E-T-A (Eaton Acquired Brand) 3600-P10-Si-8A Thermal-Magnetic Circuit-Breaker for Equipment (CBE)
Nota: E-T-A is not an original Eaton brand; it is a German over-current-protection brand acquired by Eaton. CBE stands for Circuit-Breaker for Equipment.
Decodificación de modelos
3600-P10-Si-8A
3600: 3600 serie, single-pole thermal-magnetic equipment circuit-breaker
P10: Push-button reset, P-housing; 10 = M-type tripping characteristic (thermal overload delay + electromagnetic short-circuit instantaneous trip)
Si: 6.3×0.8 mm blade terminals, supports socket plug-in / panel snap-in mounting, with unprotected shunt tap terminal, sin contactos auxiliares (suffix Sia denotes auxiliary contacts fitted)
8A: Rated current In=8 A
Especificaciones eléctricas básicas
| Artículo | Parámetro |
| polacos | 1-Polo |
| Modo de disparo | Termomagnético (delayed thermal overload + instantaneous electromagnetic short‑circuit) |
| Tensión CA nominal | 250 VAC |
| Rated DC Voltage | 65 VDC |
| Interrupting Capacity | 1000 A |
| Terminales | 6.3×0.8 mm quick‑connect blade terminals |
| Reiniciar | Manual push‑button reset (Trip‑free mechanism) |
| Montaje | Panel snap‑in mounting / plug‑in with dedicated socket bases (17‑P10‑Si / 23‑P10‑Si) |
| Ancho | 11.5 milímetros |
| Certificaciones | UL, VDE, IEC/EN60934, CSA, CE, RoHS |
| Front‑face Ingress Protection | IP40 |
Aplicaciones típicas
Equipos de control industrial, railway & tránsito, instrumentation, communication power supplies, 24-48 VDC circuit protection. It serves as a direct replacement for fuses; manual reset is available upon fault tripping with no fuse replacement required.
Información de pedido
Full order-part-number: 3600-P10-SI-020148-8A (industry-standard complete ordering code).
Available current ratings within series: 0.5 A / 1 A / 2 A / 4 A / 6 A / 8 A / 10 A / 16 A.
Suffix Sia: with auxiliary alarm contacts; Si: sin contactos auxiliares.
Compatible Socket Bases
Socket bases: 17-P10-Si, 23-P10-Si, 63-P10-Si
Montaje en panel: install via ETA original metal mounting clips for cut-out panel assembly.
Reemplazo & Alternative Selection
- OEM same-series alternative: 3600-P10-Sia-8A (for applications requiring auxiliary alarm contacts).
- Domestic compatible alternative prerequisites: 8 A rated current, M-type thermal-magnetic characteristic, 65 VDC / 250 VAC rating, 11.5 mm width, push-button reset, blade-terminal interface.
Recordatorios: This device is an equipment-specific circuit-breaker, not a distribution-type MCB miniature circuit-breaker. Its tripping curve differs from domestic-use MCBs; direct interchange is prohibited.
Comparación: E-T-A 3600-P10-Si-8A vs. Third-Party 1-Pole Thermal-Magnetic CBEs
Governing standard: EN 60934 (Circuit-Breakers for Equipment, CBE). Not compatible with DIN-rail-mounted MCB miniature circuit-breakers per EN 60898; direct swap-out is forbidden.
Key specs for 3600-P10-Si-8A: 11.5 mm width, 6.3×0.8 mm blade terminals, manual push-button reset, M-type thermal-magnetic trip, 250 VAC / 65 VDC, 1000 A interrupt rating, sin contactos auxiliares, panel snap-in or socket-plug-in installation.
- Comparison with European-brand Thermal-Magnetic CBEs (Contacto Fénix, Weidmüller, Schurter)
| Artículo de comparación | ETA 3600‑P10‑Si‑8A | Phoenix Contact Thermal‑Magnetic CBE (CB TM1 series) | Weidmüller Thermal‑Magnetic Equipment Circuit‑Breaker | Schurter Thermal‑Magnetic CBE |
| Mounting Style | Blade plug‑in, panel snap‑in / dedicated socket base; NOT DIN‑rail | Primarily DIN‑rail mount; limited plug‑in variants | Primarily DIN‑rail mount | Complemento / tarjeta de circuito impreso / DIN‑rail multi‑form‑factor |
| Terminación | 6.3×0.8 mm blade terminals for direct socket mating | Tornillo / spring‑cage terminals | Spring‑cage terminals | Quick‑disconnect blades, solder pins |
| Característica de disparo | M‑type equipment‑protection curve; magnetic instantaneous trip ≈8‑12×In | M‑type CBE curve | M‑type CBE curve | M‑type CBE curve |
| DC Voltage Rating | 65 VDC (UL rating 80 VDC) | 65 VDC | 60‑65 VDC | Up to 80 VDC |
| Interrupting Capacity | 1000 A | 1500 A | 1000‑1500 A | 1500 A |
| Reset Actuator | Front‑panel push‑button reset (Trip‑free mechanism) | Rocker‑switch reset | Rocker‑switch reset | Push‑button / rocker optional |
| Contactos auxiliares | None for Si version; Sia variant adds alarm auxiliary contacts | Auxiliary contacts integrated on selected models | Auxiliary contacts as option | Auxiliary contacts as option |
| Device Width | 11.5 mm compact footprint | 12.5 milímetros | 12.5 milímetros | 12.7 milímetros |
| Core Application Strength | Railway transit, instrumentation, equipo de comunicacion; front‑panel embedded equipment‑level protection | DIN‑rail cabinet‑internal circuit protection | Control cabinet system‑level protection | Fuente de alimentación, equipo medico |
Distinción crítica: The ETA 3600 is designed for equipment front-panel mounting or socket plug-in, not DIN-rail installation. Most Phoenix / Weidmüller thermal-magnetic CBEs are DIN-rail cabinet-mounted with spring-cage / terminales de tornillo, lacking 6.3 mm blade socket interface; mechanical fit is incompatible, direct replacement is impossible.
- Fundamental Differences vs. DIN-Rail MCB Miniature Circuit-Breakers (do / D-curve) — Common Pitfall
MCB complies with EN 60898 for power-distribution purposes. ETA 3600 complies with EN 60934 for equipment-protection CBE. Different standards; direct interchange strictly prohibited.
- Tripping Curve Difference
ETA 3600-P10-Si: M-type CBE characteristic, optimized for industrial devices, coils and power supplies; tolerates moderate inrush surge current with mild thermal tripping behaviour.
MCB C-curve: instantaneous trip 5-10 × In; D-curve: instantaneous trip 10-20 × In, designed for wiring distribution protection. Risk of nuisance tripping or failure-to-trip when protecting electronic equipment.
- DC Performance Gap
Y: 65 VDC rating, validated DC arc-extinguishing for 24-48 V industrial DC loops.
Conventional 1-pole MCB: most rated ≤48 VDC; many variants have no DC rating at all. Arc-extinguishing failure risk exists under higher DC voltage.
- Interrupting Capacity
Y: 1000 A (equipment-protection rating). Standard miniature MCBs advertise 6 kA AC interrupt rating, which applies for AC distribution short-circuit conditions; performance differs substantially for low-voltage DC short-circuit events.
- Installation Form Factor
Y: blade-socket / panel-clip mounting, fitted onto equipment chassis front-panel. MCB clamps to DIN-rail inside control cabinets.
- Comparison with Domestic Clone-Compatible CBE Products
Domestic drop-in alternatives for 3600-P10-Si replicate: 6.3×0.8 mm blade terminals, 11.5 mm width, push-button reset; physically fit original ETA sockets 17-P10-Si / 23-P10-Si.
Major performance gaps:
Tripping consistency: Bimetallic element dispersion for M-curve; significant tripping-point drift across wide temperature range (−40 ~ +85 °C), which is critical for railway-transit deployments.
Trip-free safety mechanism: Some low-cost domestic copies omit this feature; the breaker can be forced closed manually even under fault conditions, a major safety hazard.
Certification coverage: Original carries full VDE/UL/CSA approvals; many domestic alternatives only carry self-declared CE, disqualifying them for export-grade equipment.
Internal contact resistance: Original 3600 series typical resistance 12-18 mΩ; some domestic units exhibit higher resistance and excessive heating under full-load current.
- Practical Replacement Prerequisites
All criteria must be satisfied for direct drop-in replacement:
✅ Complies with EN 60934 CBE standard, M-type tripping characteristic
✅ Rated 250 VAC, DC rating ≥65 V
✅ 6.3×0.8 mm blade terminals, 11.5 mm device width
✅ Manual push-button reset + Trip-free mechanism
✅ Interrupting capacity ≥1000 A
❌ DIN-rail MCBs and electronic PTCB circuit-breakers cannot substitute directly. PTCB uses electronic current-limiting, while thermal-magnetic breakers rely on physical bimetallic actuation; fault-response behaviour is fundamentally different.
- Select suffix -Sia variant if fault-alarm signalling is required; -Si has no auxiliary contacts.
- Low-resistance sibling series: 3900-P10-Si-8A, lower internal resistance for circuits sensitive to voltage drop.
- Typical Selection Misconceptions
- “Same 8 A rating means interchangeable”: Curva de disparo, DC voltage rating, Trip-free safety mechanism and mechanical mounting interface are all mandatory matching criteria.
- Substituting thermal-magnetic CBE with Phoenix PTCB electronic circuit-breaker: PTCB implements electronic current-limiting, not thermal-magnetic actuation; overload response differs, cannot be swapped directly.
- Direct substitution with standard C-curve MCB: risk of DC arc-extinguishing failure on 24-48 V DC loops and mismatched equipment-protection tripping thresholds.
E-T-A 3600-P10-Si-8A Application Scenarios
This device is an EN 60934 thermal-magnetic Circuit-Breaker for Equipment (CBE). Its intended use is circuit-protection inside end-equipment, not cabinet-level power-distribution. Key features: panel-clip / socket-plug-in mounting, 250 VAC / 65 VDC rating, M-type thermal-magnetic trip, manual push-button reset. No fuse replacement needed after tripping.
Nota: -Si variant has no auxiliary alarm contacts. Choose the -Sia suffix model if fault-status output signal is needed.
🔌 DC Circuit Applications (Most Common for 24 V / 48 V Industrial DC)
- Internal supply sub-circuits for industrial control hardware
Power feeds for PLC peripherals, IO modules, collective sensor loops, servo auxiliary power supplies, 24 V solenoid-valve banks. The 8 A rating suits clustered banks of sensors and solenoid valves. Replaces fuses, delivers short-circuit & protección contra sobrecarga. On-site push-button reset without chassis disassembly and fuse swap.
- Telecom & industrial power hardware
Internal power branches for industrial switches, gateways, DTUs, edge-computing hardware; 48 V telecom equipment for board-card output-circuit protection.
- Battery-powered equipment
Secondary-side circuit-protection for lithium-ion / lead-acid battery-operated devices. 65 VDC rating covers nearly all 24-48 V battery-based systems.
🚆 Railway & Tránsito (ETA Traditional Strength Domain)
On-board equipment boxes, metro vehicle control units, door-control modules, cabin lighting, on-board instrumentation.
Operates over wide temperature range −40 °C ~ +85 °C, high vibration-shock resistance. Front-panel installation allows maintenance-staff reset without cabinet opening.
Railway projects normally specify -Sia auxiliary-contact variant, to report fault events to vehicle control systems.
🧪 Instrumentation & Non-Life-Support Medical Auxiliary Equipment
Test-and-measurement hardware, laboratory analytical instruments, production test fixtures, non-life-support medical auxiliary devices.
Fuse-replacement with resettable protection, reduces spare-part inventory; full UL/VDE certification satisfies equipment safety requirements.
Not recommended for direct deployment on life-critical medical primary circuits without full assessment.
📟 Industrial Chassis & Embedded Equipment
- Card-cage chassis hardware: deploy with socket bases 17-P10-Si / 23-P10-Si; breaker plugs into socket for quick hot-swap replacement.
- Panel-cutout clip-mount installation: reset push-button protrudes through equipment front-panel for easy operator access.
This is the primary differentiator vs DIN-rail breakers: it mounts to the end-equipment itself, not inside control-cabinet DIN-rail infrastructure.
⚙️ Construction Machinery & Off-Highway Vehicle Electronics
Construction-vehicle / special-vehicle on-board electrical enclosures, portable field-test gear. 24 V vehicle-system operation; M-type characteristic tolerates motor / coil inrush transients without nuisance tripping; high vibration immunity.
❌ Non-Suitable Use-Cases
- Doméstico / building power-distribution circuits: Cannot replace MCB miniature breakers; it is equipment-internal protection, not wiring-distribution protection.
- DC voltages exceeding 65 V: Maximum DC rating is 65 V; forbidden for 72 V, 110 V DC systems.
- Remote electrical-trip requirement: No shunt-trip coil available; only manual push-button reset.
- Fault-alarm signal requirement: -Si has no auxiliary contacts; order -Sia instead.
✅ Selection Tips
- Circuits containing motors or inductive coils: M-type tripping withstands motor startup surges and prevents nuisance tripping.
- Equipment requiring fault-status acquisition: Specify 3600-P10-Sia-8A.
- Voltage-drop-sensitive circuits: Upgrade to low-resistance variant 3900-P10-Si-8A.