Mitsubishi NV125-SV 3P 63A Earth Leakage Circuit Breaker

NV = Earth Leakage Circuit Breaker (ELCB); NF = standard MCCB without earth leakage protection; 125 = Frame size AF125A; SV = Standard S model; 3P = 3-pole; 63A = rated operational current In=63A ✅ Core Electrical Specifications Item Parameter Full Model No. NV125‑SV 3P 63A with adjustable earth leakage 100/200/500mA Rated Voltage Ue AC100~440V, ...

  • Detalles del producto

NV = Earth Leakage Circuit Breaker (ELCB); NF = standard MCCB without earth leakage protection; 125 = Frame size AF125A; SV = Standard S model; 3P = 3-pole; 63A = rated operational current In=63A

✅ Core Electrical Specifications

ArtículoParámetro
Número de modelo completo.NV125‑SV 3P 63A with adjustable earth leakage 100/200/500mA
Rated Voltage UeAC100~440V, suitable for 3-phase 3-wire / single-phase 2-wire circuits
Corriente nominal en63A
polacos3PAG (3 fases, neutral not switched)
Short-circuit Breaking Capacity Icu/Ics@AC400V30el / 30el
Earth Leakage Sensitivity3-nivel ajustable: 100mamá / 200mamá / 500mamá
Tipo de fugatipo de CA, surge resistant, anti-harmonic, suppresses nuisance tripping
Tiempo de funcionamientomáx.. 0.04s
Dimensión general (Ancho×Alto×Profundidad)90mm × 130mm × 90mm
PesoAprox.. 1.1kilos

📌 Model Code Breakdown

  1. NV: Earth Leakage Circuit Breaker (ELCB, moulded case type with leakage protection)
  2. 125: Frame rating 125A (frame size, this unit rated 63A)
  3. SV: Standard S type (New WS-V generation); CV = Economy type, HV = High breaking capacity type
  4. 3PAG: 3-polo, protects 3 live phases, neutral line does not pass through breaker
  5. 63A: Continuous rated circuit current 63A

Common suffix: 1.2.500MA = 100/200/500mA adjustable earth leakage

🛠️ Application Scenarios

Industrial control panels, bombas de agua, fans, small 3-phase power circuits

Integrated protection for equipment: fuga a tierra, sobrecarga & protección contra cortocircuitos

Suitable for harmonic-rich environments (VFD, servoaccionamientos), less prone to nuisance tripping than older generations

Montaje en panel, standard screw terminals; optional accessories: Alarm switch AL, Auxiliary switch AX, viaje de derivación / Under-voltage coil

⚠️ Selección & Notas de reemplazo

  1. Distinguish NV (ELCB with leakage) vs NF (standard MCCB without leakage). Similar appearance, NO directamente intercambiable.
  2. 3P version does NOT disconnect neutral conductor. Select 4P model NV125-SV 4P if neutral switching is required.
  3. Earth leakage threshold is preset at factory and adjustable via rotary knob on site; 100mA para protección personal, 200/500mA for equipment fire protection.
  4. Domestic alternatives reference: CHNT NM1LE-125S/3P 63A, Delixi CDM1LE-125/3P 63A; verify breaking capacity and adjustable leakage range.
  5. Within the same frame size, current rating can be changed directly (63/75/80/100/125A), mounting dimensions remain unchanged.

🧰 Troubleshooting Quick Reference

Trips immediately upon closing: Priority check for earth leakage or damaged load insulation; try higher leakage threshold.

Disparo por sobrecarga: Corriente de carga continua >63A; inspect motor / cable loading.

Disparo por cortocircuito: Severe short circuit; power off and inspect for phase-to-phase short circuit.

Leakage protection fails to operate: Press red TEST button periodically; verify leakage function monthly.

mitsubishi NV125-SV (WS-V Series) Built-in Accessory List (HACHA / Alabama / SHT / UVT)

All accessories are clip-on built-in modules, field mountable; compatible for NV125-SV / NF125-SV same frame; accessories installed in the right-side compartment of breaker.

  1. AX Auxiliary Switch

Modelo: HACHA-03SVU

Función: Reports ON/OFF status of main contacts, cannot distinguish manual opening or fault tripping

Calificación de contacto: 1a1b (1NO +1NC)

Solicitud: Send breaker position signal to PLC / lámparas indicadoras

Alambrado: Lead wire type; SLT version available with terminal block

  1. AL Alarm Switch

Modelo: Alabama-03SVU

Función: Activates ONLY when tripped by fault (sobrecarga, cortocircuito, fuga a tierra); no action during manual opening

Calificación de contacto: 1a1b

Solicitud: Fault trip alarm, SCADA signal upload, audible & alarma visual

Combined module: ALAX-03SVU = integrated AX+AL module (provides both position feedback and fault trip signal, más utilizado)

  1. SHT Shunt Trip

Voltage variants:

SHTA240-03SVU: AC100~240V AC shunt trip

SHTA440-03SVU: AC200~440V AC shunt trip

SHTD100-03SVU: DC24V DC shunt trip

Suffix U: built-in module; L = extended lead; S = special spec

Función: Remote electrical trip via control signal; used for emergency stop, fire linkage circuit cut-off

Nota importante: Short-time energized type, continuous power supply is prohibited.

  1. UVT Under Voltage Trip

Two types:

UVTN-03SVU Non-synchronous UVT: Instant trip upon voltage drop

UVTS-03SVU Synchronous UVT: Trip at voltage zero-crossing during voltage drop, for large inductive loads to reduce breaking surge

Voltage ratings: AC100/200/240/400V optional

Función: Automatic trip when main circuit voltage drops or power loss; will NOT auto-reclose after voltage recovery, manual closing required on site.

External Accessories for NV125-SV

Modelo de accesorioNombreDescripción
TC‑1SVTapa de terminalesInsulation protection for exposed terminals
LC‑1SVPadlock deviceHandle lockout, prevent accidental closing
MI‑05SV3Enclavamiento mecánicoMechanical interlock for 2 disyuntores (dual power switching)
HLF‑1SVExternal rotary handlePanel mounted operating handle, with door interlock

⚠️ Selección & Installation Restrictions (Crítico)

  1. One NV125-SV breaker can be fitted with max. one built-in accessory module only. SHT + ALAX cannot be installed together.

Option A: ALAX (posición + señal de falla)

Option B: SHT (remote tripping)

Option C: UVT (under-voltage protection)

  1. Built-in accessories occupy space on the right side of breaker. Do not mount breakers side-by-side with zero clearance when fitted with internal accessories (UVT needs extra space).
  2. Two ordering options:

Breaker pre-fitted with accessories at factory (complete unit order)

Purchase accessory modules separately and assemble on site

  1. ELCB NV125-SV supports SHT/UVT installation for fire linkage and loss-of-voltage protection; accessories are interchangeable with NF125-SV standard MCCB.

Ordering Examples

NV125-SV 3P 63A + ALAX-03SVU (with switch position & fault alarm contacts)

NV125-SV 3P 63A + SHTA240-03SVU (AC220V remote shunt trip)

Full Model List of Mitsubishi NV125-SV (WS-V ELCB)

Frame AF125, Uci=30kA / Ics=30kA @AC400V; Standard AC type leakage 100/200/500mA adjustable; 3P /4P; viaje termomagnético; dimension W90×H130×D90mm

Naming format: NV125-SV [3P/4P] [Rated Current A]

✅ Rated Current Range (En)

16A, 20A, 25A, 32A, 40A, 50A, 63A, 75A, 80A, 100A, 125A

✅ Full Model Matrix

3PAG (3-fase, neutral not switched)

NV125-SV 3P 16A

NV125-SV 3P 20A

NV125-SV 3P 25A

NV125-SV 3P 32A

NV125-SV 3P 40A

NV125-SV 3P 50A

NV125-SV 3P 63A (target model)

NV125-SV 3P 75A

NV125-SV 3P 80A

NV125-SV 3P 100A

NV125-SV 3P 125A

4PAG (3-fase + polo neutro, neutral can be disconnected)

NV125-SV 4P 16A

NV125-SV 4P 20A

NV125-SV 4P 25A

NV125-SV 4P 32A

NV125-SV 4P 40A

NV125-SV 4P 50A

NV125-SV 4P 63A

NV125-SV 4P 75A

NV125-SV 4P 80A

NV125-SV 4P 100A

NV125-SV 4P 125A

Derived variants on same WS-V platform

NV125-CV: Versión económica, Icu=10kA @AC400V

NV125-HV: Alta capacidad de rotura, Icu=50kA @AC400V

NV125-SEV/HEV: Electronic trip ELCB (electronic protection, long/short time delay available)

Suffix explanation: 1.2.500MA = 100/200/500mA adjustable leakage (standard for China market); 30mA high-speed leakage variant available for personal protection.

Cross-brand Equivalent Reference (Reference target: NV125-SV 3P 63A, CA 400 V., Icu≥30kA, adjustable leakage 100/200/500mA, termomagnético)

⚠️ Nota importante: Physical size and accessories are NOT interchangeable; only electrical equivalent. Verify cabinet cutout, wiring and accessory interface for site retrofit. Table based on 63A/3P.

MarcaModelo equivalenteParámetros claveObservaciones
Mitsubishi OriginalNV125-SV 3P 63A3P 63A, Icu=30kA@400V, AC leakage 100/200/500mA adjustable, viaje termomagnéticoReference unit, WS-V series
SchneiderEZD125E 3P 63A Vigi (módulo de fuga)3P 63A, Uci=30kA, adjustable residual currentEZD125E + separate Vigi module; split type leakage, not integrated ELCB; Dimensión diferente
SchneiderNSX100N 3P 63A VigiUci=36kA, fuga ajustableNSX higher performance, precio más alto, modular leakage
TEJIDOT2N160 3P 63A RCDUci=36kA, adjustable AC residual currentMCCB body + external RCD module, integrated solution Tmax T2N
siemens3VT8106-1AA03-0AA0 + leakage trip module3P 63A, Icu=25kA, optional leakage moduleBreaking capacity slightly lower than Mitsubishi; check short-circuit capacity
LimpioNM1LE-125S/3P 63A3P 63A, Uci=35kA, leakage 100/200/500mA adjustableMain domestic alternative, integrated ELCB, termomagnético, similar mounting size
DeliciosoCDM1LE-125/3P 63A3P 63A, Uci=35kA, multi-level adjustable leakageAlternativa doméstica, 125AF frame, fuga integrada
gente electricaRMM1LE-125/3P 63A3P 63A, Uci=35kA, fuga ajustableAlternativa doméstica económica

Key Differences for Replacement Engineering

  1. Leakage construction: Mitsubishi NV125-SV is integrated built-in leakage. Schneider NSX/EZD and ABB Tmax mostly adopt separate external leakage modules, more failure points.
  2. Capacidad de ruptura: NV125-SV Icu=30kA; Icu cannot be downgraded during replacement, risk of breaker failure under bus short-circuit.
  3. Compatibilidad de accesorios: Mitsubishi AX/AL/SHT/UVT are right-side clip-on modules; Schneider/ABB accessories are independent modules. Mitsubishi old accessories cannot be reused, new accessories must be purchased for retrofit.
  4. Selección de polos: 3P only switches 3 live conductors, neutral passes through. Select 4P if neutral protection is required.
  5. Leakage type: Above are all AC type, suitable for standard power frequency loads. For VFD-heavy systems, A/F type leakage is recommended.

Mitsubishi Legacy to WS-V Upgrade

Old NV125-SW / NV125-SVL (old WS series) → NV125-SV (WS-V)

Same outer dimension, mounting hole compatible

Higher short-circuit breaking capacity (old 25kA upgraded to 30kA)

Updated accessory model: old SW accessories incompatible with SV; must use -03SVU series (HACHA-03SVU / Alabama-03SVU)

Recommended Replacement Priority

  1. Cabinet space & accessory reuse preferred: Original Mitsubishi NV125-SV
  2. Import equivalent upgrade: ABB T2N160 / Schneider NSX100N Vigi
  3. Cost-effective domestic engineering replacement: CHNT NM1LE-125S / Delixi CDM1LE-125

NV125-SV 3P 63A Replacement Retrofit Risk Checklist

Alcance: Replace Mitsubishi NV125-SV 3P 63A (ELCB, CA 400 V., Uci=30kA, 100/200/500mA adjustable leakage) with identical model, imported equivalent (ABB/Schneider/Siemens) or domestic alternative (CHNT/Delixi/People). Used for ECN, technical briefing, incoming inspection and pre-commissioning check. ✅=Pass; ❌=Fail; ⚠️=Requires confirmation/rectification

  1. Electrical Parameter Verification (Prioridad más alta, No Icu Downgrade)
No.Check ItemRequisito / Criterion
1Corriente nominal enNew device ≥ 63A and matches circuit design; continuous load ≤0.8×In
2Pole ConsistencyOriginal 3P must use 3P; if changing to 4P for neutral switching, rework wiring & cabinet cutout
3Rated Voltage UeNew device rated voltage ≥ AC400V, compatible with system voltage
4Short-circuit Breaking Icu@AC400VNew Icu ≥ 30kA (must not be lower than original NV125-SV 30kA), risk of breaker damage under bus short-circuit
5ics (Capacidad de interrupción del servicio)≥30kA, same as Icu, allows reclose after short-circuit event
6Earth Leakage Protection Typetipo de CA (or A/F type); adjustable leakage range 100/200/500mA must be retained
7Tiempo de funcionamiento de fuga≤0,04 s (alta velocidad); separately verify for 30mA personal protection version
8Thermal-Magnetic Trip CharacteristicSobrecarga / short-circuit trip curve must match original coordination; electronic trip requires setting verification
9Short-circuit SelectivityRecheck selectivity coordination with upstream and downstream protective devices

⚠️ Red Line Rule①: Do NOT energize any replacement unit with Icu <30el. Leave panel de-energized rather than downgrade breaking capacity.

  1. Instalación Mecánica & Dimension Check
No.Check ItemRequisito / Criterion
1Mounting CutoutCompare original NV125-SV (W90×H130×D90mm) with cabinet cutout; re-cut or use adapter plate if dimension mismatch
2Tipo de montajeTH35 DIN rail or panel bolt mounting compatible with original bracket
3Espacio de cableadoIn/out terminal clearance sufficient for cable stripping and crimping (meet minimum cable bending radius)
4Phase ClearanceCreepage & air clearance between phase terminals comply with new device specification
5Disipación de calorPanel spacing meets thermal requirement; no tight side-by-side mounting with internal accessories fitted (UVT especially)
6Handle / Door CutoutDoor opening and handle projection match new device; confirm if external rotary handle needs replacement
7Torque for TerminalsTightening torque follows manufacturer manual; conductor cross-section adequate, crimping secure

⚠️ Red Line Rule②: Do not force oversized cutout or suspend breaker without proper support. Use manufacturer drawing or adapter plate.

  1. Accessory Compatibility Check (High Risk, Frequently Missed)
No.Check ItemRequisito / Criterion
1Accessory InterfaceOriginal AX-03SVU / Alabama-03SVU / SHTA/D / UVTN/S cannot be fitted to other brands; purchase new accessories matching new breaker brand
2Alarma / Position SignalRe-select equivalent ALAX accessory for new breaker and rewire secondary circuit
3Shunt Trip SHTReconfigure remote trip, verify AC/DC voltage rating
4Under Voltage Trip UVTReconfigure UVT; verify trip characteristic (synchronous / non-synchronous) against load type
5Mechanical Interlock MIDual power interlock must be matched accessory from new brand; interlocks from different brands are incompatible
6Cubierta de terminales / LockoutFit TC/LC protective accessories as per new device spec
7External Leakage Module (Import Split Type)Schneider NSX/EZD, ABB T2N use separate leakage module; confirm module installed and wired correctly

⚠️ Red Line Rule③: Do NOT reuse old Mitsubishi accessories on new breakers. Mismatched assembly causes poor contact, loss of alarm or protection function.

  1. Principal & Secondary Wiring Check
No.Check ItemRequisito / Criterion
1Cableado del circuito principalPhase sequence matches busbar, terminals fully tightened
2Neutral Handling3P version neutral passes through unswitched; rewire neutral if replaced with 4P
3Zero-sequence CT / Leakage TransformerIntegrated ELCB has built-in CT, no external CT needed; check CT cable passing direction for split leakage module
4Secondary Control WiresAX/AL contacts to PLC / indicator circuit; verify contact type (1a1b) and voltage rating
5Shunt / UVT Coil WiringSHT is short-time energized, continuous power forbidden; UVT coil voltage matches supply
6Wiring MarkingPhase labels and accessory terminal numbers clear and consistent with drawing
7Par de terminalesFollow manufacturer torque specification to avoid overheating / conexión floja

⚠️ Red Line Rule④: SHT coil is short-time energized, continuous supply burns coil. UVT will not auto-close after voltage recovery; manual closing required in commissioning procedure.

  1. Pre-commissioning Test & Aceptación
No.Check ItemRequisito / Criterion
1Prueba de aislamientoPhase-to-phase / phase-earth insulation resistance meets requirement; disconnect secondary / electronic accessories before test
2Prueba de fuga (TEST Button)Press red TEST button; breaker must trip reliably to validate leakage protection
3Leakage Threshold VerificationTest tripping at 100/200/500mA if site conditions permit
4Sobrecarga / Short-circuit SimulationVerify thermal-magnetic trip if test available; otherwise confirm factory trip characteristic
5Accessory Function TestTest ALAX alarm contact, SHT remote trip, UVT under-voltage trip one by one
6Mechanical OperationEncendido/apagado manual suave, no jamming, no missing phase
7Sin carga & Load Trial RunClose breaker under no-load first; then energize load, monitor temperature and nuisance tripping
8Earthing ContinuityEquipment and cabinet protective earth secure
9Setting Record FilingDocument new breaker rating, leakage setting and accessory configuration

⚠️ Red Line Rule⑤: Do NOT put into formal operation before passing TEST button leakage verification. ELCB without working leakage protection functions only as ordinary MCCB, no personnel protection.

  1. Inapplicable Conditions & Operaciones prohibidas
Guión / OperaciónJudgement
Frequent ON/OFF cycling⚠️ Thermal-magnetic trip not suitable for high cycle rate; use motor protector or add contactor
Heavy corrosion, polvo, condensación❌ Standard model not suitable; IP rated enclosure + anti-condensation heater required
VFD & servo heavy harmonic environment⚠️ AC type may nuisance trip; upgrade to A/F type leakage or surge-resistant model
Replace breaker with upstream live❌ Live working prohibited. Apagar, test dead, lockout-tagout (CORAZÓN) requerido
Reset immediately after leakage trip without investigation❌ Do not repeatedly reclose; troubleshoot insulation/earth fault first
Replace ELCB with standard MCCB (NF)❌ Loss of earth leakage protection, strictly prohibited
Replace with lower Icu rating❌ Not allowed