Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

Fuji Electric SC‑E4 contactor - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

contacteur/

Fuji Electric SC‑E4 contactor

Fuji Electric SC‑E4 (including SC‑E4/G DC type) 3‑pole electromagnetic contactor. This is a main model in the SC‑E series with an 80A frame, used for industrial motor control. Key Rated Parameters Motor Power (AC‑3): 22kW at 200–240V; 40kW at 380–440V Rated Operational Current: 80UN (AC‑3); 105A for resistive load (AC‑1) Operation Type: AC operation SC‑E4; ...

  • Détails du produit

Fuji Electric SC‑E4 (including SC‑E4/G DC type) 3‑pole electromagnetic contactor. This is a main model in the SC‑E series with an 80A frame, used for industrial motor control.

Key Rated Parameters

  1. Motor Power (AC‑3): 22kW at 200–240V; 40kW at 380–440V
  2. Rated Operational Current: 80UN (AC‑3); 105A for resistive load (AC‑1)
  3. Operation Type: AC operation SC‑E4; DC coil SC‑E4/G (par exemple. DC24V, DC110V)
  4. Montage: 35mm rail DIN / screw fixing; dimensions 67×130×112 mm; weight approx. 1.4 kg
  5. Certifications: Compliant with IEC, UL, ASC; marked with CE; finger‑safe terminals for electric shock protection

Structure & Caractéristiques

3‑pole main circuit, standard without auxiliary contacts (auxiliary modules such as SZ‑AS1T can be side‑mounted to expand 1a1b / 2un / 2b)

Direct‑connect main terminal design for easier wiring; safety structure to prevent exposed live parts

Coil options: AC110V, AC220V, AC380V, DC24V, DC110V; DC type (/G) suitable for unstable grids or DC control circuits

Compatible thermal overload relay: TK‑E3 series, for overload, locked‑rotor, and phase‑failure protection

Ambient temperature: -5℃ to +55℃ (non‑condensing); altitude ≤ 2000 m

Applications typiques & Notes de sélection

  1. For direct starting, star‑delta starting, and soft‑starting of 40kW (380–440V) / 22kW (200–240V) three‑phase asynchronous motors
  2. Selection must confirm: coil voltage, number of auxiliary contacts, control circuit voltage, courant nominal, duty category (AC‑3/AC‑1), and whether surge suppressors are required
  3. Comparable competitive models: Schneider LC1‑D80, ABB A145‑30‑11, Siemens 3RT2036

Model Example & Replacement

Model designation: SC‑E4 AC220V (AC coil); SC‑E4/G DC24V (DC coil)

Replacement notes: Coil voltage, courant nominal, mounting dimensions, and auxiliary contact configuration must match; DC coils cannot directly replace AC coils

Installation & Conseils d'entretien

  1. Install vertically; avoid dusty, oily, or corrosive environments
  2. Use crimped terminals for main circuit cables; follow torque specifications in the manual; control circuit wires ≤ 2.5 mm²
  3. Regularly inspect contact erosion, loose wiring, and abnormal odors from the coil; replace main contacts or the entire contactor if necessary
  4. Connect RC circuits or varistors in parallel to suppress coil surge and protect PLC output points

Cross‑Brand Model Cross‑Reference & Replacement Guide for Fuji SC‑E4

The following cross‑reference is based on the core parameters of the Fuji SC‑E4, categorized into international first‑tier brands, Japanese/Korean equivalent brands, and mainstream domestic brands.

Two types are distinguished:

Performance‑matched (fully matching parameters, universal function)

et

Direct interchangeable (compatible mounting dimensions and terminal positions, replaceable without cabinet modification).

  1. International First‑Tier Brands
MarqueEquivalent Model (CA/CC)AC‑3 Rated CurrentMotor Power at 380VWidthReplacement Notes
SchneiderCA: LC1D8080UN40kW70mmTop performance match, full parameter match; AC‑3/AC‑1 ratings identical to SC‑E4; mounting holes compatible; Chinese version includes 1NO+1NC aux contacts; global availability.
Economy: LC1N80
CC: LP1D80
ABBCA: A95‑30‑11 / AF80‑30‑0080UN40kW70mmPerformance‑matched; AF series supports wide AC/DC coils, strong voltage fluctuation resistance; excellent arc interruption; suitable for heavy‑duty applications.
CC: AF80‑30‑00 (wide voltage DC)
SiemensCA: 3RT203880UN37kW/40kW62mmCompact S2 frame; full 80A AC‑3 match; built‑in 1NO+1NC aux contacts; compatible with 3RU2 thermal relays; logic matches SC‑E4 + TK‑E3.
CC: 3RT2038 (DC coil suffix)
Eaton MoellerCA: DILM8080UN37kW/40kW69mmPerformance‑matched; mechanical and electrical life equivalent to Fuji; direct‑mount thermal relay compatible; ideal for export projects and European standard cabinets.
CC: DILM80 (DC coil suffix)
  1. Japanese & Korean Equivalent Brands
MarqueEquivalent Model (CA/CC)AC‑3 Rated CurrentMotor Power at 380VWidthReplacement Notes
MitsubishiCA: S‑M80 / S‑T8080UN40kW67mmDirect interchangeable; same width, mounting holes, and terminal pitch; fully compatible auxiliary and thermal relay mounting.
CC: SD‑T80
LS Électrique (former LG)CA: GMC‑85 / MC‑85a85UN45kW82mmPerformance‑matched with extra current margin; heavy‑duty rated; includes 1NO+1NC aux contacts; widely available.
CC: GMD‑85
  1. Mainstream Domestic Brands (Cost‑Effective Replacement)
MarqueEquivalent ModelAC‑3 Rated CurrentMotor Power at 380VWidthReplacement Notes
ChintCJX2‑8011 / NC1‑801180UN40kW70mmRemplacement direct; dimensions compatible with LC1D80 and SC‑E4; built‑in 1NO+1NC aux contacts; CCC/CE certified; cost‑effective.
DélicieuxCJX2s‑8011 / CDC1‑801180UN40kW70mmUniversal replacement; full parameter match; dual rail/screw mounting; silver alloy contacts; nationwide service.
TENGENCJX2‑8011 / TGC1‑801180UN40kW70mmIndustrial‑grade replacement; improved surge & humidity resistance; adapté aux environnements difficiles; meets tendering requirements.

Key Notes for Cross‑Brand Replacement

  1. Coil specification must be 1:1 matched: AC coils (AC110V/220V/380V) and DC coils (DC24V/DC110V) cannot be interchanged. SC‑E4/G DC type can only be replaced by the same DC voltage model.
  2. Auxiliary contact logic matching: SC‑E4 has no built‑in auxiliary contacts. If the replacement model includes aux contacts, verify NO/NC logic in the PLC program to avoid malfunction.
  3. Thermal relay compatibility: Confirm rated current and mounting style after replacement; direct‑mount thermal relays must match the contactor frame.
  4. Cabinet space: Direct‑interchangeable models can be installed without modification. For performance‑matched models, verify width, hauteur, and depth to avoid door interference or busbar conflict.

Précédent: