Signification du modèle & Basic Positioning
| Partie | Signification |
| CJ | Contacteur CA (China Contactor) |
| 20 | Design No. (20th generation) |
| 160 | Rated operational current 160A (AC‑3 category) |
CHINT CJ20‑160 is a 3‑pole AC contactor, a main model in the CJ20 series, suitable for frequent operations such as motor control. Il est conforme à GB/T 14048.4 and IEC/EN 60947‑4‑1 standards.
2. Paramètres techniques de base
Performances électriques
| Article | Valeur | Remarques |
| Rated operational current (AC‑3) | 160UN | Controls motor power 85kW at 380V |
| Courant thermique conventionnel (je) | 200UN | Long‑time permissible current in free air |
| Tension d'isolement nominale (Interface utilisateur) | 690V | Maximum voltage withstand class |
| Tension de fonctionnement nominale (Ue) | Up to 660V (50/60Hz) | Main circuit voltage range |
| Tension de la bobine de commande | 110V/127V/220V/380V etc. | 220V and 380V are common |
| Consommation électrique de la bobine | Inrush 855VA, Holding 85.5VA (50Hz) | Energy‑saving versions available |
| Rated operational frequency (AC‑3) | 1200 opérations/heure | Typical for motor control |
| Making/breaking capacity | 10 × rated current (1s) | Withstands motor starting surge |
| Contacts auxiliaires | Standard 2NO+2NC (expandable) | For control circuit signaling |
| Endurance mécanique | 10 millions d'opérations | Endurance électrique (AC‑3): 1 millions d'opérations |
Mechanical Structure
Double‑break direct‑acting structure, excellente extinction d'arc
Main contacts made of silver‑based alloy, arc‑resistant and anti‑welding
Overall modular design, easy installation and maintenance
Compatible with RT16‑315 fuse protection
3. Dimensions de montage & Poids
| Article | Valeur (mm) |
| Largeur (UN) | 146 |
| Hauteur (B) | 187 |
| Profondeur (C) | 178 |
| Espacement des trous de montage | 130×130 (±0.5) |
| Diamètre du trou de montage | 9mm |
| Poids | Environ. 5.5kilos |
Montage: Standard 35mm DIN rail or bolt fixing
4. Application & Guide de sélection
Champ d'application
1. CA 50/60 Hz, power circuits up to 660V
2. Remote switching on/off, frequent control of three‑phase asynchronous motors
3. Combiné avec des relais de surcharge thermique (par ex., série NR2) into magnetic starters for overload protection
4. Typical uses: les fans, pompes, compresseurs, conveyors and other industrial equipment
Notes de sélection
Pour le contrôle du moteur, select according to AC‑3 category (160A ≈ 85kW/380V)
Coil voltage must match control circuit (commonly 220V/380V)
Auxiliary contact quantity to meet control requirements (expandable)
Consider operating frequency and environment (température, humidity, altitude)
5. International Brand Replacements
| Marque | Modèle de remplacement | Compatibilité |
| Siemens | 3RT2036‑1AP00 | Same current class, similar dimensions |
| ABB | A165‑30‑11 | 165UN, remplacement direct |
| Schneider | LC1D15000M7C | 150UN, suitable for light loads |
| Schneider | LC1D18000M7C | 180UN, adapté aux charges lourdes |
| Eaton (Moeller) | DIL M175 | 175UN, high performance match |
6. Opération & Entretien
1. Inspect integrity before installation, remove packaging
2. Ensure terminals are tightly secured to avoid overheating
3. Regularly check contact wear; replace silver alloy contacts at 1/3 thickness
4. Clean arc chute to remove carbon deposits
5. Do not use without arc chute to prevent arc short‑circuit
6. Coil voltage range: 85%–110% of rated value
7. CJ20 Series Model List
| Modèle | Courant nominal (UN) | Puissance de contrôle (kW/380V) | je (UN) |
| CJ20‑10 | 10 | 4.5 | 16 |
| CJ20‑16 | 16 | 7.5 | 25 |
| CJ20‑25 | 25 | 11 | 40 |
| CJ20‑40 | 40 | 22 | 63 |
| CJ20‑63 | 63 | 30 | 100 |
| CJ20‑100 | 100 | 55 | 140 |
| CJ20‑160 | 160 | 85 | 200 |
| CJ20‑250 | 250 | 132 | 315 |
| CJ20‑400 | 400 | 200 | 500 |
| CJ20‑630 | 630 | 315 | 800 |
The mechanical endurance of CHINT CJ20‑160 is 10 millions d'opérations, the standard design index for no‑load cycles under normal conditions.
Additional Info
1. Endurance électrique: Under AC‑3 (motor control), 1.2 million operations – lower due to arcing and contact wear
2. Series difference: CJ20‑10 ~ CJ20‑160: 10 millions d'opérations; CJ20‑250/400/630: 6 millions d'opérations
3. Life factors: Actual service life depends on frequency, environment, et entretien
CHINT CJ20 Series: Core Advantages vs Other Series
The CJ20 series is a classic CHINT contactor line with strong advantages in heavy‑duty performance, pouvoir de coupure, durability and compatibility, especially compared with CJX2, NC1 and CJ40 series.
1. Structural & Performance Advantages
1.1 Excellent Breaking & Arc Extinguishing
Double‑break direct‑acting structure; models above 40A use ceramic longitudinal or grid arc chutes, better than CJX2
Breaking capacity up to 10× rated current (1s), withstands heavy motor starting
Silver‑based alloy main contacts: low resistance, stable temperature rise
1.2 Long Mechanical & Electrical Endurance
| Série | Mechanical Endurance (160UN) | Electrical Endurance (AC‑3) | Caractéristiques |
| CJ20 | 10 million | 1 million | Full series 10M (250A+: 6M.) |
| CJX2 | 6–10M | 0.6–1M | Smaller sizes lower |
| NC1 | 6–10M | 0.6–1M | Newer, better energy saving |
1.3 Modulaire & Versatile
Independent auxiliary contacts: standard 2NO+2NC, expandable
Compatible with RT16‑315 fuses and protection modules
35mm DIN rail or bolt mounting
2. Advantages vs Other CHINT Series
2.1 vs CJX2 (Economic Type)
| Article | CJ20 | CJX2 | Application |
| Robuste | Up to 630A, 315kW | Max 95A, ~45kW | CJ20 for large industrial equipment |
| Breaking | Strong, for frequent/ reverse starting | Moyen, service normal | CJ20 for crushers, mills |
| Environnement | Robust, dust/ heat resistant | Compact, environnements propres | CJ20 for metallurgy, exploitation minière |
2.2 vs NC1 (New Energy‑Saving)
Proven stable platform: decades of field use, low failure rate, ideal for retrofit projects
AC/DC energy‑saving modules (≥63A): faible bruit
Better price in same size
2.3 vs CJ40 (High‑Performance)
Wider compatibility with thermal relays (par ex., NR2)
Simpler installation & maintenance, standard dimensions
3. Key Application Strengths
1. High‑power motors: 85kW (160UN) to 315kW (630UN)
2. Frequent starting & inversion: jusqu'à 1200 opérations/heure
3. Long‑distance control in large plants, mines
4. Harsh environments: –25°C to +40°C, poussière, vibration
Core Value of CJ20 Series
CJ20 stands out for maturity, fiabilité, heavy‑duty capability and strong breaking performance. It is the top choice for heavy industrial control. While slightly less compact or energy‑efficient than CJX2/NC1, it excels in robustness and durability for demanding traditional industry and equipment upgrades.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires










![Le NXC-65 de la série Kunlun de CHINT Electric est un contacteur CA tripolaire, évalué à 65A dans la série NXC. Le modèle complet est généralement exprimé sous la forme NXC-65 [Tension de bobine] [Fréquence] NXC-65 from the Kunlun Series by CHINT Electric is a 3-pole AC contactor, rated at 65A in the NXC series. The full model is typically expressed as NXC-65 [Coil Voltage] [Frequency]](https://www.bestcontactor.com/wp-content/uploads/2026/04/ScreenShot_2026-01-30_132315_324-419x560.png)







NH42-63-318x560.png)