Série: VarPlus Can HDuty (Robuste, PowerLogic PFC low-voltage power factor correction capacitor)
BLRCH = Heavy Duty version, designed for applications with high harmonic distortion and severe operating conditions; BLRCS is the EasyCan standard version with lower harmonic withstand capability.
Décodage du modèle
BLRCH: VarPlus Can HDuty three-phase PFC capacitor
200: 20kvar @ 400V, 50Hz
A240: 24kvar @ 400V, 60Hz
B40: Rated voltage 400V
Paramètres électriques de base
Tension nominale: 400V (compatible avec 380V / 415Systèmes V), dual-rated for 50/60Hz
380V 50 Hz: 18.1kvar|380V 60Hz: 21.7gauche
400V 50 Hz: 20kvar|400V 60Hz: 24gauche
415V 50 Hz: 21.5kvar|415V 60Hz: 25.8gauche
Continuous overcurrent capability: 1.8×Dans (heavy-duty design for harmonic resistance)
Permissible continuous overvoltage: 1.1Et (maximum 8 hours within 24h)
Inrush current at switching: 250×Dans
Maximum annual switching operations: 7000 fois
Design life: 130000h
Capacitance tolerance: -5% ~ +10%
Dielectric: Metallized polypropylene film with zinc-aluminium alloy, wave-cut edge technology
Normes: CEI 60831-1 / CEI 60831-2
Terminal design: ClampTite locking terminals, vertical or horizontal mounting available
Application
Industrial sites with abundant non-linear loads (VFD, redresseurs, Hauts) and high harmonic content. Compared with standard BLRCS, it has greater harmonic margin and lower risk of bulging and premature failure.
Alternatives & Référence croisée au sein des séries
Standard version with same rating: BLRCS200A240B40 (EasyCan, for low harmonic scenarios, moindre coût)
Same capacity, higher voltage: BLRCH200A240B44 (440V)
Sélection & Matching Notes
- Heavy-duty capacitors are still recommended to use series detuned reactors for harmonic mitigation;
- Switching device: Schneider VarLogic dedicated capacitor contactor is preferred for inrush suppression;
Engineering reference: For 50Hz systems in China, 28.9A is taken as base rated current;
Max allowable continuous current of capacitor: 1.8×In → approx. 51.9A at 50Hz
Composants correspondants (contacteur, disjoncteur, câble) to be sized at 1.5~1.8×In:
Contacteur: Schneider LC1DK dedicated capacitor contactor (inrush-limiting type), ≥40A class recommended
Disjoncteur: Courbe D, 32A or 40A
Câble: Copper conductor ≥10mm² for short cabinet wiring; 16mm² for long runs or high ambient temperature
Important reminder: After series connection with reactor, voltage across capacitor rises and actual operating current increases. Do not use the base 28.9A directly for sizing; correction according to reactor percentage is mandatory.
- Reactor Sizing Logic (50Hz, 400Système V)
Reactor percentage selection rule (Schneider official guideline)
| État de fonctionnement | Recommended Reactor Percentage | Remarque |
| Low harmonic, only inrush limiting | 0.1%~1% | Only suppress switching inrush, no detuning, no harmonic filtering |
| Dominant 5th/7th harmonics from VFD & Hauts (most common sites) | 7% (Schneider preferred) /6% | Tuning frequency ≈190Hz, detuned away from 5th harmonic to avoid harmonic amplification |
| Severe 3rd harmonic from single-phase non-linear loads (DIRIGÉ, alimentation à découpage) | 14% | Tuning frequency ≈135Hz, targeted for 3rd harmonic |
Schneider OEM reactor reference (matched to VarPlus Can)
Schneider detuned reactor legacy series: LRF
LRF0714: 7%, 1.4gauche, 480V, matched to this 20kvar capacitor
LRF1428: 14%, 2.8gauche, 525V
Alternative nationale: CKSG dry-type series reactor (CKSG-1.4/0.48-7%)
III. Critical Risk Notes for this model
- BLRCH heavy-duty does NOT mean reactor-free. Capacitors will bulge and fail early under heavy harmonics without reactor; it only has higher tolerance margin than BLRCS.
- Uniform reactor percentage for all branches within one PFC cabinet. Mixing 7% et 14% detuned branches in same cubicle is not allowed, risk of internal resonance and harmonic amplification.
- Switching cycle limit for detuned branches: Max. 7000 operations per year (capac inherent limit).
- CT for power factor controller: Install CT on grid side before reactor, not after capacitor branch.
- Sizing Combination Summary Table (50Hz, 400V)
| Réacteur % | Reactor Power | Reactor Voltage Class | Calculated Capacitor Voltage | Continuous use of B40 (400V) |
| 7% | 1.4gauche | 480V | 428V | ✅ Acceptable (HDuty) |
| 14% | 2.8gauche | 525V | 465V | ❌ Recommend B44 upgrade |
Schneider OEM Matched Reactor (LVR series, PowerLogic detuned reactor for BLRCH200A240B40, 20kvar@400V 50Hz)
Schneider current preferred series: LVR (legacy LRF phased out; 5.7% reactors fully discontinued, not recommended)
Liste des modèles
| Modèles OEM | Réacteur % | Tuning Frequency | Reactor Rating | Courant nominal |
| LVR07200A40T | 7% | 190Hz (3.8ème) | For 20kvar branch @7% | ≥28.9A |
| LVR14200A40T | 14% | 135Hz (2.7ème) | For 20kvar branch @14% | ≥28.9A |
Model decoding:
LVR = Detuned Reactor
07 / 14 = 7% /14% reactor percentage
200 = Matched for 20kvar capacitor branch
A = 50Hz; B=60Hz
40 = 400V system; T = Standard version
General Specification of LVR Reactor
Classe d'isolation: Classe H
Tension assignée d'isolement Ui: 1100V, power frequency withstand 4kV/1min
Inductance tolerance: ±5%
Surcharge continue: 1.12~1.2×fundamental current (harmonic-hardened design)
Construction: Dry-type 3-phase stacked core, vertical winding, IP00, indoor cabinet mounting
Standard: CEI 60289, matched with VarPlus Can capacitor (BLRCH/BLRCS)
60Hz Matching (BLRCH200A240B40 = 24kvar @60Hz)
LVR07240B40T: 7%, matched for 24kvar @60Hz
LVR14240B40T: 14%, matched for 24kvar @60Hz
Alternative nationale (CKSG dry series reactor, largement utilisé dans les projets)
| Modèle alternatif | Réacteur % | Classe de tension | Remarque |
| CKSG-1.4/0.48-7% | 7% | 480V | Replace LVR07200A40T |
| CKSG-2.8/0.525-14% | 14% | 525V | Replace LVR14200A40T |
Sizing Hard Rules
- 5.7% (210Hz) reactors are fully discontinued by Schneider, no new specification; héritage 5.7% projects migrate to 7%.
- Uniform reactor percentage inside one PFC panel. Mixing 7% et 14% branches causes resonance hazard.
- 14% detuned branches strongly recommend 440V capacitor upgrade; 400V capacitor suffers accelerated ageing under sustained overvoltage.
- Reactor rated current to be sized on harmonic-amplified operating current, not only fundamental 28.9A.
Schneider Low-Voltage PFC Capacitor Full List (VarPlus Can Main Series)
Two core lines: BLRCS (EasyCan Standard Duty)、BLRCH (VarPlus Can Heavy Duty). Three-phase aluminium can, built-in discharge resistor, pressure disconnector, dual 50/60Hz rating, mainstream for projects in China. Legacy Varplus2, VarPlus Box mostly obsolete.
Unified Model Coding Rule
`BLRCH200A240B40`
- BLRCH: HDuty Heavy Duty (high harmonic withstand, 1.8In continuous)
- BLRCS: EasyCan Standard Duty (faible harmonique, 1.3In continuous)
- First numeric block: Rating @50Hz (gauche)
- A = 50Hz flag; trailing numeric block: Rating @60Hz (gauche)
- Bxx: Tension nominale
B40: 400V
B44: 440V
B48: 480V
B52: 525V
- BLRCH HDuty Heavy Duty Series (High harmonic sites, detuned reactor recommended; your series)
400V (B40) Common for China
BLRCH025A030B40|2.5/3kvar
BLRCH050A060B40|5/6kvar
BLRCH063A075B40|6.3/7.5kvar
BLRCH083A100B40|8.3/10kvar
BLRCH104A125B40|10.4/12.5kvar
BLRCH125A150B40|12.5/15kvar
BLRCH150A180B40|15/18kvar
BLRCH200A240B40|20/24kvar (Your referenced model)
BLRCH250A300B40|25/30kvar
440V (B44, Preferred for 14% detuned branch)
BLRCH050A060B44|5/6kvar
BLRCH104A125B44|10.4/12.5kvar
BLRCH125A150B44|12.5/15kvar
BLRCH150A180B44|15/18kvar
BLRCH200A240B44|20/24kvar
BLRCH250A300B44|25/30kvar
BLRCH285A342B44|28.5/34.2kvar
480V (B48, Exporter / 60Hz systems)
BLRCH136A163B48|13.6/16.3kvar
BLRCH170A204B48|17/20.4kvar
BLRCH208A250B48|20.8/25kvar
BLRCH339A407B48|33.9/40.7kvar
BLRCH453A544B48|45.3/54.4kvar
525V (B52, High voltage-rise application)
BLRCH400A480B52|40/48kvar
- BLRCS EasyCan Standard Series (Low harmonic, simple PF correction, moindre coût)
400V (B40)
BLRCS025A030B40|2.5/3kvar
BLRCS050A060B40|5/6kvar
BLRCS083A100B40|8.3/10kvar
BLRCS104A125B40|10.4/12.5kvar
BLRCS125A150B40|12.5/15kvar
BLRCS150A180B40|15/18kvar
BLRCS200A240B40|20/24kvar (Standard alternative of BLRCH200A240B40)
BLRCS250A300B40|25/30kvar
440V (B44)
BLRCS050A060B44|5/6kvar
BLRCS125A150B44|12.5/15kvar
BLRCS200A240B44|20/24kvar
480V (B48)
BLRCS170A204B48|17/20.4kvar
BLRCS208A250B48|20.8/25kvar
BLRCS315A378B48|31.5/37.8kvar
BLRCS339A407B48|33.9/40.7kvar
III. Matching OEM Reactor Series (LVR, replace legacy LRF)
LVR07xxxA40T: 7% reactor, 400Système V, matched to corresponding kvar capacitor
LVR14xxxA40T: 14% reactor, 400Système V
xxx = matched capacity code: 050 / 104 /125 /150 /200 /250
Exemple: LVR07200A40T → 7%, matched for 20kvar capacitor branch
- Obsolete Series (Do not specify for new design)
- Varplus2 (legacy 513xx series), fully superseded by BLRCH
- VarPlus Box oil-filled type BLR_VBHE, MEHVBENY, cabinet-mounted oil type, progressivement éliminé
- Legacy LRF reactor (all 5.7% variants discontinued)
- Comparaison de sélection
| Article | BLRCS EasyCan | BLRCH HDuty |
| Harmonic withstand | Light harmonic loads | VFD, rectifier, Hauts, high harmonic environment |
| Permissible continuous overcurrent | 1.3×Dans | 1.8×Dans |
| Design life | 100000h | 130000h |
| Recommended application | Direct switching without reactor, 7% detuned light harmonic | 7%/14% detuned branch, severe harmonic site |
Remarques importantes:
- This list covers mainstream stocked models in China market; special voltages such as 240V, 575V for overseas use are rarely available locally.
- BLRCH200A240B40 marked for phase-out by manufacturer; new projects preferably evaluate BLRCH200A240B44.
- Reactor percentage must be identical for all branches inside one PFC cabinet; mélange 7% et 14% branches is forbidden.