FX2NC ultra-compact micro PLC (DC24V powered, sortie transistorisée, Fin de vie / abandonné; only second-hand or stock spare parts available)
Explication du code modèle
FX2NC: FX2N ultra-compact series (C = Compact)
96: Total des points d'E/S 96 points
M.: Unité principale (intégré Processeur)
T: Sortie transistorisée (Type d'évier; high-speed pulse output for servo/stepper drive)
- Core I/O Specifications
Saisir: 48 points X0~X57, Entrée d'évier DC24V
Sortir: 48 points Y0~Y57, DC24V sink transistor output
E/S totales: 96 points; maximum expanded system I/O ≤256 points, input or output single direction ≤184 points
Alimentation: DC24V, voltage range DC24V -15% ~ +20%, peak-to-peak ripple ≤5%
Mécanique: Ultra-thin pluggable terminal structure, Montage sur rail DIN; poids environ. 0.45 kilos
- Programme & Mémoire
Built-in RAM: 8K étapes (lithium battery backup)
Optional memory cards: FX2NC-EEPROM4C / 16C (with RTC real-time clock), FX2NC-EEPROM16 (pas de RTC); max program capacity 16,000 mesures
Langages de programmation: Diagramme en échelle, Diagramme des fonctions séquentielles SFC
Basic instruction execution speed: 0.08 μs per instruction
Onboard real-time clock: Nécessite une carte FX2NC-RTC ou EEPROM avec RTC
- Expansion & Communication
- Expansion: Connexion directe au FX0N / Blocs d'extension FX2NC. Pour utiliser les modules FX2N standards, L'adaptateur de conversion FX2NC-CNV-IF est obligatoire.
- Modules spéciaux: Prend en charge les E/S analogiques de la série FX2N, positionnement, Modules CC-Link, limité par la capacité de courant du bus 5 V.
- Communication: RS232 / RS485 via des adaptateurs ADP externes (FX2NC-232ADP / 485ADP).
- Budget d’alimentation de l’hôte 5 V: Alimente les modules d’extension; ne doit pas dépasser le courant nominal de l'hôte 5 V. Calcul de la charge actuelle requis pour la sélection de l'extension.
- Variantes de suffixe
FX2NC-96MT-D: Modèle de base DC24V
FX2NC-96MT-DS: DC24V, spécification à l'étranger
FX2NC-96MT-DSS: DC24V, sortie double puits/source, Certifié UL
- Arrêt & Options de remplacement (Clé)
✅ Remplacement immédiat recommandé par les autorités: FX3UC-96MT/D, matériel et programme hautement compatibles; GX Works2 prend en charge la conversion directe du programme FX2NC.
✅ Option de mise à niveau de nouvelle génération: FX5UC-96MT/D (iQ-F), performances supérieures; évaluation du câblage et de la migration du programme requise.
Note: Non interchangeable broche à broche. Disposition des terminaux, power logic and battery model differ. Câblage, expansion bus and battery backup must be rechecked for retrofit projects.
- Applications typiques
Space-constrained compact automation, machines d'emballage, lignes de convoyeurs, stepper / servo positioning control. Transistor outputs are designed for pulse servo drive; cannot directly drive high-power AC contactors.
- Entretien & Défauts courants
- Battery Model: FX2NC-32BL lithium battery for program/register retention. Low-battery alarm via special registers; service life ~5 years, now end-of-life and spare parts scarce.
- Défauts courants
BATT LED ON: D8005 monitors battery voltage; risk of program/data loss.
ERR LED / Défaut d'alimentation: Excessive DC24V fluctuation, high ripple, or overload on expansion 5V bus.
Aucune réponse d'entrée: Oxidation on plug-in terminals (very common failure point for FX2NC).
No pulse from Y outputs: Output common terminal wiring, load polarity or pulse instruction parameter errors.
- Logiciel de programmation: GX Developer / GX fonctionne2; programming cable FX-USB-AW or RS422 download cable required.
- Liste de contrôle d’inspection des unités d’occasion (Achats de pièces de rechange)
- Aucune marque de brûlure sur le boîtier; fiches de connexion intactes, sans corrosion ni fissuration des broches.
- Allumez et vérifiez l'alimentation / LED ERR; lire la tension de la batterie sur le D8005.
- Vérifier le fonctionnement de lecture/écriture de la carte mémoire EEPROM.
- Forcer tous les points d'E/S X/Y un par un pour confirmer la fonction de commutation.
- Sauvegardez le programme d'origine et vérifiez la version du micrologiciel.
- Liste de contrôle pour la migration du programme (FX2NC → FX3UC)
- Téléchargez le programme FX2NC dans GX Works2 et enregistrez le projet.
- Changer le modèle PLC dans le projet en FX3UC-96MT/D, exécuter la conversion du programme, résoudre les erreurs d'instructions héritées incompatibles.
- Vérifier les registres M/D spéciaux, compteurs rapides et adresses de sortie d'impulsions.
- Refonte de la disposition de l'extension; supprimer FX2NC-CNV-IF (FX3UC prend directement en charge les modules FX3U).
- Redessiner les schémas de câblage des bornes: Les adresses d'E/S restent les mêmes mais les positions physiques des terminaux diffèrent.
- Re-evaluate battery replacement scheme and retentive register parameters.
- No-lod power-on test, followed by loaded commissioning.
- Comparaison des modèles de même série
FX2NC-16MT / 32MT / 64MT / 96MT, identical architecture with increasing I/O count.
FX2NC (FX2NC-96MT) Code d'erreur & Special Alarm Register List
Reading method: Monitor D8060~D8068 online in GX Developer/GX Works2; M80xx = alarm flags. D8004 stores the register number of the highest priority active error.
Hardware LED reference: BATT LED = battery alarm; ERROR flashing = program / parameter fault; ERROR steady ON = fatal CPU hardware fault
- Core Alarm M Relays (M8060~M8068)
| Élément | Description | Behavior | Remarques |
| M8004 | Global Error Flag | ON = any fault present | Activated when any of M8060~M8068 is ON |
| M8005 | Low Battery Voltage | BATT LED ON | Battery voltage read via D8005; triggers below threshold |
| M8006 | Latch Low Battery | Latched ON | Retains low-battery history, not cleared by power cycle |
| M8060 | I/O Configuration Error | RUN enabled | E/S définies par programme / les modules d'extension ne correspondent pas au matériel physique; D8060 = adresse E/S de départ du défaut |
| M8061 | Erreur matérielle de l'automate | ERREUR allumé en continu, ARRÊT automate | Processeur, Panne de RAM ou de bus E/S; D8061 contient le code d'erreur matérielle |
| M8062 | Programmeur / Erreur de communication périphérique | RUN enabled | Câble de programmation ou communication HOST défectueux; D8062 = code d'erreur de communication |
| M8063 | Lien parallèle / Erreur de communication RS485 | RUN enabled | Liaison parallèle multipoint ou défaut 485ADP; D8063 = code d'erreur de communication |
| M8064 | Erreur de paramètre | ERREUR clignotant, ARRÊT | Paramètres API invalides (Taille des E/S, mémoire, numéro de station); Code d'erreur D8064 |
| M8065 | Erreur de syntaxe | ERREUR clignotant, ARRÊT | Erreur de syntaxe du programme; signalé lors du téléchargement; Code d'erreur D8065 |
| M8066 | Erreur de circuit | ERREUR clignotant, ARRÊT | Erreur de logique à relais (par exemple. bobine directement connectée au bus principal); Code d'erreur D8066 |
| M8067 | Erreur d'opération | L'EXÉCUTION continue | Erreur d'exécution de l'instruction (division par zéro, débordement de registre, adresse invalide); Code d'erreur D8067 |
| M8068 | Erreur de fonctionnement verrouillé | L'EXÉCUTION continue | Le verrou conserve l'erreur d'exécution, persists through power cycle, réinitialisation manuelle requise; D8068 latched error code |
| M8069 | I/O Bus Check Bit | Manual ON trigger | Starts I/O bus diagnostic test; bus faults write 6103/6104 to D8061 |
- D Register Fault Codes (D8061/D8062/D8063)
D8061 (Hardware Error Codes)
| Code | Description du défaut | Dépannage |
| 0 | No hardware fault | – |
| 6101 | RAM abnormality | Memory damage; replace PLC |
| 6102 | CPU arithmetic circuit failure | Main unit hardware damage |
| 6103 | I/O Bus Error | Loose/corroded FX2NC expansion plug, FX2NC-CNV-IF adapter or expansion cable |
| 6104 | Missing 24V supply to expansion unit | DC24V power lost for expansion modules; D8009 logs fault unit starting I/O address |
D8062 (Programming Port / Peripheral Communication Errors)
| Code | Description du défaut |
| 0 | Normale |
| 6201 | Parité / Overrun / Framing error (serial noise, baud rate mismatch) |
| 6202 | Character error |
| 6203 | Checksum error |
| 6204 | Data format error |
| 6205 | Instruction error |
D8063 (Lien parallèle / 485ADP Communication Errors)
| Code | Description du défaut |
| 0 | Normale |
| 6301 | Parité / Overrun / Framing error |
| 6302 | Character error |
| 6303 | Checksum error |
| 6304 | Data format error |
| 6305 | Instruction error |
| 6306 | WDT Timeout (long communication blockage) |
- D8000~D8009 System Diagnostic Registers (Auxiliaire)
D8000: Watchdog timer setting (défaut 100 MS)
D8001: Version du firmware de l'automate + capacité de mémoire
D8002: Type de mémoire (00H=RAM, 02H=Protection EEPROM désactivée, 0AH = protection EEPROM activée)
D8003: Indicateur d'erreur de mémoire de sauvegarde
D8004: Numéro d'enregistrement de l'erreur active la plus prioritaire (par exemple. 8061 = défaut matériel)
D8005: Tension de la batterie, unité = 0,01 V (exemple: 300 = 3,0 V; alarme environ. en dessous de 2,7 V)
D8006: Seuil de détection de batterie faible
D8007: Compteur de panne de courant momentanée
D8008: Temps de détection de perte de puissance momentanée
D8009: Adresse d'E/S de départ de l'unité d'extension avec perte de 24 V (valable lorsque M8009 = ON)
- Défauts de modules spéciaux (Analogique / Positionnement / CC-Lien)
Modules spéciaux d'extension FX2NC (FX2NC-4AD, 4ET, 1PG, 32CCL, etc.) n'utilisez pas le D806x. Lire BFM29 pour les codes d'erreur du module via l'instruction FROM.
BFM29b0=1: Le module présente un défaut
b1: Anomalie de décalage/gain EEPROM
b2: Défaut alimentation module 24V
b3: Défaut matériel du module
b4: Utilisation abusive des instructions FROM/TO
Les bits restants varient selon le type de module (positionnement, CC-Link, etc.)
- Flux de dépannage rapide (FX2NC-96MT)
- Vérifier les LED: BATT ON → défaut batterie; ERROR flashing → program/parameter; ERROR steady ON → CPU hardware fault
- Monitor D8004 online to identify active M80xx fault source
- Read corresponding D806x to get detailed error code
- Operation faults M8067/M8068: Locate faulty instruction; M8068 requires manual reset
- I/O bus error 6103: Inspect FX2NC expansion plugs and FX2NC-CNV-IF pins for oxidation (high frequency FX2NC failure)
- Communication errors 62xx/63xx: Vérifier le débit en bauds, cable shielding and terminating resistors
- Differences vs FX3UC (Migration Reference)
FX3UC retains the M8060~M8068 system with extra alarm registers; base 61xx/62xx/63xx fault codes have identical definitions. Diagnostic logic can be reused after migration.
Mitsubishi FX2NC Full Series Model List (MELSEC-F FX2NC Ultra-Compact PLC, all EOL discontinued)
Définition du suffixe
D: DC24V supply; DS: overseas spec; DSS: sortie double puits/source + UL certification
T: pluggable connector; R = relay output; T = sortie transistor
Tous les processeurs sont alimentés en DC24V. Pas d'unités principales FX2NC alimentées en courant alternatif.
- Unités principales du processeur
| Modèle | E/S totales | Entrée X | Sortie Y | Type de sortie |
| FX2NC-16MT | 16 | 8 | 8 | Transistor |
| FX2NC-16MT-D | 16 | 8 | 8 | Transistor |
| FX2NC-16MT-DSS | 16 | 8 | 8 | Transistor (Double polarité UL) |
| FX2NC-16MR-T-DS | 16 | 8 | 8 | Relais (Bornier à vis européen) |
| FX2NC-32MT | 32 | 16 | 16 | Transistor |
| FX2NC-32MT-D | 32 | 16 | 16 | Transistor |
| FX2NC-32MT-DSS | 32 | 16 | 16 | Transistor (Double polarité UL) |
| FX2NC-64MT | 64 | 32 | 32 | Transistor |
| FX2NC-64MT-D | 64 | 32 | 32 | Transistor |
| FX2NC-64MT-DSS | 64 | 32 | 32 | Transistor (Double polarité UL) |
| FX2NC-96MT | 96 | 48 | 48 | Transistor (unité cible) |
| FX2NC-96MT-D | 96 | 48 | 48 | Transistor |
| FX2NC-96MT-DSS | 96 | 48 | 48 | Transistor (Double polarité UL) |
- Modules d'extension d'E/S dédiés FX2NC (Connexion directe à l'hôte FX2NC, pas de CNV-IF)
Extension d'entrée (EX)
FX2NC-16EX / FX2NC-16EX-DS: 16-point d'entrée DC24V (connecteur)
FX2NC-16EX-T / FX2NC-16EX-T-DS: 16-point d'entrée DC24V (bornier à vis)
FX2NC-32EX / FX2NC-32EX-DS: 32-point d'entrée DC24V
Extension de sortie (Transistor EYT / Relais EYR)
FX2NC-16EYT / FX2NC-16EYT-DSS: 16-sortie transistor ponctuelle
FX2NC-16EYR-T-DS: 16-sortie relais ponctuelle (borne à vis)
FX2NC-32EYT / FX2NC-32EYT-DSS: 32-sortie transistor ponctuelle
FX2NC-64ET: 64-point d'E/S mixtes (32-entrée +32-sortie), sortie transistorisée
Note: Les modules d'extension FX0N et FX2N standard ne peuvent pas se connecter directement au FX2NC. Adaptateur de conversion FX2NC-CNV-IF requis.
- Mémoire, Horloge & Cartes d'options
FX2NC-EEPROM-4C: 4Carte EEPROM K-step avec horloge temps réel RTC
FX2NC-EEPROM-16C: 16Carte EEPROM K-step avec RTC (common variant)
FX2NC-EEPROM-16: 16K-step EEPROM, no real-time clock
FX2NC-RTC: Real-time clock board (memory not included, adds RTC only)
FX2NC-ROM-CE1: Extended ROM board for inverter communication EXTR instruction
FX2NC-32BL: Backup lithium battery for program / register retention
FX2NC-10BPCB1 / FX2NC-100BPCB: Terminal adapter baseplate
- Communication Adapters (side-mounted to CPU)
FX2NC-232ADP: RS232 communication adapter
FX2NC-485ADP: RS485 communication adapter (parallel link, Modbus)
- Conversion Adapter
FX2NC-CNV-IF: Interface converter between FX2NC and FX0N/FX2N standard expansion modules (high-demand spare part)
- Compatible General Special Modules (Requires FX2NC-CNV-IF)
FX2N series special modules, usable with FX2NC only via CNV-IF adapter
FX2N-4AD: 4-ch analog input
FX2N-4DA: 4-ch analog output
FX2N-4AD-PT: 4-ch PT100 RTD
FX2N-4AD-TC: 4-ch thermocouple
FX2N-1HC: High-speed counter module
FX2N-1PG-E: Single-axis pulse positioning module
FX2N-1RM-E: Module de came programmable
FX2N-32CCL: Module esclave CC-Link
- Points clés du système
- E/S totales maximales pour le système FX2NC: 256 points (hôte + Extension FX2NC + Extension FX2N combinée)
- Tous les processeurs principaux sont à sortie transistor; FX2NC-16MR-T-DS est la seule unité principale à sortie relais
- Deux familles d'extension: Prise directe à extension fine FX2NC; Les modules standard FX2N nécessitent un adaptateur CNV-IF
- Toutes les séries abandonnées; seulement d'occasion, stock tiré ou restant disponible. Les batteries de secours FX2NC-32BL deviennent également rares.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur