Schneider Electric SPKVPI62611 - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider Electric SPKVPI62611 - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Schneider Electric SPKVPI62611

VPIS-SPKVP62611 (correct model: SPKVPI62611) is the core component of the Voltage Presence Indicator for Schneider Electric Easergy VPIS V3 series medium-voltage switchgear — the Voltage Presence Indicator module (VPI module).

1 Model Code Explanation

VPIS: Voltage Presence Indicator System

SPK: Schneider Electric internal order prefix (Speaker/Module, referring to a modular component)

VPI: Voltage Presence Indicator (core voltage indication module)

62611: Product specification code → 3.5 μA sensing current threshold

2 Schlüsselparameter & Funktionen

Produktserie: Easergy VPIS V3 (Voltage Output, VO)

Sensing current: 3.5 μA

Funktionen:

Three-phase voltage presence indication (LED indication)

Entspricht IEC 62271-206

Equipped with VO (Voltage Output) Funktion

Can be used with VD23 relays or T300 SC150 modules

Built-in surge protection

Applicable equipment: Schneider Electric SM6/RM6 series medium-voltage switchgear

3 Complete Model List of the Same Series (VPI626xx)

ModellSensing current threshold
VPI626113.5 μA
VPI626125.1 μA
VPI626137.4 μA
VPI6261410.7 μA
VPI6261515.5 μA
VPI6261622.4 μA
VPI6261732.5 μA
VPI6261847.2 μA

4 Official Order Code

Full order code: SPKVPI62611

Applicable enclosures: SM6, RM6, Prevecta, GM325, usw.

5 Ersatzmodelle

VPIS V2 replacement: VPI624xx series with the same current threshold (z.B. VPI62411 corresponds to 3.5 μA)

VPIS V3 replacement: Other current threshold models in the same series (must match enclosure design)

6 Betriebsumgebung

Standard: IEC 62271-206

Voltage indication threshold: Indicator lights steady/flashing above 45% of rated voltage

Schutz: Built-in lightning/surge protection

Installation: Mounted on the panel of medium-voltage switchgear, maintainable and replaceable