Schneider BLRCH200A240B40 Power Factor Correction Capacitor

Série: VarPlus Can HDuty (Robuste, PowerLogic PFC low-voltage power factor correction capacitor) BLRCH = Heavy Duty version, designed for applications with high harmonic distortion and severe operating conditions; BLRCS is the EasyCan standard version with lower harmonic withstand capability. Model Decoding BLRCH: VarPlus Can HDuty three-phase PFC capacitor 200: 20kvar @ 400V, 50Hz A240: ...

  • Détails du produit

Série: VarPlus Can HDuty (Robuste, PowerLogic PFC low-voltage power factor correction capacitor)

BLRCH = Heavy Duty version, designed for applications with high harmonic distortion and severe operating conditions; BLRCS is the EasyCan standard version with lower harmonic withstand capability.

Décodage du modèle

BLRCH: VarPlus Can HDuty three-phase PFC capacitor

200: 20kvar @ 400V, 50Hz

A240: 24kvar @ 400V, 60Hz

B40: Rated voltage 400V

Paramètres électriques de base

Tension nominale: 400V (compatible avec 380V / 415Systèmes V), dual-rated for 50/60Hz

380V 50 Hz: 18.1kvar|380V 60Hz: 21.7gauche

400V 50 Hz: 20kvar|400V 60Hz: 24gauche

415V 50 Hz: 21.5kvar|415V 60Hz: 25.8gauche

Continuous overcurrent capability: 1.8×Dans (heavy-duty design for harmonic resistance)

Permissible continuous overvoltage: 1.1Et (maximum 8 hours within 24h)

Inrush current at switching: 250×Dans

Maximum annual switching operations: 7000 fois

Design life: 130000h

Capacitance tolerance: -5% ~ +10%

Dielectric: Metallized polypropylene film with zinc-aluminium alloy, wave-cut edge technology

Normes: CEI 60831-1 / CEI 60831-2

Terminal design: ClampTite locking terminals, vertical or horizontal mounting available

Application

Industrial sites with abundant non-linear loads (VFD, redresseurs, Hauts) and high harmonic content. Compared with standard BLRCS, it has greater harmonic margin and lower risk of bulging and premature failure.

Alternatives & Référence croisée au sein des séries

Standard version with same rating: BLRCS200A240B40 (EasyCan, for low harmonic scenarios, moindre coût)

Same capacity, higher voltage: BLRCH200A240B44 (440V)

Sélection & Matching Notes

  1. Heavy-duty capacitors are still recommended to use series detuned reactors for harmonic mitigation;
  2. Switching device: Schneider VarLogic dedicated capacitor contactor is preferred for inrush suppression;

Engineering reference: For 50Hz systems in China, 28.9A is taken as base rated current;

Max allowable continuous current of capacitor: 1.8×In → approx. 51.9A at 50Hz

Composants correspondants (contacteur, disjoncteur, câble) to be sized at 1.5~1.8×In:

Contacteur: Schneider LC1DK dedicated capacitor contactor (inrush-limiting type), ≥40A class recommended

Disjoncteur: Courbe D, 32A or 40A

Câble: Copper conductor ≥10mm² for short cabinet wiring; 16mm² for long runs or high ambient temperature

Important reminder: After series connection with reactor, voltage across capacitor rises and actual operating current increases. Do not use the base 28.9A directly for sizing; correction according to reactor percentage is mandatory.

  1. Reactor Sizing Logic (50Hz, 400Système V)

Reactor percentage selection rule (Schneider official guideline)

État de fonctionnementRecommended Reactor PercentageRemarque
Low harmonic, only inrush limiting0.1%~1%Only suppress switching inrush, no detuning, no harmonic filtering
Dominant 5th/7th harmonics from VFD & Hauts (most common sites)7% (Schneider preferred) /6%Tuning frequency ≈190Hz, detuned away from 5th harmonic to avoid harmonic amplification
Severe 3rd harmonic from single-phase non-linear loads (DIRIGÉ, alimentation à découpage)14%Tuning frequency ≈135Hz, targeted for 3rd harmonic

Schneider OEM reactor reference (matched to VarPlus Can)

Schneider detuned reactor legacy series: LRF

LRF0714: 7%, 1.4gauche, 480V, matched to this 20kvar capacitor

LRF1428: 14%, 2.8gauche, 525V

Alternative nationale: CKSG dry-type series reactor (CKSG-1.4/0.48-7%)

III. Critical Risk Notes for this model

  1. BLRCH heavy-duty does NOT mean reactor-free. Capacitors will bulge and fail early under heavy harmonics without reactor; it only has higher tolerance margin than BLRCS.
  2. Uniform reactor percentage for all branches within one PFC cabinet. Mixing 7% et 14% detuned branches in same cubicle is not allowed, risk of internal resonance and harmonic amplification.
  3. Switching cycle limit for detuned branches: Max. 7000 operations per year (capac inherent limit).
  4. CT for power factor controller: Install CT on grid side before reactor, not after capacitor branch.
  5. Sizing Combination Summary Table (50Hz, 400V)
Réacteur %Reactor PowerReactor Voltage ClassCalculated Capacitor VoltageContinuous use of B40 (400V)
7%1.4gauche480V428V✅ Acceptable (HDuty)
14%2.8gauche525V465V❌ Recommend B44 upgrade

Schneider OEM Matched Reactor (LVR series, PowerLogic detuned reactor for BLRCH200A240B40, 20kvar@400V 50Hz)

Schneider current preferred series: LVR (legacy LRF phased out; 5.7% reactors fully discontinued, not recommended)

Liste des modèles

Modèles OEMRéacteur %Tuning FrequencyReactor RatingCourant nominal
LVR07200A40T7%190Hz (3.8ème)For 20kvar branch @7%≥28.9A
LVR14200A40T14%135Hz (2.7ème)For 20kvar branch @14%≥28.9A

Model decoding:

LVR = Detuned Reactor

07 / 14 = 7% /14% reactor percentage

200 = Matched for 20kvar capacitor branch

A = 50Hz; B=60Hz

40 = 400V system; T = Standard version

General Specification of LVR Reactor

Classe d'isolation: Classe H

Tension assignée d'isolement Ui: 1100V, power frequency withstand 4kV/1min

Inductance tolerance: ±5%

Surcharge continue: 1.12~1.2×fundamental current (harmonic-hardened design)

Construction: Dry-type 3-phase stacked core, vertical winding, IP00, indoor cabinet mounting

Standard: CEI 60289, matched with VarPlus Can capacitor (BLRCH/BLRCS)

60Hz Matching (BLRCH200A240B40 = 24kvar @60Hz)

LVR07240B40T: 7%, matched for 24kvar @60Hz

LVR14240B40T: 14%, matched for 24kvar @60Hz

Alternative nationale (CKSG dry series reactor, largement utilisé dans les projets)

Modèle alternatifRéacteur %Classe de tensionRemarque
CKSG-1.4/0.48-7%7%480VReplace LVR07200A40T
CKSG-2.8/0.525-14%14%525VReplace LVR14200A40T

Sizing Hard Rules

  1. 5.7% (210Hz) reactors are fully discontinued by Schneider, no new specification; héritage 5.7% projects migrate to 7%.
  2. Uniform reactor percentage inside one PFC panel. Mixing 7% et 14% branches causes resonance hazard.
  3. 14% detuned branches strongly recommend 440V capacitor upgrade; 400V capacitor suffers accelerated ageing under sustained overvoltage.
  4. Reactor rated current to be sized on harmonic-amplified operating current, not only fundamental 28.9A.

Schneider Low-Voltage PFC Capacitor Full List (VarPlus Can Main Series)

Two core lines: BLRCS (EasyCan Standard Duty)、BLRCH (VarPlus Can Heavy Duty). Three-phase aluminium can, built-in discharge resistor, pressure disconnector, dual 50/60Hz rating, mainstream for projects in China. Legacy Varplus2, VarPlus Box mostly obsolete.

Unified Model Coding Rule

`BLRCH200A240B40`

  1. BLRCH: HDuty Heavy Duty (high harmonic withstand, 1.8In continuous)
  2. BLRCS: EasyCan Standard Duty (faible harmonique, 1.3In continuous)
  3. First numeric block: Rating @50Hz (gauche)
  4. A = 50Hz flag; trailing numeric block: Rating @60Hz (gauche)
  5. Bxx: Tension nominale

B40: 400V

B44: 440V

B48: 480V

B52: 525V

  1. BLRCH HDuty Heavy Duty Series (High harmonic sites, detuned reactor recommended; your series)

400V (B40) Common for China

BLRCH025A030B40|2.5/3kvar

BLRCH050A060B40|5/6kvar

BLRCH063A075B40|6.3/7.5kvar

BLRCH083A100B40|8.3/10kvar

BLRCH104A125B40|10.4/12.5kvar

BLRCH125A150B40|12.5/15kvar

BLRCH150A180B40|15/18kvar

BLRCH200A240B40|20/24kvar (Your referenced model)

BLRCH250A300B40|25/30kvar

440V (B44, Preferred for 14% detuned branch)

BLRCH050A060B44|5/6kvar

BLRCH104A125B44|10.4/12.5kvar

BLRCH125A150B44|12.5/15kvar

BLRCH150A180B44|15/18kvar

BLRCH200A240B44|20/24kvar

BLRCH250A300B44|25/30kvar

BLRCH285A342B44|28.5/34.2kvar

480V (B48, Exporter / 60Hz systems)

BLRCH136A163B48|13.6/16.3kvar

BLRCH170A204B48|17/20.4kvar

BLRCH208A250B48|20.8/25kvar

BLRCH339A407B48|33.9/40.7kvar

BLRCH453A544B48|45.3/54.4kvar

525V (B52, High voltage-rise application)

BLRCH400A480B52|40/48kvar

  1. BLRCS EasyCan Standard Series (Low harmonic, simple PF correction, moindre coût)

400V (B40)

BLRCS025A030B40|2.5/3kvar

BLRCS050A060B40|5/6kvar

BLRCS083A100B40|8.3/10kvar

BLRCS104A125B40|10.4/12.5kvar

BLRCS125A150B40|12.5/15kvar

BLRCS150A180B40|15/18kvar

BLRCS200A240B40|20/24kvar (Standard alternative of BLRCH200A240B40)

BLRCS250A300B40|25/30kvar

440V (B44)

BLRCS050A060B44|5/6kvar

BLRCS125A150B44|12.5/15kvar

BLRCS200A240B44|20/24kvar

480V (B48)

BLRCS170A204B48|17/20.4kvar

BLRCS208A250B48|20.8/25kvar

BLRCS315A378B48|31.5/37.8kvar

BLRCS339A407B48|33.9/40.7kvar

III. Matching OEM Reactor Series (LVR, replace legacy LRF)

LVR07xxxA40T: 7% reactor, 400Système V, matched to corresponding kvar capacitor

LVR14xxxA40T: 14% reactor, 400Système V

xxx = matched capacity code: 050 / 104 /125 /150 /200 /250

Exemple: LVR07200A40T → 7%, matched for 20kvar capacitor branch

  1. Obsolete Series (Do not specify for new design)
  2. Varplus2 (legacy 513xx series), fully superseded by BLRCH
  3. VarPlus Box oil-filled type BLR_VBHE, MEHVBENY, cabinet-mounted oil type, progressivement éliminé
  4. Legacy LRF reactor (all 5.7% variants discontinued)
  5. Comparaison de sélection
ArticleBLRCS EasyCanBLRCH HDuty
Harmonic withstandLight harmonic loadsVFD, rectifier, Hauts, high harmonic environment
Permissible continuous overcurrent1.3×Dans1.8×Dans
Design life100000h130000h
Recommended applicationDirect switching without reactor, 7% detuned light harmonic7%/14% detuned branch, severe harmonic site

Remarques importantes:

  1. This list covers mainstream stocked models in China market; special voltages such as 240V, 575V for overseas use are rarely available locally.
  2. BLRCH200A240B40 marked for phase-out by manufacturer; new projects preferably evaluate BLRCH200A240B44.
  3. Reactor percentage must be identical for all branches inside one PFC cabinet; mélange 7% et 14% branches is forbidden.