Schneider RSB2A080U7 Plug-in Interface Relay - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider RSB2A080U7 Plug-in Interface Relay - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

SPS/

Schneider RSB2A080U7 Plug-in Interface Relay

Serie: Harmony RSB Plug-in Interface Relay (Gesucht) | Status: Obsolete ✅ Model Explanation RSB: RSB series plug-in interface relay 2A: 2 Wechslerkontakte (2CO / DPDT, 2NO+2NC) 080: Rated contact current 8A U7: 240V AC-Spule, keine LED, no test button 📌 Key Specifications Coil voltage: 240V und (50/60Hz) Kontakte: 2 C/O (DPDT), AgNi silver-nickel ...

  • Produktdetails

Serie: Harmony RSB Plug-in Interface Relais (Gesucht) | Status: Veraltet

✅ Model Explanation

RSB: RSB series plug-in interface relay

2A: 2 Wechslerkontakte (2CO / DPDT, 2NO+2NC)

080: Rated contact current 8A

U7: 240V AC-Spule, keine LED, Keine Testtaste

📌 Wichtige Spezifikationen

Spulenspannung: 240V und (50/60Hz)

Kontakte: 2 C/O (DPDT), AgNi silver-nickel contacts

Kontaktbewertung: 8A bei 250 VAC / 8A @28VDC

Max switching voltage: 250VAC / 300VDC

Coil resistance: 33kΩ; Coil current approx. 7.3mA

Arbeiten / Freigabezeit: 20MS

Betriebstemperatur: -40℃ ~ +70℃

Kontrollleuchte: Keiner; Testtaste: Keiner

Montage: Plug-in-Typ, used with base

Standards: IEC61810-1, UL508, CSA, EAC certification

🧩 Matching Bases (8-Stift, 2CO)

RSZE08P: Spring-cage terminal base

RSZE1S48M: Screw terminal base (alte Version)

🔄 Replacement Recommendations

No direct one-to-one OEM equivalent. Prefer same-spec models within the same series:

  1. RSB2A080M7: 230VAC, 8A, 2CO (most common in domestic market, keine LED, Keine Testtaste)
  2. If LED indicator required: RSB2A080M7S (Relais + base assembly)
  3. Alternative Schneider RXG series: RXG22M7 (230VAC, 8A, 2CO, incompatible base)

Notiz: 240VAC and 230VAC are generally compatible under normal grid conditions. Confirm coil specification for voltage-sensitive circuits.

📎 Applications

PLC/controller DO isolation, small contactor coil driving, signal transfer, cabinet interface isolation. Widely used in industrial control, HVAC and packaging machinery.

📌 Additional Info

Verpackung: 10 Stück pro Karton. It is an obsolete spare part, only stock available. Für neue Projekte nicht empfohlen.

Application Fields of Schneider RSB2A080U7 (240VAC coil, 2CO, 8A Interface Relay)

Kernfunktion: Signalisolierung, level conversion and small-load driving inside control cabinets. The 240VAC coil is designed for AC control circuits. Plug-in design facilitates spare parts replacement, hauptsächlich für die Nachrüstung und Wartung vorhandener Geräte (obsolete model).

  1. Industrielle Automatisierung (Primäre Anwendung)

PLC digital output isolation: PLC DO drives contactor coils, solenoid valves and indicator lamps to suppress electrical interference and protect PLC modules

Local cabinet control loops, hard-wired logic, signal transfer and passive dry contact expansion

Control panels for machine tools, automatische Produktionslinien, conveyor systems and assembly equipment

  1. HVAC

Auxiliary control for air handling units, Frischlufteinheiten, Klappenantriebe, water valves and fan start/stop

DDC output isolation for building automation, signal switching for heating and cooling units

  1. Verpackung, Textil & Druckmaschinen

Auxiliary circuits for packaging machines, Beutelherstellungsmaschinen, textile machines and printing machines; driving small electromagnetic devices, alarm lamps and counters

Signal switching for local machine control panels

  1. Elektrische Gebäudesysteme

Group lighting control, Fans, Abluftventilatoren, electric roller shutters and auxiliary access control outputs

Auxiliary signal and alarm loop switching in low-voltage distribution cabinets and control boxes

  1. Wasserversorgung & Abwasserbehandlung

Auxiliary pump control, liquid level signal transfer, dosing equipment and valve bank control loops

Instrument signal isolation to protect transmitters, water quality analyzers and other low-voltage devices

  1. Other Supporting Equipment

Small test equipment, power cabinets, medical auxiliary equipment and warehouse logistics equipment

Export control cabinets for 240VAC grid markets and spare part replacement for overseas legacy machines

✅ Geeignete Betriebsbedingungen

Steuerseite: 240VAC AC control circuit; Max load: 8A, 250VAC low-power loads

Vorteile: 2 changeover contacts providing NO and NC signals simultaneously; plug-in base for fast maintenance

Einschränkungen: Not suitable for direct driving of high-power motors, high-frequency switching or heavy inductive impulse loads (RC snubber recommended)

❗ Selection Reminder

This model has a 240V AC coil. For new domestic projects with 230VAC supply, RSB2A080M7 is preferred. RSB2A080U7 is mostly used for overseas equipment and legacy unit maintenance replacement.

Replacement List for Schneider RSB2A080U7 (No Exact OEM Equivalent)

Originalmodell: RSB2A080U7|240VAC coil, 2CO, 8A, keine LED, Keine Testtaste, plug-in RSB series, veraltet

Kompatible Basen: RSZE08P (spring cage) / RSZE1S48M (Schraubklemme)

  1. Same RSB Series (Direct Base Reuse, Pinout Compatible)
  2. RSB2A080M7 (Top Choice for Maintenance)

Spezifikationen: 230VAC coil, 2CO, 8A, keine LED, Keine Testtaste

Beschreibung: 230VAC and 240VAC are generally compatible in most grid environments. Direct plug-in to original base without rewiring, mainstream replacement for domestic maintenance

Unterschied: Nominal coil voltage 230V vs original 240V; Kontakte, current rating and pinout are identical

  1. RSB2A080M7S (Montage: Relais + Base)

Supplied with base, suitable for new projects where separate base procurement is not desired

  1. RSB2A080M7PV (LED indicator version)

230VAC, 2CO, 8A with LED indicator; ideal for retrofit requiring visual status check

⚠️ Warnung: If equipment strictly requires 240VAC (overseas grid with tight voltage tolerance), M7 (230V) is not suitable. Cross-brand 240VAC models should be selected instead.

  1. Other Schneider Series (Base Not Interchangeable, Base Must Be Replaced)
  2. RXG22M7

RXG series, 230VAC, 2CO, 8A; plug-in interface relay with similar size and performance

Nachteil: Different base model, original base cannot be reused; RXG base required

  1. RXM2AB2P7 (RXM-Miniaturrelais)

230VAC, 2CO, 8A; weitläufig bestückt; different outline and base, suitable for new cabinet layout

  1. Cross-brand Compatible Replacements (For Export/Maintenance, Strict 240VAC Requirement)

Anforderungen: 2CO, 8A, 240VAC coil, 8-Pin-Plug-in

Omron: MY2N-CR 240VAC (8A, DPDT)

Weidmüller: DRM2700240L

Phoenix Contact: REL-IR2 / 240Wechselstrom

Chint: NXJ-2Z/240VAC

Wichtig: Verify pin assignment before replacement. Pin layout varies between brands; do not plug in blindly.

  1. Replacement Selection Rules

✅ Domestic legacy equipment maintenance, 220/230V-Gitter: Prioritize RSB2A080M7, reuse existing base with minimal modification

✅ Export equipment, stable 240VAC grid: Prioritize cross-brand 240VAC coil models

✅ Status indication required: RSB2A080M7PV

✅ New projects, no base restriction: RXG22M7 / RXM2AB2P7

  1. Risikohinweise

Coil voltage is the critical difference: U7=240VAC; M7=230VAC. Do not mix for voltage-sensitive circuits

Contact specs: All adopt AgNi silver-nickel contacts, 8A@250VAC. RC snubber is recommended for inductive loads

All RSB series share the same mechanical and electrical life ratings, differing only in coil voltage and LED option

Full Model List of Schneider Harmony RSB Plug-in Interface Relay (Gesucht)

Serienübersicht: Plug-in interface relay, three contact configurations:

RSB1A120: 1CO, 12A

RSB1A160: 1CO, 16A

RSB2A080: 2CO, 8A (RSB2A080U7 belongs to this subgroup)

Suffixdefinition:

Suffix D = DC coil; Suffix 7 = AC coil (50/60Hz)

PV = with LED indicator + varistor surge protection; S = relay + base assembly

No PV suffix: keine LED, Keine Testtaste; No mechanical test button available for this series

Bases: RSZE08P (spring-cage terminal) / RSZE1S48M (Schraubklemme)

  1. DC Coil Models
Spulenspannung1CO 12A1CO 16A2CO 8A
6In DCRSB1A120RDRSB1A160RDRSB2A080RD
12In DCRSB1A120JDRSB1A160JDRSB2A080JD
24In DCRSB1A120BDRSB1A160BDRSB2A080BD
48In DCRSB1A120EDRSB1A160EDRSB2A080ED
60In DCRSB1A120NDRSB1A160NDRSB2A080ND
110In DCRSB1A120FDRSB1A160FDRSB2A080FD
  1. AC Coil Models (Basisversion, Keine LED)
Spulenspannung1CO 12A1CO 16A2CO 8A
24V undRSB1A120B7RSB1A160B7RSB2A080B7
48V undRSB1A120E7RSB1A160E7RSB2A080E7
120V undRSB1A120F7RSB1A160F7RSB2A080F7
230V undRSB1A120P7RSB1A160P7RSB2A080P7
230V und (M7 domestic marking)RSB1A120M7RSB1A160M7RSB2A080M7
240V und (Veraltet)RSB1A120U7RSB1A160U7RSB2A080U7

III. PV Suffix Models (LED + Überspannungsschutz, Wechselstrom)

Spulenspannung1CO 12A1CO 16A2CO 8A
24V undRSB1A120B7PVRSB1A160B7PVRSB2A080B7PV
120V undRSB1A120F7PVRSB1A160F7PVRSB2A080F7PV
230V undRSB1A120P7PVRSB1A160P7PVRSB2A080P7PV
230V AC M7RSB1A120M7PVRSB1A160M7PVRSB2A080M7PV
  1. S Suffix Assembly Models (Relais + Base, DIN Rail Mount Directly)

Regel: Add S to the end of base model, z.B. RSB2A080M7S, RSB2A080P7S, RSB1A120B7S

Supplied complete with base, no separate RSZE base purchase required, ideal for fast new project selection

  1. Aufschlüsselung der Modellcodierung (RSB)

RSB + Kontaktmenge + A + Nennstrom + Spannungscode + Optional PV/S

RSB: Harmony plug-in interface relay

1A = 1CO; 2A = 2CO

120=12A; 160=16A; 080=8A

Last two characters: voltage code

JD=12VDC, BD=24VDC, ED=48VDC, FD=110 VDC

B7=24VAC, F7=120VAC, M7=230VAC, P7=230VAC, U7=240VAC (veraltet)

PV: LED-Anzeige + Überspannungsschutz; S: Montage (Relais + Base)

  1. Wichtige Hinweise
  2. RSB2A080U7 / RSB1A120U7 / RSB1A160U7 (240VAC) are all obsolete, only stock spares available. M7/P7 are preferred for new projects
  3. Uniform AgNi silver-nickel contacts, suitable for PLC isolation, HVAC, Verpackung, water treatment and other industrial control circuits
  4. Identical pinout within the same series. Same contact configuration can be swapped on the same base
  5. Mechanisches Leben: 10,000,000 Operationen; Elektrisches Leben: 100,000 Betrieb unter ohmscher Last

Vorher: