Portable digital earth resistance meter (digital earth megger), used for lightning protection earthing, Stromverteilungsausrüstung, buildings, charging pile earthing engineering inspection. Supports 2-pole / 3-pole measurement.
- Kernspezifikationen
Earth resistance range: 0.01Ω~4000Ω; Accuracy ±(3%+3 Ziffern)
Earth voltage measurement: 0~200V AC (50/60Hz); Accuracy ±(1%+5 Ziffern)
Anzeige: 4000-count LCD backlit screen with analog bar graph
Datenspeicherung: 100 measurement records. Supports MAX/MIN/AVG and REL relative measurement
Stromversorgung: 8 × 1.5V AA batteries
Abmessungen: 180×140×65mm; Nettogewicht: 950G
Sicherheitsbewertung: CAT III 600V, compliant with EN61010-1
Umweltfreundlich: Operating temperature 0~40℃; Storage temperature -10~50℃; Humidity ≤85% non-condensing
Auto functions: 10-minute auto power-off, low battery indicator, limit value alarm
- Measurement Modes
- 3POLE 3-polige Methode: Standard-Erdungswiderstandsmessung (E-P-C drei Messleitungen + Erdsonden), bevorzugt für die technische Abnahme
- 2POLE 2-polige Methode: Vereinfachte Messung, für Szenarien mit bekanntermaßen guter Hilfserdung
- VE Erdspannung: Misst Netzfrequenz-Streuspannung an Erdungselektroden, um durch Störungen verursachte abnormale Messwerte zu vermeiden
- Standardzubehör
Haupteinheit, 5m/10m/20m Messleitungen, 2 Erdsonden, Tragetasche, Bedienungsanleitung, Batterien
- Typische Anwendungsszenarien
Blitzschutz-Erdungsprüfung für Gebäude
Erdungstest für Hoch & Niederspannungsverteilerschränke und -motoren
Erdungsanlagenabnahme für Photovoltaikanlagen und Ladesäulen
Erdungswiderstandsprüfung für Umspannwerke und Kommunikationsräume
- Betriebsrichtlinien & Allgemeine Fehlerbehebung
Betriebsrichtlinien
- 3-pole measurement: Verbinden Sie die Klemme E mit der gemessenen Erdungselektrode; Treiben Sie die P- und C-Sonden im angegebenen Abstand in den Boden. Sonden müssen fest sitzen. Gießen Sie Wasser in trockene Erde, um die Leitfähigkeit zu verbessern.
- Vor der Widerstandsprüfung die Erdspannung VE messen. Hohe Spannung weist auf Netzfrequenzstörungen hin; Beseitigen Sie Störungen, bevor Sie den Widerstand messen.
- Voreingestellte Widerstandsgrenzwerte; Der Alarm wird automatisch ausgelöst, wenn die Messwerte den Schwellenwert überschreiten.
Häufige Fehler
- Schwankende Messwerte: Schlechter Sondenkontakt, trockener Boden, starke Störungen der Stromversorgung vor Ort. Überprüfen Sie die Verkabelung und setzen Sie die Sonden neu ein.
- Zu hohe Messwerte: Falsche Platzierung der Hilfselektroden oder beschädigte Messleitungen.
- Start der Messung fehlgeschlagen: Schwache Batterie oder offener Teststromkreis.
- Alternative Referenzen
Inländisch: ETCR2000, Erdungswiderstandsmessgeräte der Serie ETCR3000
Importiert: Fluke 1623/1625 Erdwiderstandstester (höhere Genauigkeit, höherer Preis)
HABOTEST HT2302 Erdungswiderstandstester|Hauptanwendungsszenarien
Kernpositionierung: 3-Pole / 2-Mast-Vor-Ort-Abnahme- und Prüfgerät für den Erdungswiderstand. Misst gleichzeitig die Erdstreuspannung bei Netzfrequenz. Geeignet für Elektriker, Blitzschutzinspektoren, Elektromechanische Wartungsingenieure, Sicherheitsunternehmen und externe Sicherheitsinspektoren.
🏢 Gebäudeblitzschutz (Am häufigsten)
- Abnahmeprüfung der Blitzschutzerdung für Neubauten; Testen Sie künstliche Erdungselektroden und Fundamenterdungsgitter gemäß der Blitzschutznorm GB50057.
- Jährliche routinemäßige Blitzschutzprüfung: Erdungsprüfung für Fabriken, Lagerhäuser, Bürogebäude, Dachblitzstreifen und Blitzableiter.
- Blitzschutz-Erdungsprüfung für Eisenmasten, Außenüberwachungsmasten und Kommunikationsbasisstationen.
⚡ Stromverteilung & Erdung elektrischer Geräte
- Schutzerdungsprüfung für Hoch-/Niederspannungsverteilerschränke, Transformatoren, Leistungsmotoren und Verteilerkästen
- Arbeitserdung und wiederholte Erdungsprüfung in Stromverteilerräumen und auf Sockeln montierten Transformatoren; Überprüfung des Erdungssystems vor der Wartung im ausgeschalteten Zustand
- Inspektion der Gerätegehäuseerdung für Produktionslinien in Fabriken, um die Gefahr eines Stromschlags zu verhindern
🔋 Neue Energie & Ladesäulen
- Abnahme und jährliche Prüfung der AC/DC-Ladesäulenerdung (Erdung ist eine zwingende Sicherheitsanforderung für Ladesäulen)
- Erdungstest für PV-Modulhalterungen, Wechselrichter und Generatoranschlusskästen in Photovoltaik-Kraftwerken
📡 Schwacher Strom, Sicherheit & Computerräume
- Potenzialausgleichs- und antistatische Erdungsprüfung für Netzwerk- und Serverräume
- Erdungsprüfung für Überwachungssysteme, Schranken und Zugangskontroll-Schwachstromgeräte; Vermeiden Sie Schäden durch statische Elektrizität und Überspannung
- Erdungsabnahme für Beschallungsanlagen und Brandmeldezentralen
🧪 Andere technische Szenarien
- Antistatischer Erdungstest für petrochemische Werkstätten (Tanklager und Pipelines)
- Temporary power earthing inspection on construction sites for site power acceptance
- Preliminary soil resistivity survey to assist earthing engineering design
- On-site data logging for third-party testing agencies: 100-group storage for test reports
✅ Target Users
Certified electricians, Blitzschutzinspektoren, Elektromechanische Wartungsingenieure, security contractors, third-party safety inspectors.
HABOTEST HT2302 Earth Resistance Tester|Full Operation Tutorial
Tutorial 1: Pre-inspection & Power-on Preparation (Obligatorisch)
- Installieren 8 AA batteries, ensure good contact in battery compartment. Replace batteries immediately when low battery icon appears; insufficient power causes reading drift.
- Inspect 3 test leads and 2 earth probes for broken wires or insulation damage. Polish oxidized alligator clips.
- Rotary switch positions: AUS / ~VE Earth Voltage / RE 3POLE 3-pole / RE 2POLE 2-pole.
- Button description:
PRÜFEN: Start measurement
MEMO: Save readings (max 100 Gruppen)
READ: Recall historical records
CLR: Clear stored data
REL: Relative measurement (eliminate lead resistance)
Hintergrundbeleuchtung: Enable backlight in low-light environments
Pre-safety requirement: Disconnect measured earth electrode from power grid. Never measure earth resistance on live equipment. Always measure ~VE earth voltage first.
Tutorial 2: 3POLE 3-pole Method (Standard Acceptance Method, Empfohlen)
0.618 rule (golden ratio layout for potential probe), adopted for lightning protection, distribution cabinet and charging pile acceptance.
- Verdrahtung
Terminal E: 5m short lead → clamp to measured earth electrode (earth flat steel / earth rod)
Terminal P: 10m lead → potential probe, placed between E and C
Terminal C: 20m long lead → current probe
- Layout (Three points in straight line)
Total distance E to C: 30M; E→P=10m, P→C=20m (0.618 Position)
Drive earth probes vertically ≥20cm into soil. Pour small amount of salt water at probe positions for dry/sandy soil to improve contact.
- Bedienungsschritte
1) Turn rotary knob to `~VE`, measure stray earth voltage. Do NOT measure resistance if voltage>5V. Power-frequency interference will distort readings; troubleshoot interference first.
2) Switch knob to `RE 3POLE`, confirm wiring.
3) Press TEST to start measurement and wait for stable reading.
4) Press MEMO to save stable reading; average multiple measurements.
- Reference criteria: Lightning protection generally ≤4Ω; power distribution protective earthing ≤4Ω; simple repeated earthing ≤10Ω (refer to corresponding national standards).
Tutorial 3: 2POLE 2-pole Method (Indoor Quick Measurement, Reference Only, NOT for Official Acceptance)
Anwendung: Indoor concrete ground where ground probes cannot be driven.
- Verdrahtung: Short E and P terminals as one test clip; C terminal as second clip.
- Measurement principle: Use known good building earthing (water pipe, main building earth) as auxiliary ground to measure resistance between two points.
- Betrieb: Switch knob to `RE 2POLE`, attach clips and press TEST.
⚠️Disadvantages: Low precision, only for rough continuity check. Cannot be used for lightning protection or charging pile acceptance reports.
Tutorial 4: VE Earth Voltage Measurement (Interference Check, Essentiell)
- Turn knob to `~VE`, connect E and C terminals to measure AC power-frequency voltage on earth electrode.
- Funktion: Detect stray voltage on earth wire. Voltage reading indicates leakage or grid unbalance interference. Resistance measurement results are unreliable under such conditions; cut power and disconnect connections before retest.
Tutorial 5: REL Relative Measurement (Eliminate Lead Resistance, Improve Accuracy)
- Short all three clips E, P und C zusammen.
- Geben Sie den entsprechenden Widerstandsbereich ein und drücken Sie REL. Das Messgerät führt eine automatische Nullstellung durch, um den Eigenwiderstand der Prüfkabel aufzuheben.
- Trennen Sie die Clips und den Draht zur Messung wie gewohnt. Sehr empfehlenswert für Messungen mit langen Leitungen.
Tutorial 6: Datenspeicherung & Abrufen
- Drücken Sie MEMO, sobald sich der Messwert stabilisiert hat; Der Bildschirm zeigt den Speicherindex für erfolgreiches Speichern.
- Drehknopf im Messmodus belassen, Drücken Sie READ, um die gespeicherten Daten zu durchsuchen 100 Aufzeichnungen.
- Die CLR-Schaltfläche löscht einen einzelnen Datensatz oder einen vollständigen Datensatz für die Erstellung eines Berichts nach dem Standort.
Tutorial 7: Leitfaden zur schnellen Fehlerbehebung
- Schwankend, instabile Messwerte
Flache Einführung der Sonde / trockener Boden; Wassersonden und tiefer fahren. Von Stromkabeln fernhalten, Wechselrichter und Hochleistungslasten.
Rostige Clips und schlechter Kontakt; Metallkontaktflächen polieren.
- OL unendliche Lektüre
Defekte Messleitung, Offene Clip-Verbindung oder Sonden, die nicht im Boden vergraben sind.
- Deutlich hohe Messwerte
Falsche P/C-Sondenausrichtung, drei Punkte nicht kollinear. Störungen durch unterirdische Metallrohre/Bewehrungsstäbe; Positionieren Sie die Sonden in eine andere Richtung.
- Das Messgerät kann den Test nicht starten
Niedriger Batteriestand oder schlechter Anschlusskontakt.
