Adaptador Allen-Bradley 1747-AENTR

Posicionamiento: SLC500 rack EtherNet/IP remote I/O adapter (NOT an SLC processor). It converts the existing 1746 SLC I/O rack into an EtherNet/IP slave, which is scanned and controlled by Logix controllers (CompactLogix, ControlLogix). It is the most commonly used gateway module for phased upgrades of legacy SLC systems. ✅ Basic Specifications Series: A/B series; El último ...

  • Detalles del producto

Posicionamiento: SLC500 rack EtherNet/IP remote I/O adapter (NOT an SLC processor). It converts the existing 1746 SLC I/O rack into an EtherNet/IP slave, which is scanned and controlled by Logix controladores (CompactLogix, ControlLogix). It is the most commonly used gateway module for phased upgrades of legacy SLC systems.

✅ Especificaciones Básicas

Serie: A/B series; Latest firmware V2.003

Puerto: 1 ×RJ45, 10/100 Mbps auto-negotiation, Ethernet/IP (PIC)

Mandatory mounting requirement: Must be installed in Slot 0 of the SLC chassis, replacing the original SLC processor position

Plano posterior: 1746 SLC backplane with SLC backplane master function

Connection resources: máx.. 96 Clase 1 (real-time I/O) conexiones, máximo. 8 Clase 3 (explicit message) conexiones

Network topology: Soporta estrella, lineal, DLR (Device Level Ring)

configuración IP: interruptor DIP / BOOTP / DHCP; DIP switch set to `888` = factory reset

Fuente de alimentación: Powered by the SLC chassis power supply, consumo de energía aprox.. 5 W.

Requisito de software: Estudio 5000 / RSLogix5000 V20 or newer; matching EDS/AOP files required

Manuals: User manual 1747-UM076; Installation manual 1747-IN521

✅ Aplicaciones típicas

  1. Retrofit of legacy SLC systems: Retain all 1746 I/O modules and field wiring. Only replace the Slot 0 processor with 1747-AENTR and upgrade the main controller to CompactLogix/ControlLogix for phased migration without full shutdown.
  2. Replacement of legacy remote I/O adapters: Substitute 1747-ASB (RIO), 1747-ACN15/ACNR15 (ControlNet).
  3. Operate as an EtherNet/IP slave for CIP explicit read/write access by HMI or SCADA hosts.

✅ Lifecycle & Alternativas de migración

Estado: fin de vida, end-of-production date 2027-02-15. It is an engineering replacement part with no direct pin-compatible drop-in replacement.

Long-term migration options:

Opción A: Migrate the complete chassis to Compact 5000 E/S (5069 serie)

Opción B: Keep existing field wiring and adopt 1746-to-5069 adapter base

Spare parts are only available as new-old-stock or used units. For second-hand units, verify firmware, Puerto Ethernet, backplane connector and indicator lamps.

✅ Indicator Definitions

DE ACUERDO: Estado del módulo

LINK: Ethernet link status

E/S: SLC backplane I/O status

COMUNICACIÓN: CIP connection status

FORCE: Force signal active

✅ Key Common Faults

  1. CIP 0x0010 fault: The controller holds an active connection lock on the module. Inhibit the module in Studio5000 before modifying IP settings, then remove inhibit after configuration.
  2. Flashing COMM red & RPI timeout: Do not configure a short RPI for SLC analog modules (1746-NI4, OAP12 etc.). Recommended RPI: 50~100 ms, máximo 320 EM; short RPI causes frequent packet loss.
  3. Invalid DIP IP setting (000 or value >254 and not 888): Module automatically uses BOOTP/DHCP for IP assignment.
  4. Not all legacy 1746 modules are supported by AENTR; verify the support list in manual before configuration.

✅ Confusing Model Distinction

1794-AENTR: Flex I/O (1794) EtherNet/IP adapter for Flex chassis, NOT compatible with SLC 1746 chasis

1747-L5xx: Native SLC processors with backplane master capability, functionally different from AENTR

1747-AENTR Common Faults, Síntomas, Causas fundamentales & Remedios

Requisito previo: Module must be installed in SLC chassis Slot 0, occupying the processor slot; powered by SLC backplane; mainstream firmware V2.003; Studio5000 minimum V20; not all legacy 1746 modules are supported.

  1. CIP 0x0010 (Hex 0010) Falla (Más frecuente)

Síntoma: Error when modifying IP or disabling BOOTP/DHCP via BOOTP/RSLinx; prompt “Set Attribute Single failed”; configuration cannot be written from controller side; IP reverts to DHCP after power cycle.

Causa principal: una clase 1 I/O connection has been established by the controller. The module is connection-locked and rejects configuration writes from external tools.

Remedy Steps

  1. Go online in Studio5000, right-click 1747-AENTR → Properties → Connection → ✅ Check Inhibit Module, apply, and terminate the I/O connection.
  2. Modify IP and disable BOOTP/DHCP via BOOTP/RSLinx/web page to save static IP.
  3. Remove inhibit after configuration is completed to restore communication.

Alternativa: Put controller in Program mode or disconnect Ethernet cable; cable pull during production is not recommended.

  1. COMM Red Flashing, I/O Timeout, RPI Timeout, Intermittent Slave I/O Faults

Síntoma: OK verde fijo, LINK steady green, COMM red flashing; slave modules (especially 1746-NI4, OAP12 analog modules) drop out periodically; RPI timeout logged.

Causa principal

RPI configured too low for analog modules (por defecto 20 EM; SLC backplane bandwidth is limited)

Mal contacto con el backplane, insufficient chassis power rating

Incompatible legacy 1746 module present

High backplane bus load or aged module hardware

Recurso

  1. Set analog module RPI to 50~100 ms, máximo 320 EM; adjust the AENTR adapter RPI accordingly.
  2. Apagar, reseat all 1746 modules and clean gold fingers; verify SLC power supply capacity.
  3. Cross-check against supported module list and remove incompatible modules.
  4. Check backplane slot timeout counters via embedded web diagnostics to locate faulty slot.
  5. OK Steady Red, Power-On Self-Test Failure, No Communication

Síntoma: OK red solid after power-up, LINK off, module cannot be browsed in RSLinx.

Causa principal

Hardware failure or corrupted firmware

Factory reset via DIP 888 failed

Poor backplane power supply, damaged Slot 0 contactos del backplane

Module installed in wrong slot (not Slot 0)

Recurso

  1. Confirm installation in Slot 0 and test with a known-good SLC chassis power supply.
  2. Set DIP switch to 888, power cycle for factory reset; reassign IP via BOOTP.
  3. If OK remains red after reset: module hardware failure, reemplazar unidad.
  4. LINK Off / Brillante, No Network Connectivity, RSLinx Cannot Find Module

Síntoma: OK normal, LINK off or amber flashing, ping fails.

Causa principal: Cable Ethernet dañado, defective switch port, speed mismatch, IP subnet mismatch, Conflicto de dirección IP.

Recurso

  1. Replace with qualified industrial Ethernet cable and change switch port; ensure switch port is 10/100M auto-negotiation (do not force gigabit).
  2. Set DIP to 000, power up to obtain IP via BOOTP; ensure PC and module are on the same subnet.
  3. Check network for IP conflict.
  4. IP Reverts After Power Cycle, Static IP Will Not Save

Síntoma: Static IP assigned and BOOTP disabled in BOOTP tool, but IP reverts to DHCP after power cycle.

Causa principal: Only IP address changed, BOOTP/DHCP client toggle not disabled; 0x0010 connection lock prevents the disable command from being written to Flash memory.

Recurso: Inhibit module first, then set BOOTP/DHCP to Manually Configure on module configuration page, confirm successful write, then remove inhibit.

  1. AENTR Disconnect After Program Download (Known Bug for CompactLogix 5370 L3)

Síntoma: Más que 5 I/O modules in chassis; AENTR loses communication after second program download, controller USB/Ethernet port also unresponsive.

Causa principal: Rockwell known firmware defect.

Temporary workaround: Disconnect AENTR Ethernet cable before download; reconnect after controller enters Run mode. Long-term fix: Upgrade controller firmware or replace controller model.

  1. Electronic Key Fault (Hex 0103)

Síntoma: Fallo del módulo, type mismatch / keying failure alarm.

Causa principal: AOP revision or firmware revision in project does not match physical hardware; or configured slot I/O model differs from actual installed module.

Recurso

  1. Read actual firmware revision from module and match firmware version in Studio5000 module definition.
  2. Verify the part number of every 1746 module in chassis; avoid mixed use with compatible/disabled keying mode.
  3. Reimport the matching AOP file.
  4. FORCE Lamp Solid On

Síntoma: FORCE indicator illuminated.

Causa principal: One or more I/O tags are forced.

Recurso: Clear all force tags in the force window of Studio5000.

  1. Single Slave I/O Module Fault, Adapter Communication Normal

Síntoma: AENTR communicates normally, only one slot module faults while other I/O runs fine.

Causa principal: Failed 1746 módulo, poor base contact, unsupported module model, local module power fault.

Recurso: Swap the suspect module to another slot for cross-testing; verify module health; check support list.

Indicator Quick Reference

DE ACUERDO: Module status|Green = Normal; Rojo = Fallo / POST fail; Amber = Initializing

LINK: Ethernet link|Solid = Link up; Blinking = Traffic present; Off = No link

COMUNICACIÓN: CIP I/O connection|Green = I/O connection healthy; Red blink = Connection fault / se acabó el tiempo

E/S: SLC backplane I/O status|Red = Backplane / slave module fault

FORCE: Force active

Standard On-Site Troubleshooting Sequence

  1. Confirm mounting position: Ranura 0 solo
  2. Read indicator status to isolate fault domain: network, adapter hardware or backplane I/O
  3. Browse via RSLinx to confirm module accessibility and read firmware
  4. If browsable: Inhibit module prior to IP/configuration edit; inspect RPI settings
  5. If not browsable: Check cable, cambiar, fuente de alimentación, factory reset via DIP
  6. Single backplane slot fault: Isolate by module swapping
  7. Firmware corruption: Re-flash firmware with ControlFLASH Plus

Lista de verificación de inspección de unidades de segunda mano

  1. Verify factory reset via DIP 888 works reliably
  2. BOOTP assignment and embedded web page accessible
  3. Stable steady green OK lamp after power-up, no fault
  4. Chassis bench test: Mount 1746 DI module, build I/O tree in Studio5000, correr 30 minutes without RPI timeout
  5. Inspect Ethernet port and backplane gold fingers for corrosion or bad solder

Allen-Bradley SLC500 Full Model List (1747 Controller Family + 1746 Chasis & I/O Family, All EOL Discontinued)

Nota: SLC500 consists of two main families: 1747 (Processors, Adaptadores de comunicación, Scanners) y 1746 (Chasis, Fuentes de alimentación, E/S digitales, E/S analógicas, Specialty I/O). The whole platform is discontinued; spare parts are traded as new-old-stock or used hardware.

  1. 1747 Processors (UPC)|SLC5/01 ~ SLC5/05
Número de piezaFamilyDescripción
1747-L511SLC5/011K program memory, DH485, unidad base
1747-L514SLC5/014K program memory, DH485
1747-L524SLC5/024K program memory, DH485, remote I/O capable
1747-L531SLC5/038k, DH485+DH+
1747-L532SLC5/0316k, DH485+DH+
1747-L533SLC5/0332k, DH485+DH+
1747-L541SLC5/0416k, DH485+DH++RS232
1747-L542SLC5/0432k, DH485+DH++RS232
1747-L543SLC5/0464k, DH485+DH++RS232
1747-L551SLC5/0516k, integrated EtherNet/IP+DH485
1747-L552SLC5/0532k, integrated EtherNet/IP+DH485
1747-L553SLC5/0564k, integrated EtherNet/IP+DH485 (Top-tier SLC processor)
  1. 1747 Adaptadores de comunicación / Scanners (1747-AENTR Listed Here)
Número de piezaDescripción
1747-AENTREtherNet/IP adapter for SLC Slot0, converts 1746 I/O to EtherNet/IP slave (Key model)
1747-ASBRIO remote I/O adapter (RIO slave)
1747-SNRIO remote I/O scanner (RIO master)
1747-ACN15ControlNet scanner
1747-ACNR15ControlNet redundant adapter
1747-DSNDeviceNet scanner
1747-KEDH485/RS232 protocol converter
1747-CP3Programming cable adapter
1747-C11DH485 cable
1747-DU501Data storage module
  1. 1746 Chasis
Número de piezaRecuento de espacios
1746-A44-chasis de ranura
1746-A77-chasis de ranura
1746-A1010-chasis de ranura
1746-A1313-chasis de ranura
  1. 1746 Chassis Power Supplies
Número de piezaClasificación
1746-P1120/240V AC input
1746-P2120/240V y
1746-P324Entrada VCC
1746-P4120/240V y, energía alta
1746-P524V DC high power
1746-P624En DC
1746-P7120/240V y
  1. 1746 Entrada digital DI
Número de piezaClasificación
1746-IA4120V AC 4-point input
1746-IA8120V AC 8-point input
1746-IA16120V AC 16-point input
1746-IM4240V AC 4-point input
1746-IM8240V AC 8-point input
1746-IM16240V AC 16-point input
1746-IB824V DC sink 8-point
1746-IB1624V DC sink 16-point
1746-IB3224V DC sink 32-point
1746-IV824V DC source 8-point
1746-IV1624V DC source 16-point
1746-IV3224V DC source 32-point
1746-ITB1624V DC high-speed sink 16-point
1746-ITV1624V DC high-speed source 16-point
1746-IC1648V DC 16-point
1746-IH16125V DC 16-point
1746-IG165V TTL 16-point
1746-IN16Universal AC/DC 16-point
  1. 1746 Salida digital DO
Número de piezaClasificación
1746-OA8120/240V AC 8-point output
1746-OA16120/240V AC 16-point output
1746-OAP12120/240V AC high-current 12-point
1746-OB824V DC source 8-point
1746-OB1624V DC source 16-point
1746-OB3224V DC source 32-point
1746-OB6EIIsolated DC output 6-point
1746-OW4Relay 4-point
1746-OW8Relay 8-point
1746-OW16Relay 16-point
1746-OX8Isolated relay 8-point
  1. 1746 Combination I/O (DI+DO)
Número de piezaClasificación
1746-IO42DI+2DO 120V AC + relé
1746-IO84DI+4DO
1746-IO126DI+6DO AC/relay
1746-IO12DCDC combination I/O
  1. 1746 Analog I/O AI/AO
Número de piezaDescripción
1746-NI44-channel analog input 4-20mA/0-10V
1746-NI88-entrada analógica del canal
1746-NR4RTD 4-channel
1746-NT4Thermocouple 4-channel
1746-NT8Thermocouple 8-channel
1746-NO4I4-channel isolated analog output
1746-NO8V8-channel voltage output
1746-NO4V4-channel voltage output
1746-NIO4I2AI+2AO isolated analog combo
1746-NIO4V2AI+2AO voltage analog combo
  1. 1746 Specialty Modules (Contador de alta velocidad, Posicionamiento, BASIC etc.)
Número de piezaDescripción
1746-HSCEContador de alta velocidad / codificador
1746-HSCE2Upgraded high-speed counter
1746-HSTP1Stepper positioning module
1746-BAJOBASIC co-processor module
1746-SDNDeviceNet scanner (chassis mount)
1746-HCAHigh-speed counter accessory
  1. Accesorios

1746-C7, 1746-RT25, 1747-licenciado en Letras (batería de litio), bloques de terminales, covers, expansion cables etc.

Supplementary Notes for Retrofit Projects

  1. 1747-AENTR Compatibility Limit: Not all 1746 modules are supported. Early specialty modules (legacy HSCE, BAJO) may not be recognized; analog module RPI must not be too short.
  2. Easy Confusion: 1794-AENTR is Flex I/O adapter, not part of SLC500 (1746) family.
  3. Migration Path: Preferred upgrade route for full SLC replacement: CompactLogix + 5069 Compact5000 I/O.