PNOZ m B0 Base Unit, Bestell-Nr. 772100
Produktfamilie: PNOZmulti 2 modular safety controller (PNOZ m2), configurable multi-function safety relay / compact safety SPS
- Modellcode-Definition
PNOSIS: PILZ safety relay series identifier
M: Multi, modular configurable system
B0: Base Unit 0, entry-level host without onboard fieldbus
772100: Unique material order number
- Grundlegende technische Spezifikationen
- Stromversorgung: 24 In DC
- Onboard Inputs: 8 safe digital inputs
- Onboard Outputs:
4 safe semiconductor outputs (OSSD)
- Kommunikation: No integrated fieldbus interface (only B1/B2 models come with Profinet/EtherCAT onboard)
- Programmierung: Configured via PNOZmulti Configurator, program downloaded over USB port
- Sicherheitsleistung: PL e / SIL 3 (per EN ISO 13849 & IEC 61508)
- Betriebstemperatur: -10℃ ~ +55℃
- Montage: DIN-Schienenmontage
- Gehäusebewertung: IP20 (Nur für den Schrankeinbau)
- Programmspeicher: SD-Karte; program can be copied to another identical unit directly via card swapping
- Funktionen & Typische Anwendungen
Monitoring emergency stop pushbuttons, Schutztürschalter, Sicherheitslichtvorhänge, Sicherheitsmatten, Zweihand-Bedienstationen
Safety logic: AND/OR operations, Zeitverzögerung, Verriegelung, safety counter, Modusauswahl (auto/manual)
Target Equipment: Werkzeugmaschinen, Verpackungsmaschinen, automatisierte Produktionslinien, Förderanlagen, robot peripheral safety protection
Key Feature: Modular architecture; I/O expansion modules can be added later.
Notiz: PNOZ m B0 has no built-in bus interface and only supports local I/O. For fieldbus communication, select PNOZ m B1 (772100, Profinet) or PNOZ m B2 (772102, EtherCAT).
- Passende Komponenten
Erweiterungsmodule (PNOZmulti 2 Serie, mounted on the right side of 772100)
Digital input expansion: 772110
Relay output expansion: 772120
Semiconductor output expansion: 772121
Software
PNOZmulti Konfigurator (free download from PILZ official website; supports PNOZmulti Classic and PNOZmulti 2)
Program Migration
Programs can be copied directly via SD card; identisch 772100 units run the program immediately after card insertion. Migration to B1/B2 bus versions requires hardware reconfiguration inside the software.
- On-Site Troubleshooting Guide
- No POWER LED: Überprüfen 24 V DC polarity, Sicherungen, terminal wiring and power supply ripple
- Constant ERR LED: Program configuration error, corrupted SD card or hardware fault; read diagnostic data via software
- No response from safety inputs: Check dual-channel wiring continuity, Kurzschlüsse, contact polarity and input filter parameters
- OSSD semiconductor outputs fail to energize: Safety logic conditions not met, output overload or short circuit; verify load status
- Cross-Model Alternatives & Competitor Products
In-Series Upgrade
PNOZ m B1 (772101): Profinet interface
PNOZ m B2 (772102): EtherCAT FSoE interface
Markenübergreifende Äquivalente
Schneider Electric XPSM series
Siemens F30 safety relay modules
IFM safety controllers
Domestic Replacements
Configurable safety controllers certified up to PL e / SIL 3.
Einschränkung: Different software, certification and terminal definitions; projects cannot be migrated directly and require full reconfiguration.
PNOZmulti 2 (PNOZ m2) Vollständige Modellliste (Bestell-Nr. 7721xx)
Base Units (Links: bus modules; Rechts: I/O-Erweiterungsmodule)
| Modell | Bestell-Nr. | Schlüsselbeschreibung | Max. Erweiterungsmodule |
| PNOZ m B0 | 772100 | Entry model without onboard bus; 8AUS + 4OSSD; USB + SD-Karte; dieses Gerät | Bis zu 6 safety I/O modules on the right |
| PNOZ m B0.1 | 772104 | Compact successor to PNOZmulti Mini; nur 1 expansion module allowed | Max. 1 I/O module |
| PNOZ m B1 | 772101 | Dual Profinet + Modbus TCP ports; large project capacity | 12 Sicherheitsmodule + 6 standard modules |
| PNOZ m B1 Burner | 772103 | B1 version dedicated for burner control with certified burner function blocks | Same as B1 |
| PNOZ m B2 | 772102 | Native EtherCAT FSoE onboard | Same as B1 |
| PNOZ m C0 | 772105 | Standalone non-expandable unit; 8AUS + 4OSSD; no expansion capability | 0 Erweiterungsmodule |
Right-Side Safe I/O Expansion Modules (PNOZ m EF, PL e / SIL3)
Digitale I/O-Module
| Modell | Bestell-Nr. | E/A-Konfiguration |
| PNOZ m EF 16DI | 772140 | 16 safe digital inputs |
| PNOZ m EF 8DI4DO | 772142 | 8AUS + 4 OSSD semiconductor safety outputs |
| PNOZ m EF 8DI2DOT | 772144 | 8AUS + 2 transistor outputs with test pulses (for press machines) |
| PNOZ m EF 4DI4DOR | 772143 | 4AUS + 4 relay safety outputs (KEINE Kontakte) |
| PNOZ m EF 4DI4DORD | 772145 | 4AUS + 4 Relaisausgänge (NEIN + Öffnerkontakte) |
| PNOZ m EF 2DOR | 772146 | 2 independent relay safety outputs |
Safe Analog Input Module
|PNOZ m EF 4AI|772160|4-channel safe analog input (0–10 V / 4–20 mA)|
Motion Monitoring Modules (Safe axis control)
| Modell | Bestell-Nr. | Axis Count |
| PNOZ m EF 1MM | 772170 | 1-axis speed / position monitoring |
| PNOZ m EF 1MM2DO | 772172 | 1 Achse + 2 OSSD safety outputs |
| PNOZ m EF 2MM | 772171 | Dual-axis synchronous & Geschwindigkeitsüberwachung |
Right-Side Standard Non-Safe I/O Modules (PNOZ m ES, only supported by B1/B2)
| Modell | Bestell-Nr. | E/A-Konfiguration |
| PNOZ m ES 16DI | 772182 | 16 standard digital inputs |
| PNOZ m ES 14DO | 772181 | 14 standard semiconductor outputs |
Left-Side Communication & Link Modules
Fieldbus Modules
| Modell | Bestell-Nr. | Bustyp |
| PNOZ m ES Profinet | 772138 | Profinet IO (your previously referenced part number) |
| PNOZ m ES EtherCAT | 772132 | EtherCAT |
| PNOZ m ES ETH | 772130 | Standard Ethernet TCP/IP |
| PNOZ m ES Profibus | 772131 | Profibus DP |
| PNOZ m ES CANopen | 772133 | CANopen |
| PNOZ m ES CC-Link | 772134 | CC-Link |
| PNOZ m ES Powerlink | 772135 | Ethernet Powerlink |
| PNOZ m ES EtherNet/IP | 772136 | EtherNet/IP |
Safety Interlink Modules (Multi-controller networking)
|PNOZ m EF Multi Link|772120|Interlink multiple PNOZ m2 controllers (Kupfer / fibre optic)|
|PNOZ m EF PDP Link|772121|Connect distributed PDP67 remote I/O|
|PNOZ m EF SafetyNET|772122|SafetyNET p safety Ethernet networking (max. 16 Einheiten)|
|PNOZ m EF FSoE|772123|EtherCAT FSoE safety communication extension|
Preconfigured Complete Packages
PNOZ m2p: 772100 + 772144 (standard press machine configuration)
PNOZ m2p ETH: 772100 + 772130 + 772144 (press version with Ethernet)
Ersatzteile & Zubehör
- Program SD card (not included with base unit; separat bestellt werden)
- Steckklemmen: Spring-clamp terminal 783542; Schraubklemme 793542
- Inter-module jumpers: 779260
Expansion Rules (Kritisch)
- PNOZ m B0 (772100): Max. 6 EF safety modules on the right; ES standard I/O modules are NOT supported; nur 1 bus/link module on the left.
- PNOZ m B1/B2: Max. 12 EF safety modules + bis zu 6 ES standard I/O modules on the right.
- PNOZ m B0.1 (772104): Nur 1 I/O module allowed; no multi-module cascading.
