- Model Interpretation and Basic Information
| Item | Details |
| Complete Model | 3RT1024-1BB40 |
| Série de produits | Siemens SIRIUS 3RT1 Series (Discontinué, Replacement Model: 3RