Full Model Interpretation
| Segmento de modelo | Descripción | Detalles |
| NW | Serie de productos | MasterPact NW series disyuntores de aire, for high‑current power distribution systems from 800 to 6300A |
| 32 | Frame Size | Frame size 32, rated current range 800–3200A, single pole width 115 milímetros |
| H1 | Breaking Capacity Class | H1: 65kA@440V AC (H2=100kA, H3=150kA also available) |
| F2 | Montaje & Configuration | F = Fixed mount (D = Draw‑out); 2 = Equipped with Micrologic 2.0 electronic trip unit |
| 3200A | Corriente nominal | Rated operational current 3200A (a 40 ℃), fully adjustable via electronic trip |
| Official SKU | Part Number | 48082 (3P fixed) / 48087 (4P fixed), used for procurement identification |
- Key Technical Specifications
| Artículo | Valor | Notas |
| Tensión nominal (Ui/Ue) | 1000V/690V AC 50/60Hz | Suitable for global high‑voltage power distribution systems |
| Corriente nominal (En) | 3200A | Continuous current at 40℃; adjustable range 2560–3200A |
| Capacidad de ruptura (Icu/Ics) | 65kA/65kA@440V AC | Ics=100%Icu, full breaking capacity |
| Short‑time Withstand Current (Icw) | 65kA/1s (extendable to 3s) | Complies with IEC 60947‑2 |
| Tensión nominal de resistencia al impulso (árbitro) | 12kV | High surge immunity |
| Mecánico / Electrical Endurance | 10,000 / 5,000 operaciones | At 415V In, per IEC 60947‑2 |
| Degree of Protection | IP30 (estándar) / IP55 (with CDP cover) | Basic dust protection, upgradeable |
| Dimensiones (Ancho×Alto×Profundidad) | 345×352×297mm (3P fixed) | Diseño compacto, saves panel space |
| Peso | Aprox.. 47.3kilos (3P fixed) | Optimized structure for installation & maintenance |
| Pollution Class | 3 | Suitable for industrial environments |
- Core Product Advantages
3.1 Outstanding Protection Performance
Full electronic precision protection: Micrologic 2.0E trip unit provides LI (long-time + instantáneo) protección; long-time current adjustable 0.8–1.0In
65kA high breaking capacity: Reliably clears severe short-circuit faults
Selective protection: Coordinates perfectly with downstream breakers to avoid wide-area outages
Fault diagnostics: Built-in fault memory records trip cause (sobrecarga / cortocircuito / falla a tierra)
3.2 Alta confiabilidad & Durability
Double-break arc extinguishing: Combined vacuum + air system for fast arc quenching
Robust mechanical design: Shock and vibration resistant
Strong environmental adaptability: Operating temp -5℃ to +60℃; no derating up to 2000m altitude
Long service life: Reduces replacement and maintenance frequency
3.3 Flexible Installation & Fácil mantenimiento
Multiple mounting types: Fijado (F) or draw-out (D); draw-out supports hot-swap
Diseño modular: Trip and accessories field-replaceable
Universal accessory system: Reduces spare parts inventory
Smart connectivity: Supports Modbus, EtherNet/IP for remote monitoring
3.4 Seguridad & Eco-compliance
Standard isolation function: Cumple con IEC 60947-2
Visual indication: Clear contact position and trip cause display
Locking device: Prevents unauthorized operation
Green Premium certified: RoHS compliant, free of hazardous substances
- Operating Principle
NW32H1F2-3200A uses electronic tripping + double-break arc extinguishing:
- Protección contra sobrecarga (long time delay): CTs monitor current; electronic trip calculates thermal buildup
- Protección contra cortocircuitos (instantáneo): Triggers immediately when current exceeds set threshold (typically 10–12In)
- extinción del arco: Double-break contacts separate; arc is split and extinguished rapidly
- memoria de fallos: Stores last 10 trip events for analysis
- Aplicaciones típicas
- Industrial plants: Main LV distribution, transformer secondary protection
- Commercial complexes: Main incomers for high-rise buildings, malls, hoteles
- Data centers: UPS input/output protection
- Renewable energy: Grid connection for PV and energy storage power stations
- Critical infrastructure: Airports, hospitals, metros, railways
- Marina & offshore: Main switchboard protection (class-approved version)
- Instalación & Operation Guidelines
- Environment: Dry, below 40℃; max altitude 2000m
- Alambrado: Copper/aluminum busbar or ≥185mm² cable; torque 25Nm
- Coordination: Selective coordination with downstream MCCBs
- Ajustes: Adjust Ir (0.8–1.0In) and Isd based on load
- Mantenimiento: Annual full inspection including trip test
- Series Models & Alternativas
7.1 NW32H1 Series Full Model List (3200A Frame)
| Modelo | Montaje | Trip Unit | polacos | SKU |
| NW32H1F2‑3200A | Fijado | Micrologic 2.0E | 3PAG | 48082 |
| NW32H1F2‑3200A | Fijado | Micrologic 2.0E | 4PAG | 48087 |
| NW32H1D2‑3200A | Draw‑out | Micrologic 2.0E | 3PAG | 48432 |
| NW32H1D2‑3200A | Draw‑out | Micrologic 2.0E | 4PAG | 48437 |
| NW32H1F5‑3200A | Fijado | Micrologic 5.0P | 3PAG | Custom |
7.2 Reemplazo & Upgrade Options
| Demand | Modelo recomendado | Características |
| Higher breaking | NW32H2F2‑3200A | 100el |
| Funciones avanzadas | NW32H1F5‑3200A | Earth fault + medida |
| Draw‑out type | NW32H1D2‑3200A | Hot‑swap maintenance |
| Domestic alternative | CHINT NA1‑3200X‑3200A/63kA | Cost‑effective |
| ABB equivalent | Emax 2 E2N3200‑3200A/65kA | Global service |
NW32H1F2-3200A is a flagship product of the Schneider MasterPact NW series.
With 65kA high breaking capacity, precision electronic protection, flexible installation and excellent reliability, it is the ideal choice for main incomers and bus-couplers in heavy industrial and large commercial power distribution systems.
Detailed Application Scenarios
Schneider ACB NW32H1F2-3200A
MasterPact NW series high-end air circuit breaker
3200A rated current • 65kA breaking • fixed mount • Micrologic 2.0
Designed as main incomer / bus-coupler for high-current, high-reliability core LV systems, not for final subcircuits.
- Main Distribution in Large Industrial Plants
Primary application
- LV main incomer at transformer secondary
For 2000–2500kVA transformers, continuous 3200A duty
Withstands heavy short-circuit at transformer outlet
- LV main bus-coupler
For dual-bus / dual-transformer systems, backup & auto-switching
- Main power for heavy machinery
Steel, cement, chemical, automotive, paper plants
aficionados, zapatillas, compresores, kilns, production lines
Why suitable: High current, high short-time withstand, 24/7 reliability.
- Centro de datos / Computing Center Main Distribution
- LV main incomers and UPS front-end breakers
- climatización, chilled water, precision cooling main circuits
- Bus-couplers and section breakers for IDC and modular data halls
Why suitable: No nuisance tripping, full selective coordination, long life.
- Main Distribution for Large Commercial Complexes & High-rises
- Main LV incomers for landmark offices, malls, hoteles, convention centers
- Zone main incomers for super high-rises
- Main power for parking, central AC, fire-smoke extraction systems
Why suitable: High current capacity, strong breaking, safe isolation.
- Public Transport & Critical Infrastructure
- Main LV breakers for airports, high-speed rail, metro, light rail
- Main incomers for operating rooms, UCI, radiology departments
- Main distribution for stadiums, theaters, exhibition centers
Why suitable: Highest safety level, fire-system compatible, stable in harsh environments.
- Nueva energía & Power Projects
- Grid-connection incomers for large PV and energy storage plants
- LV side of wind power box transformers, PCS front protection
- Microgrid and captive power plant grid connection
Why suitable: 690V rated, high surge immunity, strong short-time withstand.
- Mines, Metallurgy, Oil & Gas (Harsh Environments)
- Main substations in coal and metal mines
- High-harmonic, heavy-impact loads in metallurgy and refining
- Power distribution in explosive / high-pollution areas
Why suitable: Pollution class 3, vibration resistant, no derating at altitude.
- Marina & Offshore (Class-approved Version)
- Main switchboard breakers for large vessels, rigs, offshore wind platforms
- Certified by CCS, BV, DNV, LR, etc..
Why suitable: Anti-roll, anti-vibration, salt-spray resistant.
One-Sentence Positioning
NW32H1F2-3200A = High-capacity, high-reliability, high-breaking “system main gate”
Used only for:
Transformer main incomers
Main bus-couplers
Critical main power supplies
Not used for:
Small loads
Final subcircuits
Standard distribution boxes