LS (MEC) Thermal Overload Relay GTH-22/3

Legacy MEC series, 22marco AF, 3-elemento (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. Modelo de reemplazo: MT-32/3H ✅ Core Specifications Trip class: Clase 10A (protección de motor estándar) Contactos auxiliares: 1a1b (1NO + 1CAROLINA DEL NORTE) Funciones de protección: sobrecarga, rotor bloqueado, 3-phase phase-loss protection (advantage of 3-element design) Construcción: bimetallic ...

  • Detalles del producto

Legacy MEC series, 22marco AF, 3-elemento (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. Modelo de reemplazo: MT-32/3H

✅ Especificaciones principales

clase de viaje: Clase 10A (protección de motor estándar)

Contactos auxiliares: 1a1b (1NO + 1CAROLINA DEL NORTE)

Funciones de protección: sobrecarga, rotor bloqueado, 3-phase phase-loss protection (advantage of 3-element design)

Construcción: tira bimetálica, compensación de temperatura, mecanismo sin viaje

Tensión nominal de aislamiento Ui: 690V

Modo de reinicio: Reinicio manual (with TEST button)

Montaje independiente: Optional bracket AZ-22H

📋 Full Current Range List for GTH-22/3

Código de modeloConfiguración del rango actual
GTH-22/3 0.160.1~0.16A
GTH-22/3 0.210.16~0.25A
GTH-22/3 0.330.25~0.4A
GTH-22/3 0.50.4~0.63A
GTH-22/3 0.80.63~1A
GTH-22/3 1.31~1.6A
GTH-22/3 2.11.6~2.5A
GTH-22/3 3.32.5~4A
GTH-22/3 54~6A
GTH-22/3 6.55~8A
GTH-22/3 7.56~9A
GTH-22/3 8.57~10A
GTH-22/3 119~13A
GTH-22/3 1512~18A
GTH-22/3 1916~22A

🔁 Información de reemplazo

Factory upgraded replacement: MT-32/3H (identical current ratings, direct replacement for GTH-22/3)

Distinción: GTH-22/2 is 2-element, without phase-loss protection, do not interchange

📌 Wiring Notes

Circuito principal: 1/2/3 EN, 4/5/6 AFUERA, connected in series between contactor outlet and motor

Contactos auxiliares: 95-96 (CAROLINA DEL NORTE, wired into contactor coil circuit); 97-98 (NO, para alarma de falla)

Configuración actual: Align dial pointer with motor full-load current (FLA)

  1. Definición de terminal & Standard Start-Stop Wiring for GTH-22/3

Marcas de terminales:

Circuito principal: 1, 3, 5 (incoming); 2, 4, 6 (outgoing), wired in series after contactor T1/T2/T3 and before motor

Contactos auxiliares:

95-96: NC normalmente cerrado (must be wired in contactor coil circuit; opens on overload to stop motor)

97-98: NO normalmente abierto (for alarm lamp / PLC fault input)

Front panel buttons: PRUEBA (simulated trip), REINICIAR (reiniciar); GTH-22/3 is factory set to manual reset only, no auto-reset selector (different from some domestic thermal relays)

Standard Start-Stop Wiring Sequence (380V Motor)

  1. Circuit breaker → Contactor KM main contacts L1/L2/L3
  2. KM output T1/T2/T3 → GTH-22/3 terminals【1, 3, 5】
  3. GTH-22/3 terminals【2, 4, 6】→ Motor 3-phase terminals
  4. circuito de control: Power supply → Stop button NC → 95 → 96 → Start button NO → KM coil A1/A2; KM auxiliary NO for latching
  5. Circuito de alarma: 97-98 in series with alarm lamp / relé intermedio, powered from control supply

Instalación de complementos: Snap directly onto the bottom of GMC-9/12/18/22 contactors. DIN rail independent mounting requires bracket AZ-22H.

✅ Offline Test Method (Apagar)

Use multimeter continuity mode:

estado normal: 95-96 conducts; 97-98 abierto

Presione el botón de PRUEBA: 95-96 abre, 97-98 cierra; release TEST, RESET button must be pressed to restore

  1. Tabla de solución de problemas (GTH-22/3 3-element phase-loss protected type)

Precaución: GTH-22/3 is Class 10A. It protects against overload, locked rotor and phase loss ONLY. It cannot provide short-circuit protection. Short-circuit protection shall be implemented by fuse or circuit breaker.

SíntomaCausa principalInspección & Recurso
Sobrecarga del motor / rotor bloqueado, thermal relay does not trip or protect1. Setting current too high2. Heating element burnt or internal solder joint open3. Mecanismo atascado, bimetallic strip deformed4. Wrong frame size (current range oversized)1. Align setting dial with motor nameplate rated current (FLA; +5%~10% allowed for frequent start)2. Measure continuity of main circuit phases 1-2, 3-4, 5-6 con multímetro; replace if open3. Activate TEST button to verify contact switching; replace if TEST fails4. Confirm model is GTH-22/3 (3-element with phase-loss protection), not GTH-22/2
Motor runs at normal load, nuisance tripping, trips immediately on startup1. Setting current too low2. Loose terminal connection, calentamiento excesivo (terminal heat triggers premature bimetallic action)3. High cabinet ambient temperature, mounted too close to hot contactor4. Long motor starting time (carga de alta inercia)5. 3-pérdida de fase de suministro de fase (GTH-22/3 trips on phase loss)1. Recheck motor rated current and adjust setting upwards2. Apagar, retighten all main circuit screws; inspect conductors for oxidation or discoloration3. Keep clear of heat sources, mejorar la ventilación; increase setting by 5% if ambient >40℃4. For long-start loads, consider Class20 thermal relay5. Measure 3-phase supply voltage, check for missing phase or broken cable
después de tropezar, RESET button cannot reset the relay1. Internal trip mechanism jammed or damaged2. Bimetallic strip not cooled down (2~5 min cooling required; hot state prevents reset)3. Auxiliary contacts welded together1. Wait for cooling then retry reset; replace if still unable to reset after cooling2. Medida 95-96 continuidad; replace if remains open after reset
Control circuit dead, el contactor no puede entrar1. Thermal relay tripped, 95-96 open2. Loose or broken wiring on 95/963. Auxiliary contacts eroded and high resistance1. Reset relay first, then test continuity of 95-962. Re-terminate control wiring; replace relay if contacts are heavily burnt
Random tripping after running for a period, restarts after cooling1. Hidden motor overload, bearing seizure, excessive load2. Undersized cable, high voltage drop, terminal overheating3. Unbalanced 3-phase current1. Measure 3-phase running current with clamp meter, compare against setting value2. Inspect motor bearings, impeller and gearbox for binding3. If current imbalance >10%, investigate supply voltage and motor winding

III. Special Notes for GTH-22/3

  1. 3-elemento (/3) ≠ 2-element (/2):GTH-22/3 has phase-loss protection; GTH-22/2 does not, cannot substitute
  2. Phase-loss protection principle: If one phase is lost, the other two phases draw elevated current, the two corresponding heating elements heat and bend the bimetallic strips to trigger trip. It is thermal accumulation, not instantaneous voltage detection.
  3. Conductor sizing: Main circuit conductors must be sized for rated current; thin wiring causes false tripping from self-heating.
  4. Avoid frequent TEST operation, which accelerates internal mechanism wear.
  5. Replacement model MT-32/3H shares identical terminal assignment and wiring logic, intercambio directo.
  6. Quick On-site Troubleshooting Sequence
  7. Isolate power → Visual inspection: marcas de quemaduras, burnt odor, overheated terminals
  8. Prueba de multímetro: main circuit phase continuity, auxiliary contact normal state
  9. Activate TEST to confirm trip action and reset function
  10. Encendido, clamp meter test 3-phase running current, cross-check setting
  11. Measure 3-phase voltage, check phase loss and imbalance
  12. Rule out motor and mechanical load faults before confirming thermal relay failure

Overload Protection Principle of Bimetallic Thermal Relé de sobrecarga (GTH-22/3 type)

Principio fundamental: Current thermal effect + bimetallic strip thermal deformation, simulating motor thermal characteristics for delayed overload protection. It cannot provide instantaneous short-circuit protection.

  1. Componente central: Tira bimetálica

Two metal strips with different thermal expansion coefficients are clad together:

Active layer: higher expansion rate

Passive layer: lower expansion rate

At ambient temperature: departamento, mechanism latched, 95-96 NC contact closed.

  1. Action Sequence on Overload
  2. Motor current flows through heating element, higher current generates more heat;
  3. Heat transfers to bimetallic strip;
  4. Differential expansion causes the strip to bend toward the low-expansion side;
  5. Sustained overcurrent accumulates bending displacement until trip threshold is reached;
  6. Mechanical latch releases: 95-96 Se abre el contacto NC, cutting contactor coil supply and stopping motor; 97-98 NO contact closes for fault signal.

Característica: Característica de tiempo inverso

Larger overload current → faster heating and shorter trip time. Mild overload requires long duration to trip, matching motor allowable short-time overload. For Class10A: trips within 4~10s at 10× setting current.

  1. Additional Phase-loss Protection Principle of GTH-22/3 (3-elemento)

Basic 2-element relays only monitor two phases.

GTH-22/3 has independent heating elements and bimetallic strips for all three phases:

When one supply phase is lost, the remaining two phases carry excess current, both heating elements bend and trigger accelerated trip.

Phase-loss protection is still thermal accumulation, not instantaneous voltage detection.

  1. Built-in Temperature Compensation (GTH series)

Internal compensation bimetallic strip offsets ambient temperature influence, preventing false tripping in hot cabinet or cold environment when current is normal.

  1. Reset Principle

después de tropezar, the bimetallic strip must cool and spring back to original shape.

GTH-22/3 is manual reset: after full cooling, press RESET to re-latch the mechanism and restore contact status.

  1. Limitaciones clave (Field Critical)

✅ Protected conditions: sobrecarga sostenida, rotor bloqueado, pérdida de fase, continuous excess current

Not protected: cortocircuito (short-circuit current is too high; the relay will burn before the strip bends. Short-circuit protection via breaker/fuse)

Not protected: corriente de irrupción instantánea (starting current is bypassed by inverse time delay)

LS (Legacy GTH + New MT Series) Thermal Relay ↔ Contactor Compatibility Chart

Notas: Direct plug-in fit. Independent DIN rail mounting requires bracket (AZ / UZ series). /3 = 3-element with phase-loss protection; /2 = 2-element without phase-loss protection.

  1. Legacy GTH Series (including GTH-22/3)
Thermal Relay ModelDirect Plug-in ContactorObservaciones
GTH-22/2, GTH-22/3GMC-9, GMC-12, GMC-18, GMC-22Max setting 22A; bracket AZ-22H for standalone mounting
GTH-40/2, GTH-40/3GMC-32, GMC-40Max setting 34A
GTH-85/2, GTH-85/3GMC-50, GMC-65, GMC-75, GMC-85Max setting 74A
GTH-100/2, GTH-100/3GMC-100, GMC-125Max setting 107A
GTH-150/2, GTH-150/3GMC-150Max setting 130A
GTH-220/2, GTH-220/3GMC-180, GMC-220Max setting 200A
GTH-400/2, GTH-400/3GMC-300, GMC-400Max setting 320A
  1. New MT Series (GTH Replacement, Metasol)
Thermal Relay ModelContactores compatiblesReplaces LegacyStandalone Bracket
MT-32/3HMC-9b, MC-12b, MC-18b, MC-22b, MC-32a, MC-40aGTH-22/3, GTH-40/3UZ-32
MT-63/3HMC-50a, MC-65aGTH-85UZ-63
MT-95/3HMC-75a, MC-85a, MC-100aGTH-100UZ-95
MT-125/3HMC-125aGTH-150UZ-125
MT-200/3HMC-150a, MC-185a, MC-220aGTH-220UZ-200

III. Common Pitfalls for GTH-22/3

  1. GTH-22/3 only plugs into GMC-9/12/18/22, cannot directly fit GMC32 and above contactors.
  2. Current rating = adjustable range, not contactor rating. Contactor rated current must be ≥ motor rated current.
  3. Ruta de actualización: GTH-22/3 → MT-32/3H. Same terminal definition and contact logic, but new contactors are MC series instead of old GMC.
  4. Bracket incompatibility: AZ-22H for old GTH; UZ-32 for new MT-32, cannot interchange.
  5. Regla de selección rápida

Motor rated current ≤22A: Old scheme GMC-9~~22 + GTH-22/3; New scheme MC-9b~~22b + MT-32/3H

Setting Current Adjustment Procedure for LS GTH-22/3 Thermal Relay

  1. Setting Principle

Setting Current = Motor Nameplate Full-Load Current (FLA)

Continuous-duty standard motor: set exactly to nameplate FLA

Admirador / pump general loads: set to nameplate value

inicio frecuente, heavy-start or long acceleration loads: +5% ~ +10% of FLA, do not exceed 1.1×

Intermittent short-cycle motor: can reduce slightly, minimum ≥0.9× FLA

Nota: The dial scale of GTH-22/3 is adjustable range, not fixed value. The value aligned by the pointer is the setpoint.

  1. Pasos de ajuste (GTH-22/3)
  2. Power off for safety (always power off before adjustment to avoid live terminal exposure)
  3. Open the front protective cover
  4. Rotate the central adjustment dial with indicator pointer
  5. Align pointer to target setting current
  6. Refit cover
  7. Encendido, test run, verify 3-phase current with clamp meter

Ejemplo:

Motor nameplate FLA = 5.2A → Select GTH-22/3 5 (4~6A range), align pointer to 5.2.

III. On-site Verification (Crítico)

Después del ajuste, run motor at full load and measure 3-phase current with clamp meter:

Measured stable current ≈ setting value: normal

Continuous running current far below setting: protection is loose, overload may not trip

Frequent tripping near rated current: check setting, sobrecarga del motor, hot terminals or high ambient temperature

  1. Conceptos erróneos comunes
  2. Set by contactor rated current: wrong, always reference motor nameplate
  3. Turn dial to maximum end: removes effective overload protection
  4. Increase setting heavily to accommodate starting inrush: inverse time characteristic is designed to withstand starting surge, no large over-set required
  5. Adjust setting to fix 3-phase imbalance: imbalance must be traced to supply, cable or motor winding, not thermal relay setting
  6. Temperature Compensation Impact

GTH has built-in temperature compensation. If cabinet ambient temperature is persistently above 40℃, relay trips easier at same current; a 5% upward setting is acceptable. If ambient <0℃, setting can be reduced slightly.

  1. Supplementary Notes for GTH-22/3

TEST button only simulates trip, it does not change the current setting value

Adjustment only changes overload trip threshold, phase-loss protection function remains active