H3BF-N8, Recycle ON-OFF Cycle Timer Relay, 8-pin socket-mount type, AC/DC wide-voltage design, for industrial cyclic timing. Applications include intermittent motor start-stop, lighting cycling and periodic equipment control.
- Décodage du modèle
H3BF: Nom de la série, Dual-setting cycle timer relay (independent ON-time and OFF-time adjustment)
N: Universal power supply: AC24-240V / DC12-240V
8: 8-pin round socket (Matching base: P2CF-08)
- Spécifications principales
| Article | Spécification |
| Mode de fonctionnement | ON/OFF cycle (T1 ON‑delay, T2 OFF‑delay, continuous cyclic operation) |
| Plage de synchronisation | 0.1s‑100h, multi‑range selector (s/min/h) |
| Alimentation | AC24‑240V, DC12‑240V, AC‑DC universal |
| Contact de sortie | Sortie relais, SPDT (Single‑Pole Double‑Throw) |
| Contacter l'évaluation | AC250V 5A (charge résistive) |
| Terminaux | 8‑pin round, compatible with base P2CF‑08 |
| Réinitialiser | Power‑off reset; external reset terminals available |
| Montage | Montage sur rail DIN / socket panel mounting |
Logique de fonctionnement
- Power on → Output energized, start timing T1 (ON-time)
- T1 timeout → Output de-energized, start timing T2 (OFF-time)
- T2 timeout → Output re-energized, restart T1, infinite cycle
✅Independent adjustment for ON duration and OFF duration, which is the key feature of H3BF-N8.
- Définition des broches (8-épingle)
Épingles 2-7: Power input, no polarity distinction for AC & CC
Épingles 1-3-4: Sortie SPDT: Pin1=Common, Pin3=NO(Normalement ouvert), Pin4=NC(Normalement fermé)
Épingles 5-6: External reset terminals. Short-circuit pin5-6 to force timer reset.
Note: Do NOT keep pins 5-6 permanently short-circuited. Timer stops timing while shorted.
- Dépannage courant
- No cyclic action: Verify T1/T2 are not set to minimum; check accidental short-circuit on external reset 5-6; confirm power supply.
- Timing inaccuracy: Confirm time unit range (s/min/h); avoid power supply fluctuation.
- No contact switching: Load exceeds 5A rating. Use auxiliary relay for load expansion.
- Sélection alternative
- Original unit: H3BF-N8 (Discontinué; mostly stock / second-hand units on market)
- Alternatives nationales:
DH48S-S (8-pin cycle timer, base compatible with P2CF-08)
ZYS48-S, similar timing parameters and pin-out
⚠️Notice: Some domestic versions omit external-reset function. Confirm reset function before ordering if pins 5-6 reset is required.
- Second-hand Unit Inspection Checklist
- Contrôle visuel: No burn marks on housing; no corrosion on socket pins.
- Test de mise sous tension: Set short timing T1=5s, T2=5s; verify alternating ON-OFF switching.
- External-reset test: Court 5-6 temporarily; timer resets immediately and resumes after release.
- Multimeter test NO/NC contact continuity to rule out contact burnout.
H3BF-N8 Text-Based Wiring Diagram + DH48S-S Comparison
Base: P2CF-08 (8-pin round base). Pin numbering clockwise facing socket openings: 1-8.
📌H3BF-N8 Pin Assignment
| Numéro de broche. | Description de la fonction |
| 2,7 | Power terminals AC24‑240V / DC12‑240V, no AC‑DC polarity requirement |
| 1 | Output COM (Commun) |
| 3 | Output NO (Normalement ouvert, closed during T1 ON phase) |
| 4 | Output NC (Normalement fermé, closed during T2 OFF phase) |
| 5,6 | External reset terminals: Temporary short 5‑6 = forced reset & pause; resume timing after release. Do NOT keep shorted permanently |
Scheme1: Basic cycle (no external reset, épingles 5-6 left open)
- Connect power L/N to pin2 and pin7.
- Load circuit: Live wire → pin1(COM); pin3(NON) connects to contactor coil / borne de charge; load other terminal returns to neutral.
- Leave pin5 and pin6 unconnected, floating.
Cycle starts upon power-on: Output energized for T1, de-energized at T1 expiry, count T2, re-energized at T2 expiry and repeat cycle.
Scheme2: Manual reset via push-button
- Power to 2-7; load wiring 1-3 unchanged.
- Connect a normally-open push-button across pin5 and pin6. Pressing button short-circuits 5-6 for immediate reset; cycle restarts after button release.
⚠️Critical Reminders:
No polarity for DC supply on pin2-7, wide-voltage tolerant.
External reset is for momentary short only. Continuous short on 5-6 freezes timer permanently.
Max contact rating 5A resistive load. Add intermediate relay when driving contactors or heavy loads.
Timing Sequence
Power-on → Output energized, T1 ON-timing running;
T1 elapsed → Output de-energized, T2 OFF-timing running;
T2 elapsed → Output energized, repeat cycle.
📊Comparison: H3BF-N8 vs DH48S-S (Remplacement domestique)
| Article | OMRON H3BF‑N8 | DH48S‑S (8‑pin digital cycle timer) |
| Ajustement | Analog knob setting | Digital code‑switch setting |
| Alimentation | AC24‑240V / DC12‑240V universel | Voltage‑specific variants e.g. AC220V, DC24V, NOT AC‑DC universal |
| External Reset | Passive short‑circuit reset via pin5‑6 | Reset pin1‑3, pause pin1‑4; low‑cost variants omit reset/pause function |
| Base Compatibility | P2CF‑08 | P2CF‑08 base plug‑in compatible |
| Plage de synchronisation | 0.1s‑100h range switch | 0.1s‑99h99m continuous setting |
| Contact de sortie | SPDT 5A relay | SPDT 5A relay |
| Statut | Discontinué, action / second‑hand | Mass‑produced, readily available, faible coût |
| Immunité au bruit | Qualité industrielle, good power‑fluctuation résistance | General domestic grade; surge suppressor recommended for harsh cabinet environment |
⚠️Notes de remplacement:
- DH48S-S has no universal AC-DC model. Match coil voltage with site supply voltage.
- If external reset is required, confirm DH48S-S model supports reset; cheap simplified units render pin5-6 ineffective.
- H3BF-N8 starts cycle immediately after power-on; DH48S-S shares identical power-on trigger logic.
🔧Second-hand H3BF-N8 Quick Power-on Test Procedure
- Install onto base; feed AC220V to pin2-7.
- Set T1=5s, T2=5s; keep pin5-6 floating.
- Mise sous tension: Observe relay click switching and indicator toggle approximately every 5 secondes.
- Momentarily short pin5-6 with wire: Timer resets instantly; cycle resumes after wire removal.
- Multimeter test continuity of NO/NC contacts for no burnout.
OMRON H3BF-N8 Temperature Parameters (Official Datasheet)
- Température ambiante de fonctionnement (powered): -10℃ ~ +55℃, pas de glaçage
- Température de stockage (unpowered): -25℃ ~ +65℃, pas de glaçage
- Operating humidity: 35%-85%RH, condensation interdite
Temperature-induced timing deviation within -10~+55℃: Max ±2%FS (plus ±10ms error for short-time ranges).
Field Application Notes
- Avoid cabinet internal temperature sustained above 50℃ in summer due to poor ventilation. Timing accuracy degrades near upper limit 55℃.
- Icing and condensation are forbidden. Below -10℃, incorrect timing or failure to start may occur.
- Protection contre la pénétration: IP40 (front panel only), sides and rear not dust/water resistant.
Reference vs Domestic DH48S-S
H3BF-N8: -10~+55℃
Most DH48S-S domestic versions: 0~+50℃, inferior low-temperature performance versus original OMRON unit.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,capteur,Encodeur,API