Reichweite: TeSys F (High-power imported contactor, eingestellt)
Model naming rule:
LC1F500 + Coil suffix
LC1F: TeSys F 3-Polschütz
500: Bemessungsbetriebsstrom 500 A under utilisation category AC-3 at 440 V
Suffix examples:
M7: Wechselstrom 220 V, 50/60 Hz (Most common model: LC1F500M7)
F7: Wechselstrom 380 V
ED: Gleichstrom 48 V
⚠️ Recommended replacement after discontinuation: LC1G500 (New-generation TeSys Giga)
- Main Electrical Parameters
Hauptstromkreis
Anzahl der Pole: 3P, 3NEIN (3 normalerweise offene Hauptkontakte)
Bemessungsisolationsspannung Ui: 1000 V
AC-3 (Motor load, 55°C): 500 A
AC-1 (Widerstandslast, 40°C): 700 A
Rated short-time withstand current Icw: 4200 A / 10 S
Controllable Motor Power (AC-3)
220 V: 147 kW
380/400 V: 250 kW
415 V: 280 kW
440 V: 295 kW
690 V: 335 kW
Spulenparameter (Take AC coil M7 as example)
Inrush power: 1100 VA
Hold-in power: 18 VA
Betriebsspannungsbereich: 0.85~1.1 × Uc
Closing time: 40~65 ms; Opening time: 100~170 ms
Lebensdauer & Maximum Operating Rate
Mechanische Haltbarkeit: 10 Millionen Zyklen
Maximale Betriebsfrequenz: 2400 Zyklen/Stunde
- Konstruktion & Montage
Hauptstromkreisanschluss: Bolt connection for busbars or cable lugs, Anzugsdrehmoment 35 N·m
Control terminal tightening torque: 1.2 N·m
Gesamtdimension (B × H × T): Ca. 233 × 238 × 232 mm
Montage: Base plate screw mounting
- Compatible Accessories
Thermisches Überlastrelais
Matching electronic thermal relay: LR9F7375 (132~220 A)
Notiz: Direct mounting between LC1F500 and LR9F7375 requires swapping Phase A and Phase C terminals of the thermal relay for alignment.
Hilfskontakte
LA1F, LA8F auxiliary contact modules (Keine eingebauten Hilfskontakte; need to be ordered separately).
Mechanische Verriegelung
LA7F406 (For forward/reversing circuit).
- Important Discontinuation Notice
LC1F500 series including LC1F500M7 / LC1F500Q7 are fully discontinued.
Stock spare parts are gradually depleted. Für neue Projekte, select the replacement directly:
✅ LC1G500KUEN (Wide voltage coil 100–250 V AC/DC)
✅ LC1G500LSEA (200–500 V AC/DC)
LC1G500 shares the same current rating, but dimension differs; cabinet layout needs hole dimension verification.
- Typische Anwendungen
3-phase fans, Wasserpumpen, Luftkompressoren, Brecher, variable frequency drive mains bypass and other LV motor circuits up to 250 kW.
Falls erforderlich, Ich kann dafür sorgen:
1) Complete dimension drawing of LC1F500;
2) Comparison checklist for LC1F500 ↔ LC1G500 replacement;
3) Full coil voltage model list.
Schneider LC1F500 (TeSys F Series)
✅ Mechanical durability: 10 Millionen Zyklen (10×10⁶ Zyklen)
Test condition: Bemessungssteuerspannung, no-load operation.
Supplementary reference parameters:
- Elektrische Haltbarkeit (AC-3, 400 V, 500 A): Ca. 150,000 Zyklen;
- Maximale Betriebsfrequenz: 2400 Zyklen/Stunde;
- Erinnerungen: Dieses Modell wird nicht mehr hergestellt; replacement model LC1G500.
Official Replacement Models for Schneider LC1F500 (TeSys F)
LC1F500 full series discontinued. Official upgrade series: TeSys Giga LC1G500 (3-Pole). It offers identical electrical rating: 500 A under AC-3 at 440 V.
- Primary Direct Replacement Models (Sorted by Coil Voltage)
| Original LC1F500 Model | Coil Specification | Recommended LC1G500 Replacement | Coil Range |
| LC1F500M7 | Wechselstrom 220 V | LC1G500KUEN | 100~250 V AC/DC (Most widely used in China) |
| LC1F500Q7 | Wechselstrom 380 V | LC1G500LSEA | 200~500 V AC/DC (Abdeckungen 380 V) |
| LC1F500F7 | Wechselstrom 110 V | LC1G500EHEA | 48~130 V AC/DC (Abdeckungen 110 V) |
| LC1F500ED | Gleichstrom 48 V | LC1G500BEEA | 24~48 V AC/DC |
Model description:
KUEN: Standardversion, 100~250 V (Top choice to replace M7)
LSEA: Advanced version, 200~500 V (To replace Q7)
EHEA: Advanced version, 48~130 V (To replace F7)
- Critical Notes During Replacement
- Mounting dimensions are not interchangeable
LC1G width is roughly 35% narrower than LC1F;
✅ To reuse existing mounting holes: Install adaptation base LA9GRFB2 (Suitable for LC1G265~500), no new drilling required.
- Accessories are incompatible; old LC1F accessories cannot be reused
Original: LA1F auxiliary contacts, LA7F mechanical interlock cannot be mounted on LC1G
New accessories for LC1G:
Hilfskontakte: LA9G series
Mechanische Verriegelung: LA9G970 (Horizontal forward/reversing)
- Matching thermal overload relay updated
Original matched LR9F7375; LC1G500 matches LR9G series electronic thermal relays.
- Leistungsvergleich
Mechanische Haltbarkeit: LC1F500 = 10 Millionen Zyklen; LC1G500 = 8 Millionen Zyklen
AC-3 rated current: Identisch 500 A @440 V
LC1G Advantages: Electronic wide-voltage coil, stronger voltage fluctuation resistance, contact wear diagnosis available.
- Alternative Solutions for Two Scenarios
- Emergency spare parts solution
For urgent on-site maintenance: Purchase original stocked LC1F500 from market (Price increased, supply tight, watch out for refurbished units). Not allowed for new projects.
- Cross-brand alternative (Non-Schneider OEM)
Siemens 3RT1075, ABB AF580; Only applicable for retrofit projects, not recommended for new cabinet design.
Simplified Selection Advice
For most domestic working conditions (Original coil AC220V LC1F500M7)
👉 Preferred option: LC1G500KUEN + LA9GRFB2 adaptation base (If original mounting holes need reservation)
Service Life Parameters of Schneider LC1G500 (TeSys Giga)
- Mechanische Haltbarkeit (Official Rating)
8 Millionen Zyklen (8×10⁶ Zyklen)
Tested under no-load condition with rated control voltage.
Compare with old LC1F500: Mechanische Haltbarkeit 10 Millionen Zyklen, etwas niedriger.
- Electrical Durability (AC-3, 400 V, 500 A Motor Load)
✅ Official standard reference value: 150,000 Zyklen (Same as LC1F500 datasheet value)
Wichtige Bemerkungen:
- Electrical durability is not a fixed value, affected by operating frequency, Anlaufstrom, Umgebungstemperatur, surge suppression and start-stop frequency;
- Under AC-3e (Heavy-duty frequent start-stop), electrical durability will be significantly lower than 150,000 Zyklen;
- Under AC-4 (Inching, reverse braking), electrical durability is only 20,000~30,000 cycles;
- Under AC-1 resistive load (Heizungen), electrical durability can reach more than 500,000 Zyklen.
- Extra Key Advantages (LC1G VS LC1F)
LC1G500 supports independent replacement of main contact assembly!
When contacts are burned out, only the contact module needs replacement instead of the whole contactor, greatly reducing long-term maintenance cost; LC1F500 does not support separate contact replacement. Once contacts are damaged, the whole unit must be replaced.
- Maximum Allowable Operating Frequency
AC-3: 600 Zyklen/Stunde
AC-3e: 600 Zyklen/Stunde
AC-1: 300 Zyklen/Stunde
AC-4: 150 Zyklen/Stunde
Service Life Comparison Table: LC1F500 ↔ LC1G500
| Parameter | LC1F500 (Auslaufmodell) | LC1G500 (Ersatzmodell) |
| Mechanische Haltbarkeit | 10 Millionen Zyklen | 8 Millionen Zyklen |
| Elektrische Haltbarkeit (AC-3) | Ca. 150,000 Zyklen | Ca. 150,000 Zyklen |
| Separable contact kit | ❌ Nicht unterstützt | ✅ Unterstützt |