement available
FAA08AW1048*48mm, 8-Stift, multi-functional, DPDT, 0.05s~300h, 100~240V ACHoch (90%)AC voltage only, suitable for AC-only application environments
  1. Crouzet
ModellSchlüsselparameterInterchangeabilityNotizen
TMR48X 88 886 11648*48mm, 8-Stift, multi-functional, DPDT, 0.05s~300h, 100~240V ACHoch (90%)Slight differences in operating modes, requires reconfiguration of the mode selector switch
TMR48U 88 886 01648*48mm, 11-Stift, multi-functional, DPDT, 0.05s~300h, 100~240V ACNiedrig (70%)Different number of pins, socket replacement required, direct interchange not recommended

III. Key Matching Points for Interchange (Mandatory Check)

Check ItemStandard ParameterMismatch Risk
Maßangabe4*48mm (1/16 DIN)Uninstallable, incompatible panel cutout
Pin Quantity8-pin round socketUninsertable, requiring rewiring/socket replacement
Operating Modes5 modes (consistent with H3CR-A8)Insufficient functions, requiring reprogramming or control logic adjustment
Output ContactDPDT (Double Pole Double Throw) time-delay contactUnable to control the original dual circuits, potentially causing equipment failure
SpannungsbereichMatched with the original model (AC100-240V or AC24-48V)Power supply incompatibility, burning out the timer or causing malfunction
Time Range0.05s~300hFailure to meet control accuracy or maximum delay requirements
Kontaktkapazität5A 250VAC (ohmsche Last)Contact overload, causing contact welding or burnout
  1. Interchange Operation Steps and Precautions
  2. Power-Off Safety Operation: Disconnect and lock the power supply before replacement to prevent electric shock and equipment damage
  3. Parameter Recording: Record the time setting, operating mode and wiring method of the original H3CR-A8
  4. Model Verification: Confirm that the key parameters of the substitute model are consistent with the original one
  5. Pin Confirmation: Check the terminal diagram of the substitute model to ensure correct wiring (H3CR-A8 terminals: 2=+, 5=-/AC neutral, 6=NC, 7=COM, 10=NO)
  6. Mode Setting: Adjust the mode selector switch of the substitute model according to the original operating mode
  7. Zeitkalibrierung: Set the same time delay as the original model to ensure consistent control logic
  8. Test and Verification: Conduct a power-on test to confirm normal timer operation and equipment operation in line with expectations
  9. Recommended Models for Special Scenarios
Application ScenarioRecommended Interchangeable ModelReason
Strict judicial/certification requirementsOmron H3CR-A8-301100% compatibility, maintaining the validity of the original equipment certification
Need for digital display upgradeOmron H5CX-L8-NSame dimensions with enhanced functions and more intuitive operation
Low-cost substitutionOmron H3CR-A8E or domestic compatible models30-50% cost reduction, suitable for non-critical applications
Wide voltage global applicationSchneider RE48AML12MWFull voltage compatibility of 24~240V AC/DC, suitable for export equipment
  1. Scenarios Not Recommended for Interchange
  2. The original equipment has special certification requirements (z.B., classification society certification) and the substitute model has no corresponding certification
  3. Complex control logic relying on unique functions of H3CR-A8 (z.B., 0.1s power reset time)
  4. Large differences in pin definition between the substitute model and the original one, with no possibility of rewiring
  5. Extremely high time accuracy requirements (±0.2% FS), and some economical substitute models have lower accuracy

Vorher: