SIRIUS 3RT series 3-Pol-Wechselstrom-Leistungsschütz, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts
- Modelldekodierung
3RT1056-6AP36
3RT: SIRIUS power contactor series
10: Standardschütz (non-safety, nicht umkehrender Typ)
56: Frame size S6, AC-3 400V 185A
6: Coil voltage 220…240V AC/DC
A: Hauptstromschienenanschluss
P: Screw terminals for auxiliary contacts
36: Hilfskontakte 2 Normalerweise geöffnet + 2 Normalerweise geschlossen (2NO+2NC)
- Grundlegende elektrische Spezifikationen
| Artikel | Parameter |
| Anzahl der Hauptpole | 3 Stangen (3NEIN) |
| AC-3 (Motor load @400V) | 185A, 90kW |
| AC-1 (Resistive load @40℃) | 215A |
| Bemessungsbetriebsspannung Ue | Max. 1000V und |
| Coil control voltage Uc | 220~240V AC/DC (Wide-range AC/DC coil) |
| Hilfskontakte | 2NEIN + 2NC, Schraubklemmen |
| Hauptstromkreisanschluss | Sammelschiene |
| Rahmengröße | S6 |
| Schutzgrad | Front IP00; IP20 with cover installed |
| Impulse withstand voltage | 8kV main circuit / 6kV auxiliary circuit |
| Umgebungstemperatur | -25℃ ~ +60℃ (Ab 40℃ ist eine Leistungsreduzierung erforderlich) |
- Anwendungsbereich
On/off control of 3-phase motors such as fans, Wasserpumpen und Kompressoren
Control cabinets, zentrale Klimaanlage, industrial production lines and power cabinets
Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression
- Alternative Modelle
- Inländisch SIEMENS Ersatz: 3RT5056-6AP36
Identische Funktion, current rating and coil specification. In China hergestellt, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model
- Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
- Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)
Notiz: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.
- Installation & Wartungsrichtlinien
- Installation: Vertikale Montage, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
- Hauptstromkreis: Sammelschienenanschluss, tighten to specified torque per datasheet to prevent overheating and contact burning.
- Spule: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
- Contact life: Under AC-3 motor duty, mechanical life approx. 10 Millionen Operationen; electrical life depends on breaking current.
- Fehlerbehebung
Coil energized but no pull-in: Spulenspannung messen, check coil open circuit or mechanical jamming
Pull-in but no continuity on main circuit: Loose busbar or burned main contacts
Geschwätz / ungewöhnliches Geräusch: Niedrige Spulenspannung, accumulated dust on iron core, Frühlingsmüdigkeit
- Zoll-HS-Code
85364900 (Elektromagnetischer Schütz)
- Optional Spare Parts & Zubehör
Thermisches Überlastrelais: 3RU2156 series (for 90kW motor)
Surge suppressor: 3RT1955-1CD00 (RC-Schaltung), 3RT1955-1DG00 (Varistor)
Auxiliary contact block: 3RH1951 (for extra auxiliary contacts)
Arc shield & Hauptkontakt-Reparatursatz: 3RT1956 contact assembly
Vergleichstabelle: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36
Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.
| Vergleichsartikel | 3RT1056-6AP36 (Imported Version) | 3RT5056-6AP36 (Inländische Version) |
| Product Line | SIRIUS 3RT1, global standard imported version | SIRIUS 3RT5, local domestic version |
| Herkunft | Amberg Factory, Deutschland | SIEMENS low voltage plant in China (SEAL) |
| AC-3 @400V | 185A / 90kW | 185A / 90kW |
| AC-1 Widerstandslast | 215A | 215A |
| Coil Specification | 220~240V AC/DC | 220~240V AC/DC |
| Hilfskontakte | 2NO+2NC, Schraubklemmen | 2NO+2NC, Schraubklemmen |
| Hauptstromkreisanschluss | Sammelschiene | Sammelschiene |
| Rahmengröße | S6 | S6 |
| Gesamtdimension / Befestigungslöcher | Identisch, direkt austauschbar | Identisch, direkt austauschbar |
| Mechanisches Leben | 10 Millionen Operationen | 10 Millionen Operationen |
| AC-3 Elektrische Lebensdauer | Dasselbe (depends on breaking current) | Dasselbe (depends on breaking current) |
| Ambient Temperature Range | -25℃ ~ +60℃ | -25℃ ~ +60℃ |
| Compatible Accessories | Full compatibility: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, Hilfskontaktblock | 100% compatible with accessories of 3RT1056 |
| Zertifizierungen | CCC, CE, UL, CSA, suitable for overseas projects | CCC, CE; UL optional for certain batches, standard for domestic projects |
| Typenschild | Deutsch + English marking, Hergestellt in Deutschland | chinesisch + English marking, made in China |
| Lieferzeit | Lang, mostly forward order with unstable lead time | Kurz, domestic stock available with fast delivery |
| Preis | Höher | Lower with cost advantage |
| Anwendungsszenarien | Ausrüstung exportieren, overseas projects, high-end foreign-invested projects, cases requiring imported components | Domestic control cabinets, Wasserpumpen & Fans, HVAC, general industrial automation |
| Elektrische Leistung | Identisch, no derating difference | Identisch, no derating difference |
| HS-Code | 85364900 | 85364900 |
| Model Naming Definition | 3RT10: Global original series | 3RT50: Domestic localized series |
Wichtige Anmerkungen
- Austauschbarkeit: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, Sammelschiene, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
- Auswahlhilfe
✅ Choose 3RT5056: Domestic projects, budget control, schnelle Lieferung; preferred for most domestic panel building projects.
✅ Choose 3RT1056: Export machinery, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.
- Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.
Ergänzend: Shared Spare Parts List
Thermisches Überlastrelais: 3RU2156 series
Surge suppressor: 3RT1955-1CD00 / 3RT1955-1DG00
Main contact repair kit: 3RT1956
Additional auxiliary contact block: 3RH1951
Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36
Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185A). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.
- Common Applications (Both Models Applicable)
(1) Direct-on-line Motor Starting (Main AC-3 Duty)
Wasserpumpen, Abwasserpumpen, Umwälzpumpen (Wasseraufbereitung, HVAC, Gebäude, chemische Industrie)
Luftkompressoren, große Fans, Rauchabzugsventilatoren
Förderer, Mischer, Extruder, Brecher (Essen, building material, Bergbau)
Chillers and large refrigeration compressors for central air conditioning
MCC motor control centre drawer units for 90kW motor circuits
(2) AC-1 Widerstandslast
High-power heating elements, resistance furnaces
Main circuit switching of high-power circuits inside distribution cabinets
(3) AC-6B Capacitor Switching
Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)
Passend: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.
- Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
- Domestic panel projects, domestic factories, HVAC, Wasserversorgung & Drainage, general factory automation
Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.
- Domestic municipal projects: Wastewater treatment plants, municipal pump stations, building HVAC cabinets
- Domestic machinery OEM: Fans, Luftkompressoren, chiller units sold in domestic market
- Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
- Retrofit replacement for old contactors, tight budget and fast delivery required
✅ Suitable for: Domestic projects without mandatory UL/CSA certification or German origin requirement
- Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
- Export machinery & Ausrüstung (export to Southeast Asia, Naher Osten, Europe and other overseas sites)
Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.
- New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
- Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
- High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
- Ersatzteilaustausch für Altgeräte: Original unit fitted with 3RT1056 and client requires identical OEM spare parts
✅ Suitable for: Export machinery, overseas projects, client specified imported components, mandatory UL/CSA certification
- Vermeidung von Auswahlfallen
- Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
- For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
- For export to Europe / Nordamerika, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
- Heavy vibration & dusty heavy industry environments (Bergbau, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
- Nicht anwendbare Szenarien
Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.
Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)
Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter


















NH42-63-318x560.png)