PHÉNIX 2904371 Alimentation à découpage sur rail DIN

Full Order Code: UNO-PS/2AC/24DC/90W/C2LPS Phoenix Contact UNO POWER Series 2-Phase Input DIN Rail Power Supply ✅ Key Specifications Input: 2-phase AC 400~500 V AC (Large gamme: 264–575 V AC) Sortir: 24 À DC, courant nominal 3.75 UN, 90 W Adjustable output voltage: 24~28 V DC (via potentiometer) Output ripple: <50 mVpp Overvoltage protection (OVP): ≤35 ...

  • Détails du produit

Full Order Code: UNO-PS/2AC/24DC/90W/C2LPS

Contact Phénix UNO POWER Series 2-Phase Input Alimentation sur rail DIN

✅ Spécifications clés

Saisir: 2-phase AC 400~500 V AC (Large gamme: 264–575 V AC)

Sortir: 24 À DC, courant nominal 3.75 UN, 90 W

Adjustable output voltage: 24~28 V DC (via potentiometer)

Output ripple: <50 mVpp

Protection contre les surtensions (OVP): ≤35 V DC

Consommation d'énergie à vide: <0.7 W

Power factor cosφ: 0.48

Classe de protection: IP20

Montage: NS35 DIN rail

Température de fonctionnement: -25℃ ~ +70℃; déclassement 2.5% per Kelvin above 55℃

Terminaux: Screw-type clamping terminals

C2LPS = NEC Class 2 output certification + hazardous area approval (Classe I, Division 2, T4). The output circuit can be wired per Class 2 requirements without extra isolation or protective sheathing, suitable for powering PLCs, sensors and valve islands in explosion-proof cabinets.

No parallel or series connection allowed

✅ Applications typiques

Control cabinets with 400V two-phase power supply, emplacements dangereux, construction machinery, CVC, wind turbine auxiliary control systems; power supply for PLCs, détecteurs de proximité, solenoid valves and HMIs.

Important distinction: Unlike conventional single-phase 220V UNO power supplies, this model is a high-voltage two-phase input version, which is frequently misselected on site.

✅ Replacement Reference

Single-phase counterpart in the same series: 2902994 (UNO-PS/1AC/24DC/90W/C2LPS), input range 85–264 V AC. Do not interchange the two models.

For higher power with the same structure: UNO 150W & 240W two-phase variants.

✅ Troubleshooting Guide

  1. DC OK indicator off: First verify two-phase input voltage. The unit will not start under phase loss or input voltage below 264 V et.
  2. Excessive voltage drop under load: Check for overcurrent or temperature-induced derating.
  3. Frequent protection trips: Load short circuit or output earth fault. Classe 2 models feature highly sensitive short-circuit protection.

PHÉNIX 2904371 (UNO-PS/2AC/24DC/90W/C2LPS) Manuel d'installation

Condition préalable de sécurité: Indoor cabinet mounting only, Indice IP20. C2LPS stands for Class 2 output plus Class I Division 2 hazardous area certification. All installation in explosive environments must comply strictly with ISA-12.12.01 standards.

  1. Présentation du produit

Numéro de commande: 2904371

Série: UNO POWER 2-phase DIN rail power supply

Saisir: 2-phase AC 264–575 V (400V two-phase, NOT single-phase 220V)

Sortir: 24 À DC, 3.75 UN / 90 W, adjustable 24–28 V

Montage: NS35 DIN rail (EN60715), installation horizontale

Largeur du boîtier: 55 mm

  1. Exigences d'autorisation (Mandatory for Heat Dissipation)

Side-by-side horizontal installation: 0 mm minimum clearance (units may be mounted tightly together)

Vertical stacking: Minimum 30 mm upper and lower clearance for cooling air flow

No upside-down or side mounting; only horizontal installation with terminals facing forward/downward

Do not install adjacent to heat-generating components (contacteurs, résistances de freinage); high ambient temperature will trigger power derating

Altitude derating: Power rating and insulation voltage must be reduced above 2000 m elevation

  1. Installation sur rail DIN & Suppression
  2. Hook the top latch onto the NS35 rail first
  3. Press down the unit until the latch clicks securely into place
  4. Suppression: Insert a flat screwdriver into the bottom latch tab, pry upward to release the lock and pull the unit off the rail

Résistance aux vibrations: Compliant with industrial cabinet vibration standards; no extra locking screws required once clipped firmly.

  1. Spécifications de câblage (M3 Screw Terminals)

Type de borne: Screw clamping terminals

Taille du conducteur: Solid wire 0.2–2.5 mm²; stranded wire 0.2–2.5 mm²; AWG24~AWG14

Strip length: 8 mm

Cable temperature rating: ≥75℃ for ambient <55℃; ≥90℃ for 55~70℃ ambient

Couple de serrage: 0.5–0.7 Nm (éviter de trop serrer pour éviter d'endommager le filetage)

Définition du terminal (Critique: Two-phase input, no neutral N!)

Bornes d'entrée: L1, L2 (two-phase 400V AC, neutral N is not connected); PE protective earth terminal

Bornes de sortie: +24 V, 0 V (24 À DC)

Adjustment potentiometer: ADJ (24~28 V fine-tuning; factory preset to 24 V)

Indicateur: DC OK (green light ON = normal output; OFF = no output or protection active)

⚠️ Avertissement critique: This is a 2-phase AC power supply. Never wire it as a single-phase L+N unit; incorrect wiring will cause failure or permanent damage.

  1. Wiring Sequence (Lockout-Tagout Safety Procedure)
  2. Confirm upstream circuit is de-energized and apply lockout-tagout
  3. Connect PE protective earth first (reliable earthing is mandatory)
  4. Wire the two-phase input lines L1/L2
  5. Terminate the 24V DC load cables
  6. Inspect for short circuits and earth insulation; confirm no shorted load circuits
  7. Apply power and verify the DC OK green LED illuminates; trim the ADJ potentiometer to set target output voltage
  8. Classe 2 (C2LPS) wiring rule: Output cabling shall follow NEC Class 2 specifications; no shared trunking with high-voltage power cables without isolation barriers.
  9. Fonctions de protection & Diagnostic des pannes

Protection contre les courts-circuits: Constant current limiting. Classe 2 versions feature high sensitivity; short-circuit triggers immediate shutdown, auto-recovery after fault removal.

Protection contre les surcharges: Current exceeding 105% rated value activates current limiting

Protection contre les surtensions (OVP): Output shuts down above 35 À DC

Thermal protection: Over-temperature shutdown; redémarrage automatique après refroidissement

Sous-tension / perte de phase: No start-up if input voltage drops below 264 V et; DC OK light remains off.

  1. Environnemental & Restrictions d'installation

Température de fonctionnement: -25℃ ~ +70℃; 2.5%/K power derating above 55℃

Humidité: 5%~95 % sans condensation

Forbidden applications: Outdoor direct mounting, dusty/corrosive atmospheres, water splash exposure

Explosion-proof installation (Class I Div.2 T4): Cabinet-only mounting; external wiring must not create ignition sources, comply with flameproof/enclosure standards.

  1. Parallèle & Series Connection

❌ This model does NOT support parallel current expansion or series voltage boosting. Select the QUINT series if multi-unit parallel operation is required.

  1. CEM & Mise à la terre

The PE terminal must connect securely to cabinet protective earth; floating earth is prohibited

Upstream overcurrent protection recommendation: C-curve MCB, 1 Un ou 2 UN (for 400V two-phase circuit)

Classe 2 output circuits normally do not require additional fuses; si nécessaire, implement UL1310 Class 2 current-limiting designs.

  1. Commissioning Checklist

Unit fully clipped onto DIN rail with no play

PE earth connection solid and reliable

L1/L2 two-phase input voltage stays within 264–575 V AC

No short circuit or earth fault on output wiring

DC OK green LED stays steady ON after power-up

Measured output voltage matches the set value

30 mm vertical cooling clearance is maintained top and bottom

III. UNO-PS Full Model List

3.1 UNO-PS / 1AC Single-phase Standard Models (24Sortie V)

Numéro de commande.Modèle completPouvoirCourant nominal
2902991UNO-PS/1AC/24DC/30W30 W1.25 UN
2902992UNO-PS/1AC/24DC/60W60 W2.5 UN
2902993UNO-PS/1AC/24DC/100W100 W4.2 UN
1088851UNO-PS/1AC/24DC/100W/H100 W High-altitude version—
2904376UNO-PS/1AC/24DC/150W150 W6.25 UN
2904377UNO-PS/1AC/24DC/240W240 W10 UN

3.2 Other Output Voltages (12V / 15V / 48V)

Numéro de commande.Modèle completNote de sortie
2902998UNO-PS/1AC/12DC/30W12 V / 30 W
2902999UNO-PS/1AC/12DC/55W12 V / 55 W
2902997UNO-PS/1AC/12DC/100W12 V / 100 W
2903000UNO-PS/1AC/15DC/30W15 V / 30 W
2903001UNO-PS/1AC/15DC/55W15 V / 55 W
2903002UNO-PS/1AC/15DC/100W15 V / 100 W
2902995UNO-PS/1AC/48DC/60W48 V / 60 W
2902996UNO-PS/1AC/48DC/100W48 V / 100 W
  1. UNO-PS/2AC Two-phase Standard Models (Non-C2LPS, No Class 2 Protection contre les explosions)
Numéro de commande.Modèle completPuissance nominale
2904371UNO-PS/2AC/24DC/90W/C2LPS90 W (C2LPS explosion-proof variant, votre modèle)
2904376UNO-PS/2AC/24DC/150W150 W (standard two-phase model)
2904377UNO-PS/2AC/24DC/240W240 W (standard two-phase model)
  1. Règle de dénomination du modèle (Pour référence de sélection)

UNO-PS / 1AC/2AC / 24CC / 90W / C2LPS

  1. 1AC = Single-phase input; 2AC = Two-phase 400V input (L1+L2, no neutral N)
  2. 24DC = 24 Sortie V CC
  3. 90W = Nominal output power
  4. C2LPS = Class 2 sortir + Division Classe I 2 hazardous area certification (only available for the 90W model)
  5. Notes complémentaires
  6. Only two C2LPS explosion-proof models are available:

Monophasé: 2902994

Two-phase: 2904371 (votre modèle). No higher-power two-phase C2LPS variants exist.

  1. No parallel current expansion for the entire UNO series. Use the QUINT series if parallel operation is required.
  2. All units come with screw terminals (CS). The second-generation UNO models use push-in PT terminals and are not mechanically interchangeable with this housing.