Model Positioning & Diferencias fundamentales
BMXDRA1605H: 16-channel relay output module of the Modicon X80 series, Harsh Environment / Hardened type. el sufijo “h” stands for Hardened, designed specifically for extreme industrial environments.
BMXDRA1605: 16-channel relay output module of the Modicon X80 series, Tipo estándar, suitable for normal industrial environments.
- Comparación detallada de parámetros técnicos
| Artículo | BMXDRA1605H (Harsh Environment) | BMXDRA1605 (Estándar) | Notas |
| Temperatura de funcionamiento | -25°C ~ +70°C | 0°C ~ +60°C | H version has wider temperature range for extreme cold & heat |
| Environmental Resistance | 3C4 (corrosive gas), 3S4 (dust/sand), 3B2 (fungi), salt spray class 2 | Standard protection | H version passes stricter environmental tests for chemical, marine, desert applications |
| Output Configuration | 16 relay outputs (8 groups of DPDT, 2 channels share a common terminal) | Same | Identical output circuit structure |
| Corriente nominal | 3A (Ith conventional free-air thermal current) | 2A (Ith) | H version has higher rated current & load capacity |
| Rango de voltaje | 24En DC (19~30V) / 24~240V AC (19~264V) | Same | Same AC/DC load voltage support |
| Tiempo de respuesta | ≤8ms (on) / ≤10ms (off) | Same | Same relay operating speed |
| Electrical Durability | AC-15: 100,000 operaciones (2A@250V AC) | Same | Same contact service life |
| DC-13: 100,000 operaciones (0.6A@30V DC) | |||
| Rigidez dieléctrica | 2000V AC/1 min (50/60Hz) | Same | Same electrical isolation performance |
| Grado de protección | IP20 | Same | Same module enclosure protection |
| Montaje | Carril DIN estándar de 35 mm, occupies 1 slot | Same | Compatible with same Modicon X80 rack system |
| Terminal Block | 20-point removable terminal block (BMXFTB2000 series) | Same | Uses same terminal accessories |
| Certificaciones | Including marine, ATEX, IEC-Ex and other special environment certifications | Standard industrial certifications | H version suitable for hazardous areas & special industries |
- Application Differences
| BMXDRA1605H Applications | BMXDRA1605 Applications |
| 1. Outdoor control panels or unconditioned field equipment | 1. Control cabinets in standard industrial buildings |
| 2. Low-temperature environments (-25°C): cold storage, polar equipment, high-altitude areas | 2. Indoor automation systems with controlled temperature |
| 3. High-temperature environments (+60~+70°C): metallurgy, glass, cement and other high‑heat industries | 3. Manufacturing in normal temperature range (0~60°C) |
| 4. Corrosive environments: chemical, electroplating, offshore platforms, coastal areas | 4. Automated production lines in ordinary environments |
| 5. Dust/sand environments: minería, building materials, desert‑area equipment | 5. Clean rooms, food & beverage, pharmaceutical industries |
| 6. Marine engineering requiring salt spray protection | 6. General commercial & civil building automation |
- Recomendaciones de selección
- Environment First Principle: BMXDRA1605H must be selected if operating temperature exceeds 0~60°C, or there is risk of corrosive gas, heavy dust, or mold growth.
- Load Capacity: For loads up to 3A, the H version provides higher current margin and more reliable long‑term operation.
- Cost Balance: The standard version (BMXDRA1605) is lower‑cost and offers sufficient performance in normal environments with better cost‑effectiveness.
- Compatibilidad: Both modules are fully compatible with Modicon M340/M580 PLC systems and X80 racks. They can be directly interchanged without program modification.
Complete Model List of Modicon X80 Series BMXDRA/BMXDRC Relay Output Modules
BMXDRA1605H and BMXDRA1605 belong to the discrete relay output module portfolio of Schneider Electric Modicon X80 series. The series offers multiple configurations to meet various industrial requirements. Below is the full model list and key parameter comparison:
- Core Model Classification & Resumen
| Modelo | Canales | Tipo de contacto | Environment | Características clave |
| BMXDRA0805 | 8 | NO (Normalmente abierto) | Estándar | Basic 8-channel relay output |
| BMXDRA0805H | 8 | NO | Harsh Environment | Hardened, operating temp -25°C~+70°C |
| BMXDRA0804T | 8 | NO | All‑Climate | Wide temp, dedicated for 100~150V DC |
| BMXDRA0815 | 8 | NO | Estándar | High isolation, 24~125V DC/24~240V AC |
| BMXDRA1605 | 16 | NO | Estándar | Basic 16-channel relay output |
| BMXDRA1605H | 16 | NO | Harsh Environment | Hardened, operating temp -25°C~+70°C |
| BMXDRC0805 | 8 | NA/NC | Estándar | 8-channel dual‑contact relay output |
- Comparación detallada de parámetros técnicos
| Artículo | BMXDRA0805 | BMXDRA0805H | BMXDRA0804T | BMXDRA0815 | BMXDRA1605 | BMXDRA1605H | BMXDRC0805 |
| Canales | 8 | 8 | 8 | 8 | 16 | 16 | 8 |
| Configuración de contacto | 8×NO (4 groups, 2 channels share common) | 8×NO (4 groups, 2 channels share common) | 8×NO (4 groups, 2 channels share common) | 8×NO (individually isolated) | 16×NO (8 groups, 2 channels share common) | 16×NO (8 groups, 2 channels share common) | 8×NO/NC (DPDT) |
| Operating Temp | 0°C~+60°C | -25°C~+70°C | 0°C~+60°C (TC treated) | 0°C~+60°C | 0°C~+60°C | -25°C~+70°C | 0°C~+60°C |
| Protección ambiental | Estándar | 3C4/3S4/3B2/salt spray class 2 | All‑climate treated | Estándar | Estándar | 3C4/3S4/3B2/salt spray class 2 | Estándar |
| Corriente nominal | 2A | 3A | 2A | 2A | 2A | 3A | 2A |
| Rango de voltaje | 24V DC/24~240V AC | 24V DC/24~240V AC | 100~150V DC only | 24~125V DC/24~240V AC | 24V DC/24~240V AC | 24V DC/24~240V AC | 5~150V DC/24~240V AC |
| Tiempo de respuesta | ≤8ms(on)/≤10ms(off) | Same | Same | Same | Same | Same | Same |
| Vida eléctrica | 100k operations | Same | Same | Same | Same | Same | Same |
| Rigidez dieléctrica | 2000V AC/1 min | Same | Same | Same | Same | Same | Same |
| Montaje | 35carril DIN mm | Same | Same | Same | Same | Same | Same |
| Terminal Block | 20-point removable | Same | Same | Same | Same | Same | Same |
| Compatible Systems | M340/M580 PLC | Same | Same | Same | Same | Same | Same |
- Características clave & Applications by Model
3.1 BMXDRA0805 Series (8‑channel Standard)
BMXDRA0805: Basic 8‑channel NO relay output for normal industrial environments (0°C~+60°C), p.ej., válvulas solenoides, contactors on production lines.
BMXDRA0805H: Harsh environment hardened version, same functions as BMXDRA0805, stable at -25°C~+70°C, tested against corrosion, dust, fungi, salt spray; ideal for chemical, marine, metallurgy.
3.2 Special‑Purpose 8‑Channel Models
BMXDRA0804T: All‑climate (TC) módulo, dedicated for 100~150V DC systems, for industrial equipment with special power supplies.
BMXDRA0815: High‑isolation 8‑channel NO relay output with wider DC voltage range (24~125V DC), better isolation for precision equipment control.
BMXDRC0805: Only model with NO/NC (DPDT) contactos, one channel with both NO and NC; suitable for complex switching control circuits.
3.3 BMXDRA1605 Series (16‑channel Standard)
BMXDRA1605: Basic 16‑channel NO relay output, 8 groups with shared common terminals, for medium‑to‑large automation systems such as assembly lines and HVAC.
BMXDRA1605H: Harsh environment hardened version, same functions as BMXDRA1605, -25°C~+70°C wide temp, 3Una corriente nominal (higher than standard), stronger load capacity for outdoor/unconditioned panels.
- Model Naming Convention
| Part | Significado |
| BMX | Modicon X80 series identifier |
| DRA/DRC | Discrete relay output module (DRA = single contact, DRC = double contact) |
| 8月16日 | Number of channels (08 = 8 canales, 16 = 16 canales) |
| 05/04T/15 | Function code (05 = standard, 04T = 100~150V DC dedicated, 15 = high isolation) |
| h | Suffix for Hardened / Harsh Environment version |
- Selection Advice
- Channel Count: Choose 8 channels for small systems, 16 channels for medium systems; mixed use improves flexibility.
- Adaptabilidad ambiental: H‑type hardened modules must be used if temperature exceeds 0°C~+60°C or special environmental stresses exist.
- Tipo de contacto: Choose DRA series (NO) for simple on/off control; choose DRC series (NA/NC) for switching control.
- Load Characteristics:
Normal loads (≤2A): all models suitable
Heavy loads (2~3A): prefer H‑type (3Una corriente nominal)
Special voltage systems: select dedicated models with matching voltage range (p.ej., BMXDRA0804T for 100~150V DC)
All models are fully compatible with Modicon M340/M580 PLC systems and X80 racks. Direct interchange is supported without program changes, facilitating system upgrade and maintenance.