Samwha EOCR from Korea, integrated into the Schneider EOCR product line, made in Korea, exclusively for EOCR motor protection relays.
- Modelldefinition
3CT: Three-phase integrated current transformer with three through-hole cores
H2: Größencode, corresponding to the cable window for 200A model
200: Primary rated current: 200 A
C: Old version suffix; Z is the new replacement model (3CT-H2-200-Z). Elektrische Parameter sind identisch, only version revision, direct plug-and-play replacement.
- Grundlegende elektrische Spezifikationen
Transformation ratio: 200/5 A
Genauigkeitsklasse: Klasse 3.0
Rated burden: 1.25 VA (Version C) / 5 VA (New Version Z)
Frequenz: 50/60 Hz
Spannung standhalten: 1150 V
Short-time thermal stability: 40Ith / 1 zweite
Isolationswiderstand: ≥10 MΩ @ 500 In DC
Anwendbarer Stromkreis: Wechselstrom 600 V motor circuit
Gewicht: ca. 580 G
- Gesamtabmessungen
W150 mm × H55 mm × D71 mm
Integral epoxy encapsulation, three circular cable holes; DIN-Schiene / Panelmontage
Secondary terminals: Q1, K2 (three independent windings for each phase); secondary wire: 1.5~4 mm² flexible cable
- Anwendung & Passend
✅ Designed exclusively for: EOCR-3DE, FDE, SSD, 3MZ and other digital motor protection relays. It samples three-phase current to implement overload, Phasenverlust, locked rotor and current unbalance protection.
✅ Application scenarios: Three-phase asynchronous motor control cabinets, Fans, Wasserpumpen, compressors and conveyor power circuits.
❌ Not suitable for energy metering (Klasse 3 accuracy for protection only, not for measurement).
- Modellauswahl & Ersatz
New in-stock replacement: 3CT-H2-200-Z, direct replacement for 3CT-H2-200-C
Other models in the same series:
3CT-H1-100-Z: 100/5 A
3CT-HH-150-Z: 150/5 A
3CT-H3-300-Z: 300/5 A
3CT-H4-400-Z: 400/5 A
- Installationsrichtlinien
- Run the main power cable directly through the three holes; P1 = supply side, P2 = motor side. Polarity reversal will cause phase error and false phase-loss tripping. CT secondary circuit must never be open-circuited.
- Use only identical 3CT models with one relay; do not mix CTs with different transformation ratios.
- Umgebungstemperatur: -20 ~ +60 ℃; Max altitude: 2000 M.
- Wiring Instruction for 3CT-H2-200-C (Neues Modell: 3CT-H2-200-Z)
Three-phase integrated CT with independent secondary windings for R/S/T phases, secondary output 5 A. Only compatible with EOCR motor protectors; cannot be connected to ordinary ammeters or metering devices.
Terminaldefinition
Primary side: Three holes for L1(R), L2(S), L3(T) Stromkabel
Polarity rule: P1 (Stromversorgung) → P2 (Motorlast); arrow points toward the load. Reversed polarity leads to phase fault and incorrect phase-loss alarm.
Secondary terminals (3 groups from top to bottom):
R phase: Q1, K2
S phase: Q1, K2
T phase: Q1, K2
Secondary cable: 1.5~4 mm² flexible wire; shielded twisted pair is recommended; cable length ≤ 15 M.
Standardverkabelung (EOCR-3DE / FDE / 3MZ / iFMZ / i3MZ)
- R-phase K1 → EOCR I1; R-phase K2 → common COM terminal
- S-phase K1 → EOCR I2; S-phase K2 → common COM terminal
- T-phase K1 → EOCR I3; T-phase K2 → common COM terminal
✅ All three K2 terminals are tied together to the protector’s current COM; single-point grounding at the COM terminal is recommended.
❌ Never allow secondary open circuit (will cause accuracy drift and insulation breakdown).
Note on mechanical life: Der Begriff “mechanisches Leben” only applies to devices with moving contacts and mechanical structures (Schütze, Leistungsschalter, Relais). Stromwandler (CT) and voltage transformers (PT) are static components without moving parts. Their service indicators are insulation life, thermal stability and environmental durability only.
Wartung & Austauschzyklus (On-site O&M Reference)
Normale Umgebung (Lüfter & Pumpe, clean indoor cabinet): Evaluate replacement after 8~12 years
Raue Umgebung (hohe Temperatur, Staub, VFD circuits, frequent direct-on-line motor starting): Check insulation and transformation ratio every 5~7 years
After short-circuit heavy current impact: Test or replace immediately. The iron core will suffer hidden performance degradation, resulting in current sampling deviation and false tripping of the protector.
Ergänzende Anmerkung
New model 3CT-H2-200-Z shares the same mechanical structure, iron core and encapsulation as version C, with identical durability. Only the rated burden is upgraded from 1.25 VA to 5 VA, making it more stable for long secondary cables and VFD applications. Mounting holes are fully interchangeable with no cabinet modification required.
- Naming Rule for 3CT-H Series Three-Phase Integrated CT
Format: 3CT-XX-XXX-Suffix
3CT: Dreiphasiger kombinierter Stromwandler (EOCR dedicated)
H1/HH/H2/H3/H4: Größencode (cable window dimension)
Numeral: Primary current (secondary output 5 A)
Suffix: C = Old version (eingestellt); Z = New version (active replacement)
Genauigkeit: Klasse 3.0; Secondary output: 5 A; Compatible with all EOCR motor protectors.
- Vollständige Modellliste (Old C-version + New Z-version, one-to-one match)
Full Specifications (ascending current rating)
- 3CT-HS-75, Verhältnis: 75/5 A
Alt: 3CT-HS-75-C (eingestellt)
Neu: 3CT-HS-75-Z (in der Produktion)
- 3CT-H1-100, Verhältnis: 100/5 A
Alt: 3CT-H1-100-C (eingestellt)
Neu: 3CT-H1-100-Z (in der Produktion)
- 3CT-HH-150, Verhältnis: 150/5 A
Alt: 3CT-HH-150-C (eingestellt)
Neu: 3CT-HH-150-Z (in der Produktion)
- 3CT-H2-200 (Ihr Modell), Verhältnis: 200/5 A
Alt: 3CT-H2-200-C (eingestellt)
Neu: 3CT-H2-200-Z (direct interchange)
- 3CT-H3-300, Verhältnis: 300/5 A
Alt: 3CT-H3-300-C (eingestellt)
Neu: 3CT-H3-300-Z (in der Produktion)
- 3CT-H4-400, Verhältnis: 400/5 A
Alt: 3CT-H4-400-C (eingestellt)
Neu: 3CT-H4-400-Z (in der Produktion)
- Key Differences between C-version & Z-version
Old suffix -C: Rated burden 1.25 VA, limited short secondary wiring length
New suffix -Z: Rated burden upgraded to 5 VA, better stability for long cables and VFD circuits; mounting footprint fully compatible for drop-in replacement without cabinet changes.
- EOCR Protector Matching Table (Aktueller Bereich)
75 A → 3CT-HS-75
100 A → 3CT-H1-100
150 A → 3CT-HH-150
200 A → 3CT-H2-200 (dieses Modell)
300 A → 3CT-H3-300
400 A → 3CT-H4-400
- Ergänzend: Zero-Sequence Split-Core CT in the Same Series
ZCT-035-Z, ZCT-050-Z, ZCT-080-Z, used for earth-fault protection and paired with 3CT series.