Application Scenarios for PNOZ m B0 (772100)
- General Safety Monitoring (Most Common Use Case)
It monitors and executes safety logic for these protection devices:
- Dual-channel E-Stop pushbuttons
- Schutztürschalter (PSEN series)
- Sicherheitslichtvorhänge & laser scanners
- Safety mats and safety edges
- Zweihand-Bedientasten (press machine dedicated logic)
- 3-position enabling switches (teach pendant)
- Mode selector switches (auto/manual/jog interlock)
- Reset buttons and muting functions
Supported logic: UND/ODER, Zeitverzögerung, Verriegelung, Kantenerkennung.
The OSSD outputs cut off main contactors or servo enable signals, fully complying with EN ISO 13849 Maschinensicherheitsnormen.
- Industry-Specific Deployments
(1) Werkzeugmaschinen & Press Equipment
Ausrüstung: Mechanische Pressen, hydraulic presses, Abkantpressen, Schere
Monitored signals: Two-hand stations, Sicherheitstore, Lichtvorhänge, slider position (mit 772170 motion module)
Sicherheitsfunktionen: Single-stroke operation, anti-repeat stroke, Verriegelung, delayed safe stop; pre-certified press function blocks available
Erfordernis: PL e Category 4; ideal for retrofits replacing multiple discrete safety relays.
(2) Verpackungsmaschinen
Machines: Vertikale Schlauchbeutelmaschinen, horizontale Verpackungsmaschinen, case erectors, Palettierer
Monitored points: Guard doors, feed opening light curtains, Not-Aus, material muting
Nutzen: Consolidate multiple safety door controls into one controller, reduce cabinet wiring and simplify fault diagnosis.
(3) Montagearbeitsplätze & Robot Cells
Anwendungen: Standalone robot cells, conveyor stations, fixture & test stations
Schutz: Fence safety gates, laser area scanners, teach pendant enable switches, multi-zone safety interlocking
Optional upgrade: Installieren 772138 Profinet module on the left to transmit safety status and fault codes to the main PLC and HMI for remote diagnostics.
(4) Materialhandhabung & Logistikautomatisierung
Ausrüstung: Bandförderer, Rollenlinien, transfer lifts, Sortiersysteme
Use case: Multiple E-stops along the line, access door interlocks, sectional safe stop; distinguish local shutdown from global emergency stop.
(5) Gummi & Kunststoffe / Spritzgießmaschinen
Injection moulders and extruders: Guard door interlocks, hopper protection, mould area light curtains, mould safety interlock and safety time delay.
(6) Thermal Processing / Furnace Systems (IN 298 Compliant)
Small heating furnaces: Monitor air pressure, flame signals, safety valve interlocks and burner safety chains.
Notiz: Multi-burner large furnace systems should select the B1 Burner variant.
- Two Standard Engineering Configurations
Modus 1: Standalone Base Unit (No Expansion Modules)
8 safe DI + 4 OSSD onboard I/O.
Best for small standalone machines: 1~2 safety gates + 1 Lichtvorhang + E-stop with simple logic, spart Platz im Schrank.
Modus 2: With Right-Side EF Expansion Modules (Max. 6 Module)
Expandable for:
Extra digital inputs / Relaisausgänge
Safe analog modules (Temperatur & pressure safety monitoring)
Safe motion control modules (Geschwindigkeit, position and safe speed limitation)
Suitable for medium-sized machines with multiple guard points and axis safety monitoring.
- Nachrüstung & Machine Modernisation Projects
Perfect for legacy equipment upgrades:
Replace dozens of discrete safety relays with one controller, simplify wiring and reduce troubleshooting time.
Logic is software-configured; the built-in LCD directly pinpoints fault locations, cutting spare part varieties.
Program backup via SD card; replacement units run immediately after card insertion.
- Selection Boundaries (When NOT to choose 772100)
- Large production lines with high I/O count and demand for standard non-safety I/O → Choose PNOZ m B1 (772101)
- Native EtherCAT FSoE bus required → Choose PNOZ m B2 (772102)
- Minimal safety points with zero expansion needed → Compact PNOZ m C0 (772105)
- Multi-burner furnace systems → PNOZ m B1 Burner
- Bus Communication Solution: 772100 + 772138
Install the PNOZ m ES Profinet (772138) module on the left slot of PNOZ m B0:
Hardwired local safety cut-off remains fully independent. Safety status, fault codes and I/O states are uploaded to the main PLC via Profinet.
The PLC only performs monitoring; safety shutdown never relies on fieldbus communication, fully complying with functional safety regulations.
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter




















NH42-63-318x560.png)