Définition du code modèle
Breakdown of NSYCVF165M230PF
| Segment de code | Signification | Description |
| NSY | Product series prefix | General mark for Schneider ClimaSys cabinet cooling products |
| CV | Sous-série | ClimaSys CV series standard cabinet filter fan |
| F | Type de produit | Ventilateur |
| 165 | Air flow rate | Rated airflow 165m鲁/h at 50Hz, 193m鲁/h at 60Hz |
| M. | Type de montage | Side mounting on cabinet |
| 230 | Tension nominale | 230V et |
| P. | Protection configuration | Equipped with pre-filter |
| F | Air outlet configuration | Fitted with front grille |
- Paramètres de spécification de base
| Catégorie | Index technique | Remarques |
| Paramètres de base | ||
| Type de produit | Cabinet Filter Fan | ClimaSys CV series, IP54 protection |
| Air Flow | 165m³/heure (50Hz) / 193m³/heure (60Hz) | Measured with standard G2 filter |
| Plage de tension | 175~253V AC | Compatible with most 230V power grids worldwide |
| Tension nominale | 230V 50/60Hz | Dual frequency compatibility |
| Paramètres électriques | ||
| Pouvoir | 16.3W (50Hz) / 14.3W (60Hz) | Haute efficacité énergétique |
| Actuel | 0.12UN (50Hz) / 0.94UN (60Hz) | Low power consumption design |
| Connexion | Faston terminal + câble d'alimentation | Installation facile |
| Physical Parameters | ||
| External Dimension | 268×248×104mm | Hauteur×Largeur×Profondeur |
| Cutout Size | 223×223mm | Standard cabinet mounting hole |
| Matériel | Air outlet grille: ASA+PC thermoplastic | Anti-aging, grey RAL 7035 |
| Poids | 1.14kilos | Stable installation, low resonance |
| Paramètres de performances | ||
| Classe de protection | IP54 | Dustproof and splashproof, suitable for outdoor cabinets |
| Bearing Type | Ball bearing | Longue durée de vie, faible bruit |
| Niveau de bruit | 50~51dB | Quiet operation, applicable near office areas |
| Max Static Pressure | 50Pa (0m³/heure) | Resists certain air resistance |
| Paramètres environnementaux | ||
| Température de fonctionnement | -20℃~60℃ | Wide temperature range for harsh environments |
| Température de stockage | -40℃~70℃ | Reliable transportation and storage |
| Attestation | ATTEINDRE, RoHS | Compliant with environmental standards |
- Liste des modèles de la série complète
| Modèle | Air Flow(m³/heure) | Tension | Configuration | Cutout Size(mm) | External Size(mm) |
| NSYCVF38M230PF | 39 | 230V et | Grille + Filtre | 117×117 | 137×137×85 |
| NSYCVF54M230PF | 54 | 230V et | Grille + Filtre | 148×148 | 170×170×92 |
| NSYCVF85M230PF | 85 | 230V et | Grille + Filtre | 170×170 | 190×190×95 |
| NSYCVF165M115PF | 165/193 | 115V et | Grille + Filtre | 223×223 | 268×248×104 |
| NSYCVF165M230PF | 165/193 | 230V et | Grille + Filtre | 223×223 | 268×248×104 |
| NSYCVF165M24DPF | 165/193 | 24À DC | Grille + Filtre | 223×223 | 268×248×104 |
| NSYCVF300M230PF | 300/350 | 230V et | Grille + Filtre | 262×262 | 300×300×110 |
| NSYCVF550M230PF | 550/650 | 230V et | Grille + Filtre | 336×336 | 380×380×120 |
| NSYCVF850M230PF | 838/980 | 230V et | Grille + Filtre | 400×400 | 450×450×130 |
| NSYCVF850M400PF | 838/980 | 400V et | Grille + Filtre | 400×400 | 450×450×130 |
- Cross-brand Replacement Comparison
| Marque | Modèle | Air Flow(m³/heure) | Tension | Classe de protection | Cutout Size(mm) | Avantages du remplacement |
| Rittal | 3239200 | 74/87 | 230V et | IP54 | 148×148 | Tool-free quick installation |
| Rittal | 3241700 | 160/190 | 230V et | IP54 | 223×223 | High-efficiency energy saving series |
| Stego | FK 66230 | 165/193 | 230V et | IP54 | 223×223 | Integrated temperature control, intelligent start-stop |
| Pfannenberg | 1041230 | 160/190 | 230V et | IP54 | 223×223 | Long filter service life, low maintenance frequency |
| RS PRO | 130-853 | 165/193 | 115V et | IP54 | 223×223 | Rentable, sufficient stock |
- Dépannage des pannes courantes & Entretien
| Phénomène de défaut | Causes possibles | Inspection Steps | Maintenance Solution |
| Fan not running | 1. Alimentation coupée | 1. Test power voltage | 1. Reconnect power supply |
| 2. Motor burnout | 2. Check motor winding resistance | 2. Replace identical motor | |
| 3. Stuck bearing | 3. Manually rotate fan blade | 3. Clean and lubricate bearing | |
| 4. Control circuit failure | 4. Inspect loose Faston connector | 4. Reconnect or replace connector | |
| Reduced airflow | 1. Clogged filter | 1. Check filter blockage | 1. Clean or replace G2 filter |
| 2. Dust accumulated on blades | 2. Inspect blade cleanliness | 2. Clean blades with soft brush | |
| 3. Sous-tension | 3. Measure operating voltage | 3. Adjust voltage to rated value | |
| 4. Reverse rotation | 4. Verify mounting direction | 4. Reinstall fan outward air discharge | |
| Abnormal noise | 1. Worn bearing | 1. Locate noise source | 1. Replace bearing or whole fan |
| 2. Unbalanced fan blade | 2. Check blade deformation and attachments | 2. Correct balance and clear debris | |
| 3. Loose mounting | 3. Tighten mounting screws | 3. Fasten all screws | |
| 4. Vibration resonance | 4. Observe cabinet vibration | 4. Add shock pad or adjust position | |
| Protection contre les surintensités | 1. Motor short circuit | 1. Test insulation resistance | 1. Replace motor |
| 2. Excessive bearing friction | 2. Check bearing flexibility | 2. Lubricate or replace bearing | |
| 3. Surtension | 3. Measure operating voltage | 3. Restore normal voltage |
- Environnement d'application & Cas industriels
Scénarios applicables
- Automatisation industrielle: Cooling for PLC, inverter and servo drive cabinets
- Système d'alimentation: Heat dissipation for outdoor ring main units, box substations and charging pile control boxes
- Telecommunication: Ventilation for base station cabinets, optical distribution boxes and data center server cabinets
- Transport ferroviaire: Temperature control for signal boxes and converter cabinets
- Nouvelle énergie: Cooling for photovoltaic inverters and energy storage control cabinets
Non-recommended Scenarios
- Corrosive atmosphere such as chemical and marine environment (anti-corrosion model required)
- Heavy dust sites like mines and cement plants (extra pre-filter needed)
- Submerged or long-term rain exposure (IP54 only splash-proof)
- Fully sealed space without air inlet circulation
Cas typiques
Automobile Factory: Installed on welding robot cabinets, failure rate reduced by 70% against high temperature
Power Grid Company: Eliminated switch misoperation, equipment service life extended 3 fois
Centre de données: Hierarchical cooling with air conditioner, energy consumption cut by 20%
- Conseils de sélection & Avoidance Guide
Quick Calculation Rule
- Airflow demand = Cabinet volume × (8~10) m³/heure, suitable for 16~20m³ cabinet
- Voltage selection: 230V for general industry, 115V for North America, 24V for DC system
- Mounting mark: M=side, MF=top, FB=bottom
Operation Warnings
- Inspect and replace G2 filter every 3 months to avoid airflow drop and motor overload
- Keep air outlet outward and match air inlet for effective ventilation
- Adopt cabinet air conditioner when external temperature is 5℃ higher than internal temperature
- Restrict voltage fluctuation within ±10% to guarantee service life
- Confirm UL, CE and other certifications for export use
- Order Information
Modèle: NSYCVF165M230PF
Numéro de commande: NSYCVF165M230PF (Global unified)
Package Contents: 1 axial fan motor, 1 cutting template, 1 pre-filter, 1 air outlet grille, 1 câble d'alimentation, 2 protective grilles
Delivery Lead Time: 3-5 working days for standard stock items