Producto: 3TL61 series 7.2 kV medium-voltage vacuum contactor (legacy imported unit, interrumpido)
3TL61: 7.2 kV voltage class; 3TL65: 12 kV voltage class. The 3TL platform is an older-generation vacuum contactor manufactured in Berlin. Its successor series is the 3TM.
Decodificación de modelos: 3TL6113-0BM4
3TL61: 7.2 kV vacuum contactor base series
13: 3-polo, rated operating current 250 A
0: Versión estándar, no mechanical latching
B: Coil control voltage AC 24 V
M4: Configuración de contactos auxiliares: 4NO + 4NC positively-driven auxiliary switch
Especificaciones eléctricas clave
| Artículo | Parámetro |
| Rated operating voltage Ue | 7.2 kV |
| Rated operating current Ie | 250 A |
| Número de polos | 3-polo |
| Frecuencia | 50-60Hz |
| voltaje de la bobina | AC 24 V |
| Closing power | 600 W., holding power 90 W (with economy holding resistor) |
| Resistencia mecánica | 3 million operations |
| Vacuum interrupter electrical endurance | 2 million operations |
| Frecuencia máxima de funcionamiento | 1200 operaciones por hora |
| Contactos auxiliares | 4NO + 4CAROLINA DEL NORTE, positively‑driven |
| Power‑frequency withstand voltage (phase‑to‑ground / fase a fase) | 32 kV, 1 min |
| Tensión soportada al impulso del rayo | 60 kV |
Aplicaciones típicas
Switching of high-voltage motors, bancos de capacitores, transformers and reactors; contactor-fuse combination (FC-circuit) inside KYN28, XGN switchgear cubicles.
Opciones de reemplazo
- siemens original successor: 3TM3313-0BB40
(7.2 kV-250 A, AC 24 V coil, 4NO+4NC auxiliary contacts, functional drop-in replacement. Cabinet cut-out dimensions require verification.)
- Spare part order numbers:
Interrumpiendo el vacío: 3TY5652-0AA00
Operating coil: 3TY5651-0AB00
Economy holding resistor: 3TY5664-0AA00
Notas de mantenimiento
When procuring spare parts for legacy units, always verify the complete type designation plus serial number from the nameplate; do not rely solely on the order number.
The 3TL61 series uses an economy holding resistor for the coil. Do not remove it during servicing.
Main-circuit resistance shall be ≤ 280 μΩ; measurement is mandatory during overhaul.
The auxiliary switch is positively-driven. Do not substitute with standard auxiliary contacts.