Standardbezeichnung: iC65N 2P C32A (commonly abbreviated as IC65N-2P32A in the market; C-curve by default)
Material codes: A9F18232 (C-Kurve); A9F17232 (B-curve); A9F19232 (D-Kurve)
✅ Modelldefinition
iC65: Acti9-Serie Miniatur-Leistungsschalter
N: Breaking capacity class 6kA (iC65H=10kA, iC65L=15kA)
2P: 2-Pole, simultaneous disconnection of phase and neutral for protection
32A: Rated current In=32A
C-Kurve (am häufigsten): Magnetic trip 5~10In, zur Beleuchtung geeignet, socket outlets and general power loads; B-curve 3~5In (low-voltage circuits); D-curve 10~20In (Motoren, transformers with inrush current)
📋 Grundlegende elektrische Spezifikationen
Rated voltage Ue: AC 230/400V, 50/60Hz
Rated short-circuit breaking capacity Icn: 6kA @400V AC (GB10963.1 / IEC60898-1)
Schutz: Thermisch-magnetischer Auslöser (Überlast + short-circuit dual protection), disconnector function
Montage: DIN35mm rail, width 36mm (2 Module)
Isolationsspannung Ui: 500V; Stoßspannungsfestigkeit Uimp: 6kV
Current limiting class: Klasse 3
Terminal protection IP20, IP40 when installed inside enclosure; CCC, CE-Zertifizierung
Verdrahtung: Von oben nach unten / bottom-in top-out both acceptable
📌 Typische Anwendungen
Main incoming breaker for residential buildings, single-phase distribution circuits in shops
Beleuchtung, Steckdosenschaltungen, ordinary fans and water pumps (C-Kurve)
Can be assembled with Vigi iC65 residual current add-on block to form RCBO
🔄 Replacement Information
Vorgängermodell: C65N 2P32A (eingestellt)
Schneider equivalent upgrade: iC60N 2P C32A (A9F74232)
Inländisches Äquivalent: Chint NXB-63 2P C32A, Delixi DZ47s 2P C32A
⚙️ Optional Accessories (compatible within series)
Vigi iC65 RCD add-on block (30mA Typ A)
iMX shunt trip release, iMN undervoltage release, iOF auxiliary contact, iSD fault alarm contact
Differences between iC65N series and iC60N series
iC65N: China domestic version (CCC); iC60N: International general version (CE/IEC). Same outline, module width and basic tripping characteristic; 6kA breaking capacity per IEC60898. Directly interchangeable on DIN rail. But they differ in certification, applicable standards, contact status indication, available trip curves, accessory system and material codes.
- Marktpositionierung & Zertifizierung
iC65N: Model dedicated for Chinese market, CCC-zertifiziert, standard GB10963.1 (identical to IEC60898-1). No separate CE for overseas acceptance, not recognized for export projects.
Material prefix: A9F18xxxx (C-Kurve). Beispiel: 2P C32A = A9F18232
iC60N: Global Acti9 international version, CE+IEC certified, konform mit IEC60898-1 (household distribution) + IEC60947-2 (industrial disconnector). Preferred for export panels, overseas complete sets and foreign-invested projects.
Material prefix: A9F74xxxx (C-Kurve). Beispiel: 2P C32A = A9F74232
- Bruchkapazität (Hauptunterschied)
iC65N N grade: 6kA @400V (IEC60898 only)
iC60N N grade: 6Die (IEC60898) / 10Die (IEC60947 industrial condition), higher breaking capacity under industrial standard
- Available Trip Curves
iC65N: B / C / D
iC60N: B / C / D / K / Z / MA (K for transformers, Z for electronic circuits, MA fixed magnetic trip for motors; wider selection for industrial control)
- Front Panel Indication (VisiSafe / VisiTrip)
iC65N: Simplified China version. Green handle = open position; red marker for fault trip
iC60N: Full VisiSafe (visible true contact separation) + VisiTrip (independent red window for fault trip). Widely required by overseas safety specifications and site verification
- Zubehörkompatibilität
Accessories look identical but have separate material code ranges. Strongly recommended to match accessories within the same series
iC65: iOF / iSD / iMX / iMN, Vigi iC65 RCD add-ons (China A9 domestic accessories)
iC60: Vigi iC60, overseas auxiliary / Rangierfahrt; compatible with PowerTag smart energy monitoring modules (iC65 generally not fitted with overseas smart modules)
- Dimension & Austauschbarkeit
✅ Same module size: 1P=18mm, 2P=36mm, direct DIN35 rail swap, wiring from top or bottom allowed
⚠️ Important risk note: iC65N preferred for domestic cabinets in China; for export, foreign-owned projects or CE certificate requirement, select iC60N. iC65N cannot be substituted, overseas inspectors do not accept iC65N certificates.
- Auswahlvergleichstabelle
| Artikel | iC65N | iC60N |
| Sales Territory | Mainland China only | Global |
| Main Certification | CCC | CE, IEC |
| Anwendbarer Standard | GB10963.1 | IEC60898-1 + IEC60947-2 |
| Bruchkapazität (N) | 6Die | 6Die (Verteilung) /10Die (industriell) |
| Trip Curves | B/C/D | B/C/D/K/Z/MA |
| Statusanzeige | Basic open indication | VisiSafe+VisiTrip dual indication |
| Typische Anwendung | Wohnen, domestic construction, local panel build | Export, foreign-owned factory, Auslandsprojekt, industrial distribution |
- Reference for your model 2P32A
iC65N 2P C32A: A9F18232 (regular stock for China domestic)
iC60N 2P C32A: A9F74232 (for export / foreign invested projects)
- Prefix Coding Rule
1) iC65N (China CCC version)
B-curve: A9F17xxxx
C-Kurve: A9F18xxxx (Mainstream)
D-Kurve: A9F19xxxx
5th digit = pole count: 1=1P; 2=2P; 3=3P; 4=4P
Last two digits = rated current: 01=1A, 02=2A…32=32A, 63=63A
2) iC60N (International CE version)
B-curve: A9F73xxxx
C-Kurve: A9F74xxxx (mainstream for export)
D-Kurve: A9F75xxxx
Pole & current coding rule identical to iC65N, one-to-one mechanical interchange
- iC65N Full Model & Material Code List (B/C/D, 1P/2P/3P/4P, 1~63A)
(1) 1P Single Pole
| Aktuell | B-curve(A9F171xx) | C-Kurve(A9F181xx) | D-Kurve(A9F191xx) |
| 1A | A9F17101 | A9F18101 | A9F19101 |
| 2A | A9F17102 | A9F18102 | A9F19102 |
| 4A | A9F17104 | A9F18104 | A9F19104 |
| 6A | A9F17106 | A9F18106 | A9F19106 |
| 10A | A9F17110 | A9F18110 | A9F19110 |
| 16A | A9F17116 | A9F18116 | A9F19116 |
| 20A | A9F17120 | A9F18120 | A9F19120 |
| 25A | A9F17125 | A9F18125 | A9F19125 |
| 32A | A9F17132 | A9F18132 | A9F19132 |
| 40A | A9F17140 | A9F18140 | A9F19140 |
| 50A | A9F17150 | A9F18150 | A9F19150 |
| 63A | A9F17163 | A9F18163 | A9F19163 |
(2) 2P Two Pole (your 2P32A here)
| Aktuell | B-curve(A9F172xx) | C-Kurve(A9F182xx) | D-Kurve(A9F192xx) |
| 1A | A9F17201 | A9F18201 | A9F19201 |
| 2A | A9F17202 | A9F18202 | A9F19202 |
| 4A | A9F17204 | A9F18204 | A9F19204 |
| 6A | A9F17206 | A9F18206 | A9F19206 |
| 10A | A9F17210 | A9F18210 | A9F19210 |
| 16A | A9F17216 | A9F18216 | A9F19216 |
| 20A | A9F17220 | A9F18220 | A9F19220 |
| 25A | A9F17225 | A9F18225 | A9F19225 |
| 32A | A9F17232 | A9F18232 | A9F19232 |
| 40A | A9F17240 | A9F18240 | A9F19240 |
| 50A | A9F17250 | A9F18250 | A9F19250 |
| 63A | A9F17263 | A9F18263 | A9F19263 |
(3) 3P Three Pole
| Aktuell | B-curve(A9F173xx) | C-Kurve(A9F183xx) | D-Kurve(A9F193xx) |
| 6A~63A | A9F173xx | A9F183xx | A9F193xx |
| 32A | A9F17332 | A9F18332 | A9F19332 |
| 63A | A9F17363 | A9F18363 | A9F19363 |
(4) 4P Four Pole
| Aktuell | B-curve(A9F174xx) | C-Kurve(A9F184xx) | D-Kurve(A9F194xx) |
| 32A | A9F17432 | A9F18432 | A9F19432 |
| 63A | A9F17463 | A9F18463 | A9F19463 |
III. iC60N Full Model & Material Code List (B/C/D,1P/2P/3P/4P,1~63A)
Coding Reference
B-curve: A9F73xxx
C-Kurve: A9F74xxx (mainstream for export)
D-Kurve: A9F75xxx
(1) 1P
| Aktuell | B(A9F731xx) | C(A9F741xx) | D(A9F751xx) |
| 32A | A9F73132 | A9F74132 | A9F75132 |
| 63A | A9F73163 | A9F74163 | A9F75163 |
(2) 2P (match your 2P32A)
| Aktuell | B(A9F732xx) | C(A9F742xx) | D(A9F752xx) |
| 32A | A9F73232 | A9F74232 | A9F75232 |
| 63A | A9F73263 | A9F74263 | A9F75263 |
(3) 3P
| Aktuell | B(A9F733xx) | C(A9F743xx) | D(A9F753xx) |
| 32A | A9F73332 | A9F74332 | A9F75332 |
| 63A | A9F73363 | A9F74363 | A9F75363 |
(4) 4P
| Aktuell | B(A9F734xx) | C(A9F744xx) | D(A9F754xx) |
| 32A | A9F73432 | A9F74432 | A9F75432 |
| 63A | A9F73463 | A9F74463 | A9F75463 |
- Direct Replacement for your 2P32A
- Domestic China project requiring CCC: iC65N 2P C32A → A9F18232
- Export / foreign-invested project requiring CE: iC60N 2P C32A → A9F74232
- Matching RCD Add-on Blocks (DO NOT cross-series mix)
For iC65N: Vigi iC65 residual current add-on (A9V52xxx)
For iC60N: Vigi iC60 residual current add-on (A9V53xxx)