Tutorial 8: Betriebsspezifikationen vor Ort & Sicherheitsverbote
✅ Empfohlen
An bewölkten Tagen mit feuchter Erde testen. Vermeiden Sie Messungen unmittelbar nach starkem Regen (Übermäßige Bodenfeuchtigkeit führt zu verfälschten Messwerten).
Trennen Sie Blitzschutzleisten und Geräte während der Erdungsnetzprüfung vom Erdungsnetz, um Parallelschaltungseinflüsse zu vermeiden.
❌ Verboten
Messen Sie den Erdungswiderstand, während das System unter Spannung steht
Prüfspitzen direkt unter Hochspannungskabel verlegen
Erstellen Sie offizielle Abnahmeprotokolle im 2-poligen Verfahren
HABOTEST HT23xx Erdungswiderstandstester-Serienliste (Gleiche Plattform wie HT2302)
Bei der HT23-Serie handelt es sich um leitungsgebundene 3/2-polige Erdwiderstandsmessgeräte (erfordert Erdsonden, keine Erdungszangen). Commercially available HABOTEST models:
✅ HT2301 (Basic Entry Model)
Measurements: 2-Pole,3-pole earth resistance + AC earth voltage
Reichweite: 0.01~2000Ω
Lagerung: 50 Aufzeichnungen, no soil resistivity function
Anwendung: Simple earth inspection for electricians, temporary construction power; no soil resistivity measurement
Positionierung: Low-cost entry unit for basic routine screening
✅ HT2302 (Your Current Model, Mainstream Standard Version)
Measurements: 2-pole /3-pole earth resistance, earth voltage
Reichweite: 0.01Ω~4000Ω; AC earth voltage 0~200V
Lagerung: 100 Gruppen, MAX/MIN/AVG, REL relative measurement, analog bar graph
Leistung: 8×AA batteries
Positionierung: Main model for lightning protection, charging pile and power distribution acceptance; highest sales volume
✅ HT2303 (High Version with Soil Resistivity)
Measurements: 2/3-pole earth resistance, earth voltage, soil resistivity ρ (4-pole method)
Reichweite: Earth resistance 0.01~4000Ω; Soil resistivity 0~4000kΩ·m
Lagerung:100 Gruppen, limit alarm, REL
Positionierung: Lightning protection labs and earth grid survey for soil resistivity design; upgraded version of HT2302
✅ HT2304 (Professional Enhanced Version)
4-pole soil resistivity, upgraded anti-interference circuit, AC earth voltage up to 600V
Operates under heavy power-frequency interference (Umspannwerke, near high voltage lines)
Higher accuracy margin, preferred by third-party certification labs
Other HABOTEST Earthing-related Instruments (Not part of HT23xx lead tester series, reference for selection)
- HT5910: Loop resistance + RCD tester (measures loop resistance and residual current devices, NOT earth resistance tester)
- HABOTEST has no proprietary clamp-type earth resistance tester (clamp-on earth testers are separate category; ETCR is mainstream brand)
Model Selection Comparison Table
| Modell | Soil Resistivity | Resistance Range | Storage Groups | Recommended Application |
| HT2301 | ❌ | 0.01~2000Ω | 50 | Simple inspection by electricians, begrenztes Budget |
| HT2302 | ❌ | 0.01~4000Ω | 100 | Blitzschutz, charging pile and cabinet earthing acceptance (Am häufigsten verwendet) |
| HT2303 | ✅ | 0.01~4000Ω | 100 | Blitzschutztest + Untersuchung des Bodenwiderstands |
| HT2304 | ✅ | 0.01~4000Ω | 100 | Hohes Störfeld, Professionelle Tests durch Dritte |
Auswahlempfehlungen
Nur Erdwiderstandsakzeptanz (Ladestapel / Gebäudeblitz / Geräteschutzerde) → HT2302 ist ausreichend
Erfordern eine Messung des Bodenwiderstands und eine vorläufige Untersuchung des Erdungsnetzdesigns → HT2303