IC693ALG392C GE Fanuc, now Emerson 8-Channel Analog Output Module

Modelo: IC693ALG392C Type: Analog Voltage / Current Output Module Applicable Platforms: GE Series 90-30, PACSystems RX3i Channels: 8 single-ended outputs; each channel can be configured independently 📌 Configurable Output Ranges (Software Setup Only) Voltaje: 0~10V (unipolar), -10~+10V (bipolar) Actual: 0~20mA, 4~20mA (widely used for control valves and transmitters) 📐 Key Technical Specifications Resolution: 15~16 bits, ...

  • Detalles del producto

Modelo: IC693ALG392C

Tipo: Analog Voltage / Actual Módulo de salida

Applicable Platforms: GE Series 90-30, PACSystems RX3i

Canales: 8 single-ended outputs; each channel can be configured independently

📌 Configurable Output Ranges (Software Setup Only)

Voltaje: 0~10V (unipolar), -10~+10V (bipolar)

Actual: 0~20mA, 4~20mA (widely used for control valves and transmitters)

📐 Key Technical Specifications

Resolución: 15~16 bits, depending on selected range

Refresh Time: 8 ms for all 8 canales

Maximum Load: 5 mA por canal

Fuente de alimentación:

Backplane 5VDC (110mamá); external 24VDC user power (315mamá).

The 24VDC must be wired to terminal blocks; backplane power alone is insufficient.

Diagnóstico: Open-wire fault detection for current mode, with fault alarm sent to the CPU.

Power-down Behavior: Configurable – hold last output value or reset to zero (only valid if external 24V stays powered).

Exactitud: Factory-calibrated at ambient temperature; ±1%FS for current signals, ±3%FS for voltage signals under strong RF interference.

Instalación: Fits any I/O slot; metal control cabinet mounting recommended.

⚠️ Version Notes

IC693ALG392A / B / do / D: Hardware revisions. Version C is the most widely stocked model, fully backward-compatible with existing programming and hardware configurations.

Comparación dentro de la serie.: IC693ALG390 (2HACIA), IC693ALG391 (2HACIA). The ALG392 is the high-density 8-channel variant.

🔧 Typical Applications

Modulating control valves, VFD setpoints, proportional valves, 4–20mA actuators, signal retransmission to recorders (climatización, tratamiento de agua, industria química, packaged machinery).

🛠️ Troubleshooting Common Failures

  1. Open-wire fault in current loop: Check terminal wiring, instrument power supply and loop resistance. The module does not supply loop power.
  2. Output drift: Stabilize the external 24VDC power supply, route wiring away from inverter high-power cables, and perform recalibration.
  3. No output change: Verify range configuration in GX Configurator, backplane power status, and online module status.

🔁 Alternative Replacements

Actualización de la misma plataforma: IC694ALG392 (RX3i high-performance version)

Reemplazo entre marcas: Depends on PLC backplane; cannot be directly swapped with Allen-Bradley modules.

Application Scenarios for IC693ALG392C (GE 90-30 / RX3i 8-Channel AO Module)

Función principal: 8 independent 4~20mA / 0~10V / -10~+10V analog outputs to send setpoints to field actuators. This is a control-side output module; it only transmits control commands and does not collect field signals.

Controladores compatibles: GE Fanuc Series 90-30, PACSystems RX3i. Mostly used for legacy project spares and retrofits of imported packaged equipment.

  1. Tratamiento de agua (Aplicación más común)
  2. VFD setpoint: 4–20mA frequency command for water supply pumps, return pumps and chemical dosing pumps.
  3. Electric control valves: Regulate inlet valves, outlet valves, pH control valves and turbidity valves.
  4. Chemical dosing systems: Variable-speed metering pump flow setpoints for PAC/PAM, acid and alkali dosing.
  5. Aeration control: Adjust aeration duct dampers and fan vane opening for closed-loop DO (oxígeno disuelto) control.
  6. Sludge handling: Control sludge return valves and waste sludge valves.
  7. climatización & Cleanroom Air Conditioning
  8. AHU air handlers: Modulate cold water valves, hot water valves and humidifier valves for constant temperature & control de humedad.
  9. VAV variable-air-volume dampers for air handling units and exhaust cabinets.
  10. Torres de enfriamiento: Regulate cooling water valves and fan speed setpoints.
  11. Temperatura & humidity closed-loop control for pharmaceutical cleanrooms.
  12. Químico & Fine Chemical Batching Systems
  13. Mezclando & batching lines: Control feed valves and proportional valves to stabilize material ratios.
  14. Pressure control loops: Pneumatic diaphragm valves to maintain tank pressure.
  15. Temperature control loops: Steam and cooling water control valves for reactors.
  16. Small reaction vessels: VFD speed command for agitators, plus steam/cooling valve regulation.

Ventaja: High-density 8-channel design; multiple PID control loops can be centralized in one module to save I/O slots.

  1. Calefacción & Boiler Energy Systems
  2. Boiler controls: Gas regulating valves, feedwater valves, induced draft fan VFD setpoints.
  3. Heat exchanger stations: Primario & secondary network regulating valves for heat exchanger temperature control.
  4. Waste heat recovery device modulation.
  5. Extrusión de plástico, Embalaje & Maquinaria general
  6. Extrusoras: Proportional valve control and melt pump speed setpoints for barrel zone temperature control.
  7. Revestimiento & laminating machines: Tension proportional valves and line speed synchronization via VFD analog setpoints.
  8. Hydraulic proportional valve control (±10V signal preferred for pressure/flow continuous regulation).
  9. Multi-section speed synchronization for production lines.
  10. Grano & Procesamiento de piensos
  11. Grain drying lines: Hot air dampers and exhaust dampers for drying temperature closed-loop control.
  12. Continuous loss-in-weight feeding: VFD setpoints for feeding conveyors.
  13. Otras aplicaciones

Constant-pressure water supply pump control panels for buildings.

Exhaust gas treatment (RCO/RTO): Air damper adjustment and dilution fan speed setpoints.

Analog signal transmission to paperless recorders and digital indicators (0~10V signal).

✅ Selección & Pautas de solicitud

  1. 4~20mA: Preferred for control valves, inverters and metering pumps. The module does not provide loop power; an external power supply is required to complete the current loop.
  2. ±10V: Used for hydraulic proportional valves and servo actuators.
  3. Designed for continuous closed-loop PID regulation; not suitable for discrete on/off signals.
  4. Primarily used for legacy equipment retrofits: Many older imported packaged machines use the 90-30 SOCIEDAD ANÓNIMA; IC693ALG392C is the preferred spare part.

❌ Aplicaciones inadecuadas

Analog signal acquisition (use AI modules such as IC693ALG220 / ALG221 instead).

Direct driving of solenoid valves or high-power loads.

High-speed servo motion control (8ms full-channel refresh limits dynamic response).

Full List of GE Fanuc (emerson) Analog Output AO Modules

(Including mixed I/O modules with analog output channels)

Platform Classification: Serie 90-30 (IC693), RX3i Universal Backplane I/O (IC694), RX3i High-Performance PCI Backplane (IC695).

Suffix A/B/C/D = PCB hardware revisions; all versions are fully interchangeable with identical functions.

  1. Serie 90-30 (IC693, Obsoleto, Spare Parts Only)
ModeloCanalesTipoRangesObservaciones
IC693ALG3902HACIASalida de voltaje0~10V / -10~+10VVoltage-only, no current output
IC693ALG3912HACIASalida actual0~20mA, 4~20mACurrent-only
IC693ALG3928HACIAUniversal Voltage/Current0~10V, ±10V, 0~20mA, 4~20mASingle-ended; open-wire diagnosis; IC693ALG392C is the most common stock version
IC693ALG4424IA+2AOMixed Analog I/O0~10V, ±10V, 0~20mA, 4~20mA4 differential inputs + 2 HACIA; compatible with 90‑30 & RX3i
  1. RX3i IC694 Series (Backward Compatible with 90-30, Reemplazo de actualización directa)
ModeloCanalesTipoRangesObservaciones
IC694ALG3902HACIASalida de voltaje0~10V, ±10VUpgrade version of IC693ALG390
IC694ALG3912HACIASalida actual0~20mA, 4~20mAUpgrade version of IC693ALG391
IC694ALG3928HACIAUniversal Voltage/Current0~10V, ±10V, 0~20mA, 4~20mADirect replacement for IC693ALG392; 8ms refresh
IC694ALG4424IA+2AOMixed Analog I/O0~10V, ±10V, 0~20mA, 4~20mA2ms high-speed refresh
IC694ALG5424IA+2AOMixed Analog I/O0~10V, ±10V, 0~20mA, 4~20mAMayor precisión; capacidad de intercambio en caliente
  1. RX3i IC695 Series (High-Performance PCI Backplane, New Project Standard)
ModeloCanalesTipoRangesObservaciones
IC695ALG7044HACIAUniversal Voltage/Current0~10V, ±10V, 0~20mA, 4~20mAWith upper/lower limit alarm, rampa & slew rate limiting
IC695ALG7088HACIAUniversal Voltage/Current0~10V, ±10V, 0~20mA, 4~20mAHigh-density 8-channel; no HART support
IC695ALG7288HACIAUniversal AO + CIERVO0~10V, ±10V, 0~20mA, 4~20mACompatible con protocolo HART, ideal for smart control valves
IC695ALG8088HACIAChannel-Isolated AO0~10V, ±10V, 0~20mA, 4~20mAChannel-to-channel galvanic isolation; high anti-interference for chemical and hazardous cabinet applications
  1. Notas complementarias
  2. All IC693 series modules are discontinued; solo stock excedente, refurbished and used units are available. New projects should select IC694 or IC695 series.
  3. Guía de selección:

Standard valves & VFD setpoints: IC693ALG392 / IC694ALG392 / IC695ALG708

Smart HART valves: IC695ALG728

High EMI & ground potential difference: IC695ALG808 (isolated channels)

Few analog points & compact cabinets: ALG390/391, IC695ALG704

Combined AI+AO to save slots: ALG442 / ALG542

  1. Common Power Requirement for all AO modules:

Backplane 5VDC only supplies logic power. An external 24VDC field power supply is mandatory. Current loops require external power to complete the circuit; the module cannot supply loop current.

  1. VersaMax Micro System (IC200) AO Modules (Reference Only)

IC200ALG320: 4-channel 4~20mA current output

IC200ALG321: 4-channel universal voltage/current output