Entry-level economical three-phase VFD, version without built-in EMC filter
Erklärung des Modellcodes
ATV310: Altivar Easy 310 Serie (simple general-purpose vector type)
H: Rahmengrößencode
U75: Heavy-duty rating 7.5 kW
N4: Three-phase 380~460 V
E: Ohne eingebauten EMV-Filter (Contrast: ATV310HU75N4A with built-in EMC filter)
⚡ Rated Power & Aktuell
Robust (HD): 7.5 kW / 10 PS, continuous output 17 A; 60 s overload 170~200% (25.5 A)
Normaler Dienst (ND): 11 kW / 15 PS, continuous output 22.8 A; 60 s overload 110% (25.1 A)
Eingang: Three-phase 380–460 V, 50/60 Hz
Nettogewicht: 3.7 kg; fan cooling standard, Lärm 50 dB(A)
🧠 Control Modes
V/F-Steuerung (linear, quadratic energy-saving curve)
Sensorlose Vektorsteuerung (SVC, Open-Loop-Vektor)
Ausgangsfrequenz: 0.5 ~ 400 Hz
Schaltfrequenz: 2 ~ 12 kHz einstellbar, Werkseinstellung 4 kHz
Speed regulation range: 1:20 for asynchronous motors
Bremsen: Ca. 70% braking torque without braking resistor; bis zu 150% braking torque with external braking resistor
Slip compensation adjustable
📶 Communication & E/A
Standard Modbus RTU, 2-wire RS485, front RJ45 port
Baudrate: 4800/9600/19200/38400 bps, address 1–247
Terminals: 4 digital inputs LI, 1 analog input AI, Relaisausgang; supports potentiometer, Terminal Start/Stopp, Mehrgeschwindigkeit, PID (Lüfter & Pumpe)
🌡️ Ambient & Zertifizierungen
Schwere Beanspruchung: -10 ~ 55 °C without derating; short-time max 60 °C
Beschichtung: 3C3/3S2, suitable for standard control cabinets and light dust environments
Zertifizierungen: CE, EAC, RoHS, WEEE
Schutz: IP20 (Nur zur Schrankmontage)
📌 Typische Anwendungen
Förderer, Fans, Pumps, general machine tools, Materialtransport, speed regulation for ordinary asynchronous motors, suitable for simple speed control and constant pressure water supply.
Schneider ATV310 VFD Fault Code List (Compatible with ATV310HU75N4E)
Notiz: Codes starting with F = fault, locked trip; codes starting with -= status prompt, NOT faults. Fehler-Reset: Leistungszyklus / keypad reset / Kommunikation zurückgesetzt
| Fehlercode | Fehlerbeschreibung | Häufige Ursachen | Abhilfemaßnahmen |
| F001 | Pre-charge fault | Failed DC bus pre-charge on power-up, faulty charging circuit or bus capacitor | Check input power, Gleichrichterbrücke, Ladewiderstand; internal hardware fault requires repair |
| F002 | Power board identification error | Mismatched control board & Leistungsplatine, inkompatible Firmware | Modell überprüfen, reload firmware, replace matching boards |
| F003 | Power board incompatibility | Wrong power board model, mixed spare parts | Replace with original matching power board |
| F004 | Internal serial communication fault | Communication loss between control board and power board, loose ribbon cable | Re-seat ribbon cable; replace board if damaged |
| F005 | Region code error | Mismatched firmware regional version | Flash correct regional firmware |
| F006 | Current sensing circuit fault | Sampling circuit failure, damaged Hall sensor | Internal hardware fault, send for repair |
| F007 | Internal temperature sensor fault | Broken or faulty IGBT temperature sensor | If alarm occurs immediately on cold power-up, sensor is almost certainly damaged |
| F008 | CPU-Fehler | Main controller anomaly, program runaway | Aus- und wieder einschalten; if ineffective, Steuerplatine austauschen |
| F009 | Over-braking (braking overspeed) | Too short deceleration time, hohe Lastträgheit, faulty braking circuit | Verzögerungszeit verlängern; install braking resistor / Bremseinheit; check bus voltage |
| F010 | Überstrom | Motor jam, Motorkurzschluss, incorrect auto-tune, load surge | Check mechanical jamming; test motor insulation with megger; reduce switching frequency; re-run motor auto-tune |
| F011 | VFD overheat | Verstopfter Luftkanal, defekter Lüfter, hohe Umgebungstemperatur, continuous heavy load | Clean cooling air path; Lüfter prüfen; reduce ambient temperature; Betrieb herabsetzen |
| F012 | Process overload | PID / process protection threshold triggered, sustained overload | Verify process overload parameters, check load condition |
| F013 | Motorüberlastung | Long-term motor overcurrent, thermal protection threshold set too low | Check motor for stall; verify motor nameplate data; extend thermal protection time |
| F014 | Output single phase loss | Broken motor cable, burnt output contactor contact, loose terminal | Check U/V/W output wiring, terminals and output contactor |
| F015 | All output phases lost | Motor disconnected, all output contactors open, no-load detection alarm for small motors | Überprüfen Sie die Motorverkabelung; disable phase loss detection for no-load test (parameter 605=00) |
| F016 | Überspannung im DC-Bus | High grid voltage, regenerative Energie beim Abbremsen, failed braking circuit | Eingangsspannung prüfen; Verzögerungszeit verlängern; Bremswiderstand einbauen |
| F017 | Verlust der Eingangsphase | Missing one incoming phase, poor contact of circuit breaker, Sicherung durchgebrannt | Check upstream power supply, circuit breaker and incoming terminals |
| F018 | Motorkurzschluss | Inter-phase short circuit on motor winding or power cable | Disconnect motor and test VFD separately; megger motor insulation |
| F019 | Erdschluss | Output cable earth fault, Motorisolationsausfall, large leakage with multiple parallel motors | Megger motor and cable insulation; install output reactor |
| F020 | IGBT short circuit | Power module breakdown | Do NOT repeatedly power on; send for repair and replace power module directly |
| F021 | Kurzschluss am Ausgang | Direct short circuit on VFD output side | Power off and inspect power cable to eliminate short point |
| F027 | IGBT over-temperature | Excessive IGBT junction temperature, schlechte Wärmeableitung | Prioritize cooling fan and air duct inspection, Belastung reduzieren |
| F030 | DC bus undervoltage | Grid voltage dip, kurzzeitiger Stromausfall, insufficient incoming capacity | Check incoming voltage; inspect circuit breaker and terminal connections; confirm grid capacity |
Status Prompt Codes (Not Faults, Status Indication Only)
| Code | Bedeutung |
| 1 | Fast stop activated |
| 6 | Freewheel stop (coast stop) activated |
| 0 | Freewheel stop complete, stehen zu |
Supplementary Practical Information
- Fault history: Parameters 910~921 to view historical faults and current/voltage readings at fault occurrence
- Phase loss detection parameter: 605 output phase loss detection (00=disabled, 01=enabled). Disable temporarily for no-load commissioning, keep enabled for formal operation
- Motor auto-tune: Parameter 318. Auto-tune is recommended after motor replacement to reduce F010 and F013 alarms
- Methoden zurücksetzen: Keypad reset, digital terminal assigned fault reset, Modbus communication reset, power cycle reset
Complete Model List for Schneider Altivar Easy ATV310 VFD
Notiz: Altivar Easy main product is ATV310. Stromspannung: three-phase 380–460 V. Suffix E = without built-in EMC filter, A = with built-in EMC filter. HD = heavy-duty power rating, ND = normal-duty power rating
Erläuterung der Modellcodierung
ATV310: Altivar Easy 310 economical general-purpose vector VFD
H: Frame code
Leistungscodes: 037=0.37 kW, 075=0.75 kW, U15=1.5 kW, U22=2.2 kW, U30=3 kW, U40=4 kW, U55=5.5 kW, U75=7.5 kW, D11=11 kW, D15=15 kW, D18=18.5 kW, D22=22 kW
N4: Three-phase 380~460 V
E: Without built-in EMC filter|A: Mit eingebautem EMV-Filter
E-version List (No Built-in EMC Filter, your ATV310HU75N4E is in this list)
| Modell | HD Heavy Duty | ND Normal Duty |
| ATV310H037N4E | 0.37 kW / 0.5 PS | 0.55 kW / 0.75 PS |
| ATV310H075N4E | 0.75 kW / 1 PS | 1.1 kW / 1.5 PS |
| ATV310HU15N4E | 1.5 kW / 2 PS | 2.2 kW / 3 PS |
| ATV310HU22N4E | 2.2 kW / 3 PS | 3 kW / 4 PS |
| ATV310HU30N4E | 3 kW / 4 PS | 4 kW / 5 PS |
| ATV310HU40N4E | 4 kW / 5 PS | 5.5 kW / 7.5 PS |
| ATV310HU55N4E | 5.5 kW / 7.5 PS | 7.5 kW / 10 PS |
| ATV310HU75N4E | 7.5 kW / 10 PS | 11 kW / 15 PS |
| ATV310HD11N4E | 11 kW / 15 PS | 15 kW / 20 PS |
| ATV310HD15N4E | 15 kW / 20 PS | 18.5 kW / 25 PS |
| ATV310HD18N4E | 18.5 kW / 25 PS | 22 kW / 30 PS |
| ATV310HD22N4E | 22 kW / 30 PS | 30 kW / 40 PS |
A-version List (Gleiche Macht, Eingebauter EMV-Filter, widely used in domestic projects)
Change suffix E → A, z.B.
ATV310H037N4A, ATV310H075N4A, ATV310HU15N4A … ATV310HD22N4A
Ergänzen: Another Altivar Easy Family Series ATV610 (High-power Easy Range)
ATV610 also belongs to Easy series, larger power range, 380–460 V three-phase, mainly for fan & Pumpenanwendungen
ATV610D11N4, ATV610D15N4, ATV610D18N4, ATV610D22N4, ATV610D30N4, ATV610D37N4, ATV610D45N4, ATV610D55N4, ATV610D75N4, ATV610D90N4, ATV610C11N4, ATV610C13N4, ATV610C16N4
General Common Parameters for Full ATV310 Range
Kontrolle: V/F + Sensorless Vector SVC
Kommunikation: Standard Modbus RTU (RJ45)
E/A: 4AUS, 1KI, 1 Relaisausgang
Schutz: IP20, Schrankmontage
Anwendung: Förderer, Fans, Pumps, general OEM machinery
Auswahlnotizen
- Heavy-duty applications (Heben, Extrusion, shock load) select according to HD rating; Fans & pumps with smooth light load can use ND rating
- For export CE EMC compliance, select A (eingebaute EMV); E version requires external EMC filter
- Upgrade-Alternative: ATV320 (höhere Leistung, encoder support, more expansion cards)
Schneider ATV310 (Altivar Easy) Leitfaden zur Anwendungsauswahl
Voraussetzung: ATV310 is an economical open-loop vector VFD, no encoder interface, closed-loop vector not supported. Two capacity ratings: HD (Robust) / ND (Normaler Dienst). Suffix A=built-in EMC filter, E=no built-in EMC filter, three-phase 380~460 V.
Selection rule: Shock load, häufiges Start-Stopp, stall risk → select HD; Fans & pumps with smooth light load → ND is acceptable
- Rated Current Quick Reference Table (Base Data)
| Modell | HD Power | HD Continuous Current | ND Power | ND Continuous Current |
| ATV310H037N4 | 0.37 kW | 2.1 A | 0.55 kW | 2.7 A |
| ATV310H075N4 | 0.75 kW | 3.0 A | 1.1 kW | 4.2 A |
| ATV310HU15N4 | 1.5 kW | 4.1 A | 2.2 kW | 5.5 A |
| ATV310HU22N4 | 2.2 kW | 5.5 A | 3.0 kW | 7.2 A |
| ATV310HU30N4 | 3.0 kW | 7.2 A | 4.0 kW | 9.4 A |
| ATV310HU40N4 | 4.0 kW | 9.4 A | 5.5 kW | 11.7 A |
| ATV310HU55N4 | 5.5 kW | 11.7 A | 7.5 kW | 16.5 A |
| ATV310HU75N4 | 7.5 kW | 17.0 A | 11 kW | 22.8 A |
| ATV310HD11N4 | 11 kW | 24.0 A | 15 kW | 30.0 A |
| ATV310HD15N4 | 15 kW | 30.0 A | 18.5 kW | 37.0 A |
| ATV310HD18N4 | 18.5 kW | 37.0 A | 22 kW | 43.0 A |
| ATV310HD22N4 | 22 kW | 43.0 A | 30 kW | 57.0 A |
- Anwendungsklassifizierung + Selection Scheme + Accessories Recommendation
Kategorie 1: Centrifugal Fans & Kreiselpumpen (Smooth Load, Quadratic Torque, ND Preferred)
Load characteristics: Niedriges Anlaufdrehmoment, stabiler Betrieb, no shock; suitable for PID constant pressure / constant airflow, long continuous running
Selection rule: Select by ND power rating
Recommended suffix: A for export CE projects (eingebaute EMV); E for standard domestic cabinets with independent EMC solution
Zubehör:
Braking resistor normally not required (coast stop acceptable)
Parameter: V/F quadratic curve, PID enable
Einschränkung: Large inertia smoke exhaust fans, high-temperature induced draft fans, suggest one size up, select HD
Beispiel: 11 kW centrifugal pump → ATV310HU75N4A (ND=11 kW)
Kategorie 2: General Conveyors, Belt Lines, Roller Tables (Konstantes Drehmoment, Intermittent Start-Stop, HD Preferred)
Load characteristics: Konstantes Drehmoment, moderate starting resistance, häufiges Start-Stopp, occasional material jam shock
Selection rule: Strictly select by HD rating, motor rated current ≤ VFD HD current
Zubehör:
Long deceleration, high inertia belt: add braking resistor
Multi-speed control uses built-in DI terminals directly, no expansion card required
Einschränkung: High-speed positioning, high-precision synchronization not suitable for ATV310, use ATV320 instead
Beispiel: 7.5 kW belt conveyor → ATV310HU75N4A (HD=7.5 kW)
Kategorie 3: Mixing Tanks, Mixer (High Starting Torque, Schwere Ladung)
Load characteristics: Hohes Anlaufdrehmoment, high resistance from tank media, high stall risk, konstantes Drehmoment
Selection rule: HD selection, reserve 1.1~1.2 safety margin; motor rated current ≤ 90% of VFD HD current
Zubehör: Braking resistor for emergency stop; motor auto-tune recommended
High viscosity mixing: select one power size up
Beispiel: 5.5 kW mixing motor → Prefer ATV310HU75N4 (HD 7.5 kW) for margin
Kategorie 4: Screw Pumps, Gear Pumps, Positive Displacement Pumps (Konstantes Drehmoment)
Load characteristics: Medium starting torque, pressure fluctuation, dry running prohibited
Selection rule: HD for normal operation; upsizing for heavy pressure fluctuation & häufiges Start-Stopp
Zubehör: PID-Konstantdruck, add pressure feedback AI
Beispiel: 4 kW screw pump → ATV310HU40N4 (HD 4 kW)
Kategorie 5: Holzbearbeitungsmaschinen, Grinders, General Machine Tool Spindles (Continuous Constant Torque)
Load characteristics: Continuous cutting, load fluctuation, stable torque requirement
Selection rule: HD selection; upsizing for heavy cutting shock
❌ Not applicable: Spindle positioning, rigid tapping, closed-loop control → ATV310 has no encoder support, use ATV320
Kategorie 6: Heben, Hoist, Winch, Hydraulic Main Pump ( ATV310 NOT Recommended)
Wichtige Warnung: ATV310 is economical open-loop vector VFD, no brake logic, no torque verification, no safety functions. NOT allowed for lifting applications. Hoisting duty requires ATV320 + safety relay or dedicated hoist VFD.
Kategorie 7: Kühlturmventilatoren, Roof Fans, Exhaust Fans (Light Load Quadratic Torque)
Auswahl: ND rating, best cost performance
Notiz: Ambient temperature below -10 °C requires cabinet heater, VFD derating applies
Cabinet for outdoor installation prefers A version built-in EMC to avoid interference
Kategorie 8: Multi-motor Parallel Drive (Synchronous drag, multiple small motors)
Auswahl: Sum of all motor rated currents matched against HD current; motor auto-tune must be disabled, run in V/F mode
Zubehör: Fit thermal relay for each motor for individual overload protection; output reactor recommended
- Suffix A / E Selection Judgment (EMV)
- ATV310…N4A (Eingebauter EMV-Filter)
Geeignet: EU CE export, control cabinet close to sensors, Instrumente, PLC communication cables, high EMC requirement
- ATV310…N4E (No Built-in EMC Filter)
Geeignet: Standard domestic factory, power cables separated from signal wires, project procures separate external EMC filter; niedrigerer Preis
Risiko: Direct operation may interfere with sensors, weighing instruments, RS485-Kommunikation
- Ambient Derating Rules
Ambient temperature 45~55 °C: HD rating no derating; >55 °C derating mandatory
Höhe >1000 M: herabsetzen 4% pro zusätzlich 1000 M; ATV310 not recommended above 2000 M
Staub, ätzendes Gas: Enclosed cabinet + air conditioning required; standard ATV310 is 3C3 coated
- When to Upgrade from ATV310 to ATV320
Select ATV320 if any condition below applies:
- Encoder closed-loop control, high precision speed / Positionierung / synchronization required
- Safe torque off STO safety function required
- Multiple expansion cards needed (encoder card, Profinet/EtherNet/IP Ethernet card)
- Heben, Aufzug, hoist loads
- Severe dynamic shock, fast torque response required
- Übersichtstabelle zur Schnellauswahl
| Anwendungstyp | Torque Characteristic | Recommended Rating | Empfohlenes Suffix | Braking Resistor Suggested |
| Radialventilator / Pumpe | Quadratic Torque | ND | A (Export) / E (Inländisch) | NEIN |
| Belt Conveyor, Roller Table | Konstantes Drehmoment | HD | A / E | Yes for high inertia |
| Mischen, High Viscosity Blending | Konstantes Drehmoment, High Starting Torque | HD + Upsize One Step | A | Yes for emergency stop |
| Positive Displacement Pump (Screw Pump) | Konstantes Drehmoment | HD | A / E | Optional |
| General Machine Tool Spindle | Constant Torque with Fluctuation | HD | A | NEIN |
| Multi-motor Parallel V/F Drive | Combined | Total Current Match HD | A | Optional |
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter