Nro. de orden: 1SFL491001R8011|Status: Legacy A series discontinued, direct replacement AX185-30-11-80 (1SFL491074R8011)
Aplicaciones típicas: 3-phase motor starting, bypass circuits, distribución de energía, HVAC water pumps, fans, compresores de aire, conmutación de condensadores (AC-1). Compliant with IEC/GB14048.4
✅ Desglose del modelo
A185: Tamaño del marco, rated 185A at AC-3, 415V
30: 3 normally open main contacts, no main normally closed contacts
11: Built-in auxiliary contacts 1NO+1NC
80: Coil code → AC220-230V 50Hz / AC230-240V 60Hz
📌 Core Electrical Specifications
polacos: 3PAG
Tensión máxima del circuito principal: 690V
Corriente térmica convencional Ith (40℃ aire libre): 275A
AC-3 (motor duty, 55℃): 400/415V → 185A
AC-1 (carga resistiva, 55℃): 690V → 250A
Coil holding power: 35VA @50Hz; Energía de irrupción: 550VA @50Hz
Rango de voltaje de funcionamiento: 0.85~1.1×Uc
Vida mecánica: 5 millones de operaciones; Electrical life AC-3: aprox. 1 millones de operaciones
Frecuencia máxima de funcionamiento: 300 cycles/hour for AC-3; 3600 cycles/hour mechanical
🔌 Wiring Specifications (Main Circuit Copper Cable)
Single solid conductor: up to 120mm²
Cableado de contactos auxiliares: 0.75~2,5 mm² (with crimp terminals)
🧩 Accesorios compatibles (Interchangeable with AX185)
Relé de sobrecarga térmica: TA200DU (for 185A range)
Bloques de contactos auxiliares: CAL18 (side mount), CA5 (front mount)
Supresores de sobretensiones: amortiguador RC, varistor
Enclavamiento mecánico, busbar connectors, cubiertas de terminales
🔁 Información de reemplazo (Notas clave)
Discontinued legacy model: A185-30-11-80
Fully compatible replacement: AX185-30-11-80, dimensiones de montaje idénticas, cutout and wiring, upgraded performance and readily available stock
Coil code cross reference: 81=24V, 83=48V, 84=110V, 85=380V, 80=220/230V
📎 HS Code
código SA: 85364900 (electromagnetic contactor, >32A)
⚠️ Selección & Consejos de mantenimiento
- For heavy-duty motors, reversing or frequent start-stop applications, select next higher frame size or AF series (AC/DC wide-voltage coil);
- Derating is required for ambient temperature>55℃ or installation inside enclosed cabinets;
- Verify coil voltage code during replacement; código 80 is the most common AC220V coil for China market;
- Prioritize AX new model for spare parts procurement, genuine brand-new A series stock is nearly unavailable.
TEJIDO A185-30-11-80 Contactor Application Cases (AC-3 400V, suitable for 75kW 3-phase motor, Bobina de 220V CA, built-in 1NO+1NC auxiliary)
Observación: A series is discontinued. AX185-30-11-80 shall be adopted for new projects. Mounting and wiring logic are identical for all cases below.
Caso 1: Heating Station Circulating Water Pump (DOL Direct-On-Line Starting)
Carga: 75kW hot water circulating pump, 380V, for industrial/municipal heat exchange stations, primary chilled water pumps of large commercial HVAC systems
Configuración: A185-30-11-80 + TA200DU thermal relay (setting range 140~200A) + moulded case circuit breaker for protection
Lógica de control: SOCIEDAD ANÓNIMA / local pushbutton start-stop; built-in 1NO for run feedback, 1NC para enclavamiento
Características: Continuous stable operation; AC-1 resistive rating 250A ideal for steady pump loads; auxiliary contacts send status signals to BMS building management system
nota de riesgo: Derating and cabinet cooling fan required in summer for enclosed cabinets; avoid frequent cycling
Caso 2: Variable Frequency Multi-Pump Cabinet, Mains Bypass Contactor
Carga: 75kW main water supply pump for constant-pressure water supply, VFD + mains dual circuit
Esquema: Contactor at VFD output + A185 mains bypass contactor, mechanical interlock accessory fitted between two contactors
Lógica: Pump runs via VFD under normal condition; upon VFD fault, PLC opens VFD circuit and closes A185 bypass to run motor directly on mains for uninterrupted water supply
Requisito crítico: Eléctrico + mechanical interlock mandatory to prevent catastrophic parallel connection of VFD output and mains; 1NO/1NC for bypass status feedback and interlock signals
Industrias: Water treatment plants, sewage plants, high-rise secondary water supply, park water supply
Caso 3: Soft Starter Bypass for Screw Air Compressor Main Motor (emparejado con ABB PSTX soft starter)
Carga: 75kW screw air compressor main motor
Esquema: ABB PSTX soft starter + A185-30-11-80 bypass contactor
Proceso: After soft start completes and current drops, PLC energizes A185 to short-circuit the soft starter; motor runs continuously via bypass contactor to reduce heat loss on soft starter thyristors
Ventaja: Air compressor is heavy inductive load; bypass configuration greatly extends soft starter service life. 5 million mechanical cycles suit compressor stations with multiple daily starts
Accesorios: CAL18 side-mounted auxiliary contact expansion, RC surge suppressor to absorb coil back EMF
Caso 4: Dust Removal Fan / Induced Draft Fan Control (Caldera & Dust Treatment)
Carga: 75kW centrifugal induced draft fan, main baghouse dust fan, for cement plants, chemical plants, waste incineration facilities
Control: DCS remote start-stop, interlocked with differential pressure, temperature and vibration signals; A185 switches main circuit, thermal relay for overload protection
Operating characteristics: High inertia, long start duration; not suitable for frequent jogging; usually DOL start or soft start + bypass
Nota de selección: AF wide-voltage AC/DC series is preferred if frequent forward/reverse operation is required
Caso 5: Main Contactor for Star-Delta Reduced-Voltage Starting (KM Main)
Carga: 75kW high-power motor, star-delta starter cabinet
Cabinet combination: 1 A185 as main contactor KM1 + 2 smaller contactors for star and delta switching
Suitable for sites with limited grid capacity and strict inrush current limits; auxiliary contacts send start-phase and completion feedback to PLC
Precaución: Transient impulse current occurs during star-delta transition, accelerating contact wear compared with standard DOL; regular inspection of contact erosion required
Caso 6: Capacitor Bank Switching in Low-Voltage Reactive Power Compensation Cabinet (Carga resistiva AC-1)
Carga: Low-voltage power factor correction capacitor bank, total 3-phase capacitor current ≤250A (A185 AC-1 rating 250A)
Observación: Capacitor switching belongs to AC-1 resistive duty with high switching inrush current; standard A185 is only suitable for slow, infrequent switching. ABB dedicated UA capacitor contactors are recommended for high-frequency switching
Solicitud: Factory power rooms, commercial power distribution boards, low switching frequency (≤10 times per day)
Caso 7: Heavy-Duty Belt Conveyor Drive (Minería / Sand & Aggregate / Materiales de construcción)
Carga: 75kW main drive motor for sand transport, mining feed conveyor
Condiciones de funcionamiento: Heavy start torque, risk of stall; A185 + TA200DU thermal relay + stall interlock
Limitación: A series has poor AC-4 performance for frequent reversing and jogging; AF series upgrade is recommended
✅ General Selection & Site Reminders
- Coil code 80 = AC220V, most widely used in domestic control cabinets; AF wide-voltage coil is recommended for sites with large voltage fluctuation
- Built-in 1NO+1NC satisfies standard feedback; add CAL18 side auxiliary blocks if more signal points are needed
- Nota de reemplazo: A series discontinued; AX185-30-11-80 is direct replacement with identical cutout, wiring and accessories
- Protection matching: MCCB for short-circuit protection + TA200DU thermal relay for overload protection
Operating Principle of ABB A185-30-11-80 AC Contactor
This is an electromagnetic AC contactor. Its core function is using electromagnetic force to drive mechanical linkage to switch main and auxiliary contacts. Coil code 80 means AC220V coil, contactos auxiliares 1NO+1NC incorporados, 3-pole main contacts for 3-phase motors, zapatillas, fans and other loads.
Observación: A series discontinued; AX185 shares identical working principle.
- Componentes internos principales
- Electromagnetic coil (excitation coil): Control circuit component, energized by AC220V to generate alternating magnetic field
- Núcleo fijo, moving core (armadura): Magnetic circuit. Fixed core is stationary; moving core couples with contact carrier. A shading ring is embedded on the end face of fixed core, exclusivo de los contactores de CA.
- Contactos principales (3 pairs of normally open main contacts): Carry high current to switch 380V main loads (motores, pumps etc.)
- Contactos auxiliares (incorporado 1NO+1NC): Low-current signal contacts for latching, entrelazar, run feedback, PLC/DCS signalling
- resorte de retorno: Pushes moving core back and opens contacts when coil is de-energized
- Arc chute: Elongates and cools electric arc during contact separation, extinguishes arc to prevent contact melting and phase-to-phase short circuit
- Complete Working Sequence
2.1 Bobina energizada (pull-in stage)
AC220V rated voltage applied to control coil → alternating magnetic field generated, fixed core magnetized and electromagnetic attraction produced.
Attraction overcomes the force of return spring and contact pressure springs, pulling moving core down to close.
Linked mechanism operates synchronously:
3 pairs of main NO contacts close, 3-phase main circuit energized, motor/load starts running
Los contactos auxiliares conmutan simultáneamente: NO cierra, Se abre NC
The 1NO can be used for self-latching or sending run status to PLC; the 1NC is used for interlock and fault feedback.
✅ Shading ring function: AC magnetic field crosses zero every half cycle, causing temporary loss of attraction. Eddy current induced in shading ring creates a lagging magnetic field to maintain suction and eliminate hum and chatter of the core.
2.2 Coil continuously energized (holding stage)
Core stays closed, main circuit remains conductive.
Coil consumes low holding power (much lower than pull-in inrush power). Contact springs maintain adequate contact pressure to reduce contact resistance and avoid overheating under high current.
2.3 Bobina desenergizada (liberar & breaking stage)
Control circuit de-energized → magnetic field disappears, electromagnetic attraction vanishes.
Return spring rebounds and resets moving core:
3 contactos principales abiertos, main power supply disconnected
Restablecimiento de contactos auxiliares: NO abre, NC cierra
Arc forms at contact separation, cut and cooled by arc chute for arc extinction. Switching cycle completed.
- Auxiliary Contact Logic (Punto clave)
A185-30-11-80 built-in 1NO+1NC:
Bobina desenergizada: NO abierto, NC cerrado
Bobina energizada: NO cerrado, NC abierto
They operate synchronously via mechanical linkage and are not independently controlled.
- Key Performance & Notas de aplicación
- It is a control switch: It does NOT provide short-circuit protection. It only performs remote electric switching. Upstream circuit breaker for short-circuit protection and thermal relay for overload protection are mandatory.
- AC-3 (motor duty) characteristic: Make motor starting inrush current, break rated running current. Not suitable for frequent breaking of locked-rotor current (Servicio AC-4). Frequent reversing and jogging accelerate contact wear.
- Arc quenching principle: Grid-type arc chute splits long arc into multiple short arcs, cooled by air for rapid extinction, suitable for inductive loads up to 690V.
- Operating voltage window: 0.85~1.1×Uc. Low voltage causes insufficient suction, contact chatter and arcing damage.
- Simple Control Example (Self-Latching Circuit)
Press start button → coil energized, el contactor se activa, built-in NO auxiliary contact closes and parallels across start button. When start button is released, coil remains energized via this NO contact (self-latching). Press stop button, coil de-energized and contactor drops out.
- Conceptos erróneos comunes
AC contactor cannot provide electrical isolation for maintenance. Upstream circuit breaker must be opened for service work.
Shading rings are only fitted on AC magnetic cores; DC contactors do not have shading rings.
Main contacts and auxiliary contacts are mechanically linked but electrically isolated. High main circuit current will not leak into low-voltage control signal circuits.
Regla de codificación del modelo (A185-30-11-80)
AXX-30-XX-XX
- AXX: Clasificación actual del marco (A9~A300)
- 30: 3 contactos principales normalmente abiertos (3NO+0NC, standard for 3-phase motors)
- Auxiliary contact definition:
00: Sin contactos auxiliares incorporados
11: 1NO+1NC (standard for this model)
22: 2NO+2NC
- Coil code (últimos dos dígitos)
| Código | Voltaje de la bobina |
| 81 | CA 24V |
| 83 | CA48V |
| 84 | CA 110 V. |
| 80 | CA 220 V. (ampliamente utilizado en China) |
| 85 | CA380V |
Observación: A series discontinued; AX series with identical suffix is direct replacement with same mounting cutout and wiring.
Full 3-Pole Model List (30 main contact version, circuitos de motor)
Low current range (A9~A75)
A9, A12, A16, A26, A30, A45, A50, A75
Standard suffix: -30-10 / -30-11
Typical full part numbers:
A9-30-10-80, A26-30-11-80, A75-30-11-80
Medio & high power range (A95~A300, including A185)
Main models for pumps, fans, air compressors and star-delta starters:
A95, A110, A145, A185, A210, A260, A300
Auxiliary options for each frame (3-polo 30 versión)
- No built-in auxiliary: -30-00
- Incorporado 1NO+1NC (más común, same as A185-30-11): -30-11
- Built-in 2NO+2NC: -30-22
Full coil variants for A185 frame
A185-30-11-80 (CA 220 V., your reference model)
A185-30-11-84 (CA 110 V.)
A185-30-11-81 (CA 24V)
A185-30-11-85 (CA380V)
A185-30-00-80 (no built-in auxiliary)
A185-30-22-80 (2NA+2NC auxiliar)
Full frame list A95~A300 (3-polo 30)
- A95-30-00 / 11 / 22
- A110-30-00 / 11 / 22
- A145-30-00 / 11 / 22
- A185-30-00 / 11 / 22 (tu modelo)
- A210-30-00 / 11 / 22
- A260-30-00 / 11 / 22
- A300-30-00 / 11 / 22
Add coil code suffix 80/84/81/85 to each model above.
OEM versions (sufijo D, AxxD)
A95D, A115D, A150D, A185D, A205D, A260D, A300D, A370D
Same electrical performance as standard A series, different supply channel only.
4-pole models (40 main contact, for capacitor & cargas de iluminación)
A9-40-00, A16-40-00, A26-40-00, A45-40-00, A50-40-00, A75-40-00
AX Replacement Cross Reference (for new projects)
A95→AX95;A110→AX110;A145→AX145;A185→AX185;A210→AX210;A260→AX260;A300→AX300
Suffix coding remains unchanged: AX185-30-11-80 directly replaces A185-30-11-80.
Matching Thermal Relay List (TA200DU for A185)
A95/A110 → TA110DU
A145/A185 → TA200DU
A210/A260 → TA300DU
A300 → TA450DU