Schneider XS4P30AB120 Inductive Proximity Sensor - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Schneider XS4P30AB120 Inductive Proximity Sensor - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

Sensor/

Schneider XS4P30AB120 Inductive Proximity Sensor

(Telemecanique OsiSense XS4) Tipo de producto: M30 Non-Flush Analogue 4–20mA Inductive Proximity Sensor ✅ Model Code Definition XS4: XS4 series inductive proximity sensor P: PBT plastic housing 30: M30 thread A: Analogue output B: Cable connection 1: fuente de alimentación CC 20: 4–20mA current output 📌 Core Technical Specifications Item Parameter Outline Cylindrical M30×1.5, longitud total 53 ...

  • Detalles del producto

(telemecanica OsiSense XS4)

Tipo de producto: M30 Non-Flush Analogue 4–20mA Sensor de proximidad inductivo

✅ Definición del código del modelo

XS4: XS4 series inductive proximity sensor

PAG: PBT plastic housing

30: hilo m30

A: Salida analógica

B: Cable connection

1: fuente de alimentación CC

20: 4–20mA current output

📌 Core Technical Specifications

ArtículoParámetro
DescribirCylindrical M30×1.5, longitud total 53 milímetros
MontajeMontaje no empotrado (flush installation not allowed)
Distancia de detección nominal Sn15 milímetros (effective linear range: 1.5 ~ 15 milímetros)
Tensión de alimentación12…24 VDC, limit range 10~38 VDC
Señal de salida4~20mA analogue current (3-cable)
Cable2 m de cable de PVC, 3×0.34 mm²
Clase de protecciónIP67
Material de la carcasaCuerpo: PBT; cara sensible: PPP
Repeat accuracy≤3% of Sr
Linearity error±2 mA
Frecuencia de conmutación≤300 Hz
Consumo de energía sin carga4 mamá
Temperatura de funcionamiento-25℃ ~ +70℃
CertificacionesCE, UL, CSA

🔌 Wiring Definition (3-cable central)

Marrón: CC+ (poder positivo)

Azul: corriente continua(poder negativo)

Negro: 4~20mA signal output → connect to PLC analogue AI current input channel

Principio de funcionamiento: The closer the metal target is to the sensor, the higher the output current (rising from 4mA to 20mA).

15 mm distance = 4 mamá; 1.5 mm distance = 20 mamá.

Used for continuous displacement feedback and closed-loop control, not just discrete on/off switching.

📎 Typical Applications

  1. Continuous position closed-loop feedback for hydraulic cylinders / pneumatic actuators (hydraulic presses, tooling clamps, cilindros de elevación)
  2. Workpiece thickness & gap measurement, material level monitoring
  3. Continuous position feedback for manipulator soft limit & deceleration control
  4. Metal workpiece distance detection on conveyor lines
  5. Foot pedal position feedback (XS4P18ABxx of the same series is widely used for XPE foot pedals)

⚠️ Notas de instalación & Cross-Model Reference

  1. Strictly use non-flush mounting. No metal close to the sensor body, otherwise the sensing range will shrink.
  2. Set the PLC AI module to 4–20mA current mode, not voltage input.
  3. Same analogue sub-series comparison:

XS4P30AB110: 0~10V voltage output

XS4P30AB120: 4~20mA current output (este modelo, mainstream type)

  1. Domestic alternative requirement: M30 non-flush, 4–20mA analogue inductive proximity sensor, Sn=15 mm, 12–24 VDC supply.

📄 Supporting Documents

Original datasheet, diagramas de cableado, and PLC AI calibration examples are available on request.

XS4P30AB120 (M30, Sn15mm, 4–20mA Analogue Inductive Sensor) Field Application Cases

Característica principal: Instalación no enrasada, metal target only, continuous distance output (1.5mm=20mA; 15mm=4mA). It is not a simple limit switch; ideal for continuous position feedback, PID closed-loop control, gap & thickness monitoring. IP67 rated for dusty, oily workshop environments.

Caso 1: Closed-loop position feedback for hydraulic / cilindros neumáticos (estaciones hidráulicas, machine tool presses, maquinaria de construcción)

condiciones de trabajo: Presses, clamping jigs, cilindros de elevación. Real-time rod position acquisition for PLC PID speed regulation, soft stop and buffer deceleration to avoid mechanical impact.

Instalación: Fix XS4P30AB120 at the cylinder tail; mount a square steel target (45×45mm standard target) on the piston rod end. Keep the sensor axially aligned with the target, and keep the working stroke within 1.5~15 mm.

Lógica de control: 4mA = 15 milímetros (fully retracted); 20mA = 1.5 milímetros (fully extended). The PLC converts current value to displacement and triggers speed reduction when reaching preset positions.

Ventajas: Lower cost than pull-wire displacement sensors, aceite & dust resistant, simple installation for short-stroke cylinder buffering control.

  1. DC 3-wire Discrete Output (P Series, PNP / NPN for PLC Digital Input)

1) Salida PNP (Positive switching)

XS4P30PB340: NO normalmente abierto, 12~24 VCC, 2cable m

XS4P30PB370: NC normalmente cerrado, 12~48VDC, 2cable m

XS4P30PC410: NA+NC (1NO+1NC), 12~24 VCC, 4-cable de alambre

XS4P30PB340D: NO normalmente abierto, conector M12

XS4P30PB370D: NC normalmente cerrado, conector M12

2) Salida NPN (Negative switching)

XS4P30NB340: NPN NO normally open

XS4P30NB370: NPN NC normally closed

III. 2-wire AC/DC Universal (M Series, suitable for relay circuits)

XS4P30MA230: NO normalmente abierto, 24~240 V CA/CC, 2cable m, IP68

XS4P30MB230: NC normalmente cerrado, 24~240 V CA/CC

Cable extension suffix: L1=5m, L2=10m (p.ej. XS4P30MA230L1)

  1. XS4P30AB Analogue Sub-series (Solo 2 models available)
ModeloSeñal de salidaVoltaje de suministroSolicitud
XS4P30AB1100~10V voltaje24~48VDCPLC analogue voltage AI channel
XS4P30AB1204~20 mA de corriente12~24 VCCPLC analogue current AI channel (modelo convencional)
  1. Suffix Options for Ordering

L1: Cable extended to 5 metro

L2: Cable extended to 10 metro

D: Replace cable with M12 4-pin connector

k: Extended body (longitud total 70 milímetros)

  1. Quick Selection Guide for XS4P30 Series
  2. Displacement closed-loop, nivel de material & gap measurement → XS4P30AB120 (4–20mA)
  3. Position limit with digital switching signal → PB340 / MA230
  4. Voltage analogue signal acquisition → XS4P30AB110

✅ Original Accuracy Specifications for XS4P30AB120 (Standard steel target 45×45×1 mm, 25℃)

  1. Linearity error: ±2 mA

Full span 4~20mA (16mA total range), effective travel 1.5~15 mm (13.5 mm de carrera).

±2mA corresponds to ±1.69 mm linear deviation.

  1. Repeat accuracy: ≤3% Sr

Sr=15 mm → maximum repeat error ≤0.45 mm.

Significado: Readout fluctuation will not exceed 0.45 mm when repeatedly positioning at the same spot.

  1. Deriva de temperatura (output current drift): máx. 10% FS (escala completa) across -25~+70℃

Range note: Linear performance and accuracy are only guaranteed within the effective working range of 1.5 milímetros (20mamá) ~ 15 milímetros (4mamá).

📌 Plain Summary

Excellent repeatability: aprox. 0.45 milímetros, suitable for repeated positioning control.

Moderate linear deviation: ±1.7 mm, not for micron-level precision measurement; it is an industrial coarse-range analogue proximity sensor.

Additional A/D conversion error will be introduced by the PLC AI module, further reducing overall system accuracy.

⚠️ Key Factors Affecting Measurement Accuracy

Target material must be mild steel; stainless steel or aluminium will change sensitivity and increase error.

Strict non-flush mounting; no surrounding metal interference.

Strong welding electromagnetic interference, vibration and wide temperature swings will aggravate drift.

Anterior:

Deja una respuesta

Dejar un mensaje