Nombre completo del producto: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector)
3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15
Decodificación de modelos
3RV6 0 11-1 Automóvil club británico 15
3RV6: SIRIUS domestic motor protection circuit-breaker
0: Motor protection application
11: Frame size S00 (Width 45 mm)
1: Capacidad de ruptura estándar
Automóvil club británico: Thermal overload setting range 1.1-1.6 A
15: Built-in side auxiliary contacts 1NO+1NC (10 = without auxiliary contacts)
Parámetros técnicos básicos
| Artículo | Especificación |
| Thermal overload setting (A) | 1.1 … 1.6 A |
| Short‑circuit release N‑release | 21 A (13×En) |
| clase de viaje | CLASS 10 (Normal motor starting) |
| Polos del circuito principal | 3PAG |
| Tensión operativa nominal | AC‑690 V |
| Rated motor power @400V | 0.55 kilovatios |
| Breaking capacity Icu@400V | 100 ka |
| Terminación | Terminales de tornillo |
| Contactos auxiliares | Integrated side‑mounted 1NO + 1NC |
| Montaje | 35 mm DIN‑rail, o montaje con tornillos |
| Dimensiones generales | W45 mm × H97 mm × D91 mm |
| Grado de protección | IP20 (Front side) |
| Temperatura de funcionamiento | ‑20 … +60 ℃ |
| HS customs code | 85362010 |
Realizar pedidos & Reemplazos
- Imported OEM replacement: 3RV2011-1AA15 (identical functions and specifications, made in Germany)
- Version without auxiliary contacts: 3RV6011-1AA10
- Domestic 3RV6 and imported 3RV2 are fully interchangeable with identical mounting dimensions and wiring.
Aplicaciones típicas
Protection for small-size three-phase motors, proporcionando sobrecarga, short-circuit and phase-failure protection. Widely used in control cabinets, fans, pumps and small conveyors. Can be combined with contactors to form a motor starting unit.
Accesorios compatibles (S00 frame size)
Side-mount auxiliary contacts: 3RV6901-1A
Side-mount auxiliary contacts: 3RV6901-1E (already integrated in this model)
Liberación de subtensión, liberación de derivación, rotary operating handle and other expandable accessories.
Escenarios de aplicación de siemens 3RV6011-1AA15
Configuración actual: 1.1-1.6A, compatible with 0.55kW three-phase motor at 400V, Class 10 trip characteristic, built-in 1NO+1NC auxiliary contacts, S00 frame size (45 mm width). Proporciona sobrecarga, short-circuit and phase-failure protection. Auxiliary contacts can be used for fault alarm and PLC signal feedback.
- Typical Motor Load Applications
- Pequeños fans & cooling fan motors
Equipment cooling fans, cabinet ventilation fans, small HVAC fans. Continuous-run loads with moderate starting current. Offers phase-loss and overload protection; auxiliary contacts transmit fan fault signals.
- Miniature water pumps & bombas de circulación
Small process circulation pumps, bombas de agua de refrigeración, laboratory pumps. Rapid thermal tripping upon pump stalling to prevent motor burnout.
- Small conveying & drive equipment
Mini belt conveyors, small rollers, feeding mechanisms, compact conveyor drives. For standard direct-on-line (DOL) a partir de. Combined with 3RT7 contactors for complete motor starter assemblies.
- Machine-tool auxiliary drive motors
Machine-tool coolant pumps, bombas de lubricación, small feed auxiliary motors. Compact cabinet installation; fault signals sent to PLC for equipment alarm.
- Small actuators for packaging & maquinaria de impresión
0.55 kW three-phase drive motors for compact packaging machines, labellers and printing auxiliary equipment.
- Non-motor & System-level Applications
- Protection for small three-phase control transformers
Overload and short-circuit protection for low-inrush small-size transformers. Not suitable for transformers with high magnetizing inrush current.
Nota: Use 3RV64 series for transformers with heavy inrush to avoid nuisance tripping.
- Compact motor feeder circuits inside control cabinets
High-density DIN-rail layout for multi-loop small-motor cabinets. Built-in 1NO+1NC eliminates extra auxiliary contact modules; outputs trip/closed status signals to PLC and HMI.
- Motor protection inside standalone machines
Integrated protection for built-in machine motors. Can also serve as an isolating switch for maintenance.
- Industry Sectors
Automatización industrial: Custom special-purpose machinery, test equipment
climatización: Unit internal small fans and circulation pumps
Máquinas herramienta: Coolant and lubrication pump motors
Manipulación de materiales: Mini conveying mechanisms
Laboratorio & test equipment: Small three-phase drive assemblies
Compact control cabinets & OEM export equipment (Domestic 3RV6, cross-compatible with imported 3RV2011-1AA15)
- Recommended System Configurations
- Direct-on-line (DOL) starter: 3RV6011-1AA15 + 3RT7 contactor. Complete motor protection-starter unit. 3RA1931 bus module enables fast assembly without inter-wiring, ahorrando espacio en el gabinete.
- Signal feedback configuration: Contacto NC para alarma de fallo; NO contact for closed-state feedback, connected to PLC digital input modules.
- Non-applicable Conditions
- Frequent heavy-duty starting and high-shock loads (incompatible with Class 10 trip characteristic)
- Motors with rated current outside 1.1-1.6 A range
- Transformers with high magnetizing inrush risk of unwanted tripping
- Outdoor environments with heavy dust or corrosive atmosphere (requires additional protective enclosure)
Rated Operational Voltage of 3RV6011-1AA15
Main-circuit rated operational voltage Ue: AC-690V (50-60 Hz)
Especificaciones detalladas
- Common operating voltages for motors
CA 400 V.: Standard three-phase motor operating condition, matches 0.55 kW motor
CA 230 V. / AC500V / AC690V are permissible. Breaking capacity remains 100 kA at 690 V.
- Rated voltage for auxiliary contacts (1NO+1NC)
AC-15: máx.. 230 V; DC-13: máx.. 60 V
⚠️ Auxiliary contacts shall not be connected to 690 V main circuits. Reserved for low-voltage signal circuits only.
- Tensión nominal soportada al impulso Uimp: 6 kV
Standards reference: IEC 60947-2, IEC 60947-4-1. Domestic 3RV6 and imported 3RV2011-1AA15 share identical voltage ratings.
Overall Dimensions of Siemens 3RV6011-1AA15 (S00 Frame Size)
| Artículo | Valor |
| Ancho W | 45 milímetros (DIN‑rail footprint width in cabinet) |
| Altura H | 97 milímetros |
| Profundidad D | 91 milímetros (Body depth, protrusion depth after DIN‑rail mounting) |
| Tamaño del marco | S00 |
| Peso neto | Aprox.. 0.29 kilos |
Instrucciones de montaje
- Mounting options: 35 mm DIN-rail snap-on mounting, or base-plate screw fastening
- Orientación de montaje: Any mounting position is allowed
- Clearance requirements:
Vertical clearance: ≥50 mm
Lateral clearance: ≥30 mm
Rear clearance: 0 milímetros (flush against DIN-rail)
Imported replacement 3RV2011-1AA15 has identical dimensions for direct drop-in replacement.