Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

 Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

cortacircuitos/

Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker

Nombre completo del producto: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector) 3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15 Model Decoding 3RV6 0 11-1 Automóvil club británico 15 3RV6: SIRIUS domestic motor protection circuit-breaker 0: Motor protection application 11: Frame size S00 (Width 45 mm) 1: Standard breaking capacity AA: Thermal overload setting ...

  • Detalles del producto

Nombre completo del producto: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector)

3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15

Decodificación de modelos

3RV6 0 11-1 Automóvil club británico 15

3RV6: SIRIUS domestic motor protection circuit-breaker

0: Motor protection application

11: Frame size S00 (Width 45 mm)

1: Capacidad de ruptura estándar

Automóvil club británico: Thermal overload setting range 1.1-1.6 A

15: Built-in side auxiliary contacts 1NO+1NC (10 = without auxiliary contacts)

Parámetros técnicos básicos

ArtículoEspecificación
Thermal overload setting (A)1.1 … 1.6 A
Short‑circuit release N‑release21 A (13×En)
clase de viajeCLASS 10 (Normal motor starting)
Polos del circuito principal3PAG
Tensión operativa nominalAC‑690 V
Rated motor power @400V0.55 kilovatios
Breaking capacity Icu@400V100 ka
TerminaciónTerminales de tornillo
Contactos auxiliaresIntegrated side‑mounted 1NO + 1NC
Montaje35 mm DIN‑rail, o montaje con tornillos
Dimensiones generalesW45 mm × H97 mm × D91 mm
Grado de protecciónIP20 (Front side)
Temperatura de funcionamiento‑20 … +60 ℃
HS customs code85362010

Realizar pedidos & Reemplazos

  1. Imported OEM replacement: 3RV2011-1AA15 (identical functions and specifications, made in Germany)
  2. Version without auxiliary contacts: 3RV6011-1AA10
  3. Domestic 3RV6 and imported 3RV2 are fully interchangeable with identical mounting dimensions and wiring.

Aplicaciones típicas

Protection for small-size three-phase motors, proporcionando sobrecarga, short-circuit and phase-failure protection. Widely used in control cabinets, fans, pumps and small conveyors. Can be combined with contactors to form a motor starting unit.

Accesorios compatibles (S00 frame size)

Side-mount auxiliary contacts: 3RV6901-1A

Side-mount auxiliary contacts: 3RV6901-1E (already integrated in this model)

Liberación de subtensión, liberación de derivación, rotary operating handle and other expandable accessories.

Escenarios de aplicación de siemens 3RV6011-1AA15

Configuración actual: 1.1-1.6A, compatible with 0.55kW three-phase motor at 400V, Class 10 trip characteristic, built-in 1NO+1NC auxiliary contacts, S00 frame size (45 mm width). Proporciona sobrecarga, short-circuit and phase-failure protection. Auxiliary contacts can be used for fault alarm and PLC signal feedback.

  1. Typical Motor Load Applications
  2. Pequeños fans & cooling fan motors

Equipment cooling fans, cabinet ventilation fans, small HVAC fans. Continuous-run loads with moderate starting current. Offers phase-loss and overload protection; auxiliary contacts transmit fan fault signals.

  1. Miniature water pumps & bombas de circulación

Small process circulation pumps, bombas de agua de refrigeración, laboratory pumps. Rapid thermal tripping upon pump stalling to prevent motor burnout.

  1. Small conveying & drive equipment

Mini belt conveyors, small rollers, feeding mechanisms, compact conveyor drives. For standard direct-on-line (DOL) a partir de. Combined with 3RT7 contactors for complete motor starter assemblies.

  1. Machine-tool auxiliary drive motors

Machine-tool coolant pumps, bombas de lubricación, small feed auxiliary motors. Compact cabinet installation; fault signals sent to PLC for equipment alarm.

  1. Small actuators for packaging & maquinaria de impresión

0.55 kW three-phase drive motors for compact packaging machines, labellers and printing auxiliary equipment.

  1. Non-motor & System-level Applications
  2. Protection for small three-phase control transformers

Overload and short-circuit protection for low-inrush small-size transformers. Not suitable for transformers with high magnetizing inrush current.

Nota: Use 3RV64 series for transformers with heavy inrush to avoid nuisance tripping.

  1. Compact motor feeder circuits inside control cabinets

High-density DIN-rail layout for multi-loop small-motor cabinets. Built-in 1NO+1NC eliminates extra auxiliary contact modules; outputs trip/closed status signals to PLC and HMI.

  1. Motor protection inside standalone machines

Integrated protection for built-in machine motors. Can also serve as an isolating switch for maintenance.

  1. Industry Sectors

Automatización industrial: Custom special-purpose machinery, test equipment

climatización: Unit internal small fans and circulation pumps

Máquinas herramienta: Coolant and lubrication pump motors

Manipulación de materiales: Mini conveying mechanisms

Laboratorio & test equipment: Small three-phase drive assemblies

Compact control cabinets & OEM export equipment (Domestic 3RV6, cross-compatible with imported 3RV2011-1AA15)

  1. Recommended System Configurations
  2. Direct-on-line (DOL) starter: 3RV6011-1AA15 + 3RT7 contactor. Complete motor protection-starter unit. 3RA1931 bus module enables fast assembly without inter-wiring, ahorrando espacio en el gabinete.
  3. Signal feedback configuration: Contacto NC para alarma de fallo; NO contact for closed-state feedback, connected to PLC digital input modules.
  4. Non-applicable Conditions
  5. Frequent heavy-duty starting and high-shock loads (incompatible with Class 10 trip characteristic)
  6. Motors with rated current outside 1.1-1.6 A range
  7. Transformers with high magnetizing inrush risk of unwanted tripping
  8. Outdoor environments with heavy dust or corrosive atmosphere (requires additional protective enclosure)

Rated Operational Voltage of 3RV6011-1AA15

Main-circuit rated operational voltage Ue: AC-690V (50-60 Hz)

Especificaciones detalladas

  1. Common operating voltages for motors

CA 400 V.: Standard three-phase motor operating condition, matches 0.55 kW motor

CA 230 V. / AC500V / AC690V are permissible. Breaking capacity remains 100 kA at 690 V.

  1. Rated voltage for auxiliary contacts (1NO+1NC)

AC-15: máx.. 230 V; DC-13: máx.. 60 V

⚠️ Auxiliary contacts shall not be connected to 690 V main circuits. Reserved for low-voltage signal circuits only.

  1. Tensión nominal soportada al impulso Uimp: 6 kV

Standards reference: IEC 60947-2, IEC 60947-4-1. Domestic 3RV6 and imported 3RV2011-1AA15 share identical voltage ratings.

Overall Dimensions of Siemens 3RV6011-1AA15 (S00 Frame Size)

ArtículoValor
Ancho W45 milímetros (DIN‑rail footprint width in cabinet)
Altura H97 milímetros
Profundidad D91 milímetros (Body depth, protrusion depth after DIN‑rail mounting)
Tamaño del marcoS00
Peso netoAprox.. 0.29 kilos

Instrucciones de montaje

  1. Mounting options: 35 mm DIN-rail snap-on mounting, or base-plate screw fastening
  2. Orientación de montaje: Any mounting position is allowed
  3. Clearance requirements:

Vertical clearance: ≥50 mm

Lateral clearance: ≥30 mm

Rear clearance: 0 milímetros (flush against DIN-rail)

Imported replacement 3RV2011-1AA15 has identical dimensions for direct drop-in replacement.

Anterior:

Deja una respuesta