Proximiteur/moniteur sismique Bently Nevada 3500/42M-A09-B00 (Module d'acquisition de données dynamiques)
Marque: Courbé Nevada (Boulanger Hughes), part of the 3500 Series TSI Machinery Protection System. Official Name: Proximitor/Seismic Monitor. Base Order Part Number: 143694-01. It is a 4-channel programmable card supporting both protection alarming and dynamic waveform acquisition, serving as the core monitoring card for steam turbine units.
- Explication du code modèle: 3500/42M-A09-B00
3500: 3500 TSI Machinery Protection System
/42M.: 4-channel Proximitor/Seismic Monitor card. Le suffixe “M.” means dynamic waveform acquisition is supported. The legacy 3500/42 does not support dynamic data acquisition.
A09: Segment A = Sensor Input Option. 09 = Supports both Proximitor (Eddy Current) and Seismic sensors (velocity / accélération).
B00: Segment B = Certification Option. 00 = Without CSA NRTL/C certification; B01 is the version with CSA certification.
Notes de distinction
A01: Eddy current input only; A02: Seismic sensor input only; A09 hybrid type can connect to 3300XL eddy current probes for shaft vibration / axial displacement measurement, and also piezoelectric velocity sensors for bearing housing vibration measurement.
3500/40M.: Speed and keyphase only; 3500/45: Temperature card; 3500/42M is the primary monitoring card for vibration and displacement.
- Spécifications techniques de base
| Article | Spécification |
| Nombre de canaux | 4 chaînes indépendantes. Channels are configured in pairs (1&2 as one group, 3&4 as another group). Each group can be set for one measurement type. |
| Sensor Input (A09) | Eddy current Proximitor (3300XL series) + Seismic sensors (velocity / accélération) |
| Measurable Parameters | Radial shaft vibration, axial thrust displacement, differential expansion, eccentricity, REBAM, bearing housing velocity/acceleration, shaft absolute vibration, CAA (Circular Acceptance Area) |
| Signal Frequency Range | Courant de Foucault: 10Hz~10kHz; Seismic:1Hz~10kHz |
| Static Measurement Accuracy | ±0,5 % PE; Dynamic waveform acquisition for System1 spectrum analysis |
| Alarm Configuration | Alert warning available per channel; Each group supports 2 Danger trip setpoints to drive hardwired protection relays via 3500/33 carte |
| Température de fonctionnement | -30℃ ~ +65℃ (à l'intérieur du meuble) |
| Consommation d'énergie | Max 10W, powered by rack backplane |
| Indicateurs | D'ACCORD, TX/RX backplane communication LEDs, independent status LED for each of 4 chaînes |
| SIL | The complete system meets SIL2 (subject to full loop assessment); Compliant with API670 machinery protection standard |
| Installation | Full-height card, fits any monitoring slot in 3500 étagère; hot-swappable (interlock must be removed before operation) |
III. Fonctions principales
- Paired channel configuration: Channels 1&2 can be configured for shaft vibration while channels 3&4 for bearing housing vibration. The same card can mix eddy current and seismic sensors.
- Static protection measurement: Calculate vibration amplitude and displacement values in real time, compare with setpoints to trigger Alert / Danger alarms, and send signals to 3500/33 relay card for hardwired unit trip protection.
- Dynamic waveform acquisition (core feature of M version): Capture raw vibration waveforms, 1X/2X amplitude and phase, upload to System1 for spectrum and orbit analysis to diagnose faults such as rotor unbalance, misalignment and rub.
- Sensor self-diagnosis: Detect probe open circuit, short circuit and excessive gap deviation; sensor faults are directly logged into rack event history.
- REBAM® Bearing Condition Monitoring: Bently patented algorithm to evaluate bearing oil film stability.
- Journalisation des événements: Alarms and sensor faults are recorded with timestamps, which can be uploaded to DCS through 3500/92 communication gateway card.
- Scénarios d'application typiques
Steam turbines, centrifugal compressors, axial fans, gros moteurs; TSI systems in thermal power, coal chemical and oil & gas refining industries.
Eddy current channels: Rotor radial vibration, axial displacement, differential expansion
Seismic channels: Bearing housing casing vibration (velocity / accélération)
- Installation & Directives de configuration
- Câblage: Eddy current probe extension cable + proximitor. Cable length must be matched (3300XL system uses fixed-length cables, must not be arbitrarily cut). Seismic sensor shielded cable with single-point grounding.
- Configuration Procedure
Connect rack via Rack Configuration software and add 3500/42M card.
Channel grouping: Set channel1/2 to eddy current radial vibration; channel3/4 to seismic velocity.
Set sensor sensitivity, measurement range, Alert warning value and Danger trip setpoint.
Enable dynamic acquisition and configure waveform sampling parameters.
Download configuration to rack; confirm channel OK LED steady on, perform probe gap verification and simulate alarms to test relay operation.
- Mise en service: Verify eddy current probe gap voltage (around -10V DC); calibrate seismic sensor sensitivity.
- Common Troubleshooting Checklist
- OK LED flashing: Manquant / invalid card configuration, re-download rack configuration.
- Channel reports sensor fault: Abnormal proximitor power supply, open/short circuit of cable, worn probe or out-of-range gap; check gap voltage output from proximitor.
- Fluctuating vibration readings: Multi-point grounding of proximitor shield, cable routed near power cables causing interference; loose probe mounting.
- Normal static value but no dynamic waveform in System1: Dynamic acquisition not enabled in configuration, or missing 3500/22M transient interface module.
- Danger alarm fails to trigger relay: Verify alarm voting logic and configuration mapping between 3500/33 relay card.
VII. Comparaison des séries & Sélection du modèle
| Modèle | Type d'entrée | Dynamic Acquisition | Attestation |
| 3500/42M-A09-B00 | Hybrid Eddy Current + Seismic | Soutenu | No CSA |
| 3500/42M-A09-B01 | Hybrid Eddy Current + Seismic | Soutenu | With CSA |
| 3500/42M-A01-B00 | Eddy Current Only | Soutenu | No CSA |
| 3500/42-A01-B00 | Eddy Current Only | No dynamic acquisition | No CSA (héritage, progressivement éliminé) |
Metrix ST5484E-123-434-22 Seismic Velocity Vibration Transmitter
Marque: Metrix (USA). ST5484E is an integrated 2-wire loop-powered velocity vibration transmitter. It adopts built-in piezoelectric accelerometer core, integrating circuit and true RMS processing, directly outputs 4–20mA signal for bearing housing casing vibration monitoring. Different from Bently eddy current probes which measure shaft vibration.
- Explication du code modèle: ST5484E-123-434-22
Model format: ST5484E AAA BBCC EF
123: Range code, 2.0 in/s (50.8 mm/s RMS), 4mA=0; 20mA=full scale 50.8mm/s
434: Filtre, mounting thread, housing material
4: Filter option
3: Mounting thread 1/4-28 UNF stud mounting
4: 316 stainless steel housing
22: Connexion électrique + certification antidéflagrante
2: 2-terminal block wiring
2: Ex ia IIC T4 intrinsically safe version
Notes de distinction
ST5484E: Casing vibration velocity transmitter; ST5491E with local display; SW5484E with built-in relay vibration switch.
- Spécifications techniques de base
| Article | Spécification |
| Principe de mesure | Piezoelectric acceleration + intégration, outputs vibration velocity RMS value |
| Plage de mesure | 0~2.0 in/s (0~50.8 mm/s RMS) |
| Signal de sortie | 2-wire 4–20mA, loop powered; Metrix patented IPT non-polar wiring |
| Tension d'alimentation | 11~29.6 VDC (24VDC recommandé) |
| Réponse en fréquence | 2Hz ~ 1kHz, suitable for casing vibration monitoring of pumps, les fans, motors and compressors |
| Matériau du boîtier | 316 acier inoxydable |
| Installation | 1/4-28 UNF stud, directly fastened onto bearing housing surface |
| Explosion-proof Rating | ATEX/IECEx Ex ia IIC T4 Ga (intrinsèquement sûr, safety barrier required) |
| Protection contre la pénétration | IP67 |
| Température de fonctionnement | -40℃ ~ +85℃ |
| Isolement | 500Vrms isolation between loop and housing |
| Poids | Environ. 170g |
| Caractéristiques | Factory calibrated, no zero/range potentiometer for field adjustment; 4-wire version optional with raw acceleration dynamic output |
III. Fonctions principales
- Integrated RMS processing: Built-in integration and true RMS circuit, directly output 4-20mA proportional to vibration velocity. Can be connected to DCS/PLC directly without extra proximitor.
- IPT non-polar loop: Wiring without positive/negative polarity distinction to reduce field wiring errors.
- Intrinsically safe explosion protection: Zone 0 intrinsèquement sûr, applicable for hazardous areas in chemical and petrochemical industries.
- Optional narrowband filter to suppress high-frequency interference, fit for rolling bearing equipment monitoring.
- Single-direction measurement: Measures along sensor axial direction; align monitoring direction (horizontal / verticale) during installation.
- Scénarios d'application typiques
Bearing housing casing vibration monitoring for centrifugal pumps, les fans, moteurs, gearboxes and small compressors; pétrochimique, coal chemical and power plants.
>Comparison with Bently 3500/42M: ST5484E outputs standard 4-20mA to DCS and cannot provide raw dynamic waveform for spectrum analysis. Bently 42M can capture raw waveforms for fault diagnosis.
- Installation & Directives de mise en service
- Installation: Stud must be tightened on flat metal surface of bearing housing, polish and remove rust on contact surface. Sensor axial direction must align with measured vibration direction. Avoid installation on thin wall or stiffener (resonance interference).
- Câblage: 2-wire intrinsically safe loop, intrinsically safe safety barrier is mandatory. Shielded cable single-point grounding; do not route together with power cables in the same cable tray.
- Loop calculation: Maximum allowable loop resistance depends on supply voltage. Max loop resistance ≈650Ω under 24VDC supply.
- Étalonnage: Full-unit calibration on vibration shaker table. No zero or span adjustment knobs inside sensor; range cannot be modified on site.
- Configuration: Set in DCS: 4mA=0 mm/s, 20mA=50.8 mm/s, configure high vibration alarm and high-high interlock setpoints.
- Common Troubleshooting Checklist
- Fixed 4mA output: Broken loop, faulty safety barrier, loss of sensor power supply; damaged internal sensing element.
- Fixed 20mA output: Short circuit in loop, damaged internal circuit of sensor, vibration exceeds full scale.
- Fluctuating readings: Montage lâche, resonance on contact surface; multi-point grounding of shield; cable interference from inverter power lines.
- Low vibration readings: Wrong installation direction; paint/gasket on contact surface leading to weakened vibration transmission.
VII. Comparaison des séries & Sélection du modèle
| Modèle | Gamme | Câblage | Antidéflagrant | Dynamic Output |
| ST5484E-123-434-22 | 50.8mm/s RMS | 2-core terminal | Intrinsically safe Ex ia | Non (4-20mA only) |
| ST5484E-124 | 125mm/s | Fil de plomb | Facultatif | Non |
| ST5484E 4-wire version | On demand | 4-cœur | Facultatif | With raw acceleration dynamic signal |
| ST5491E | Same as ST5484E | Facultatif | Facultatif | With local digital display |
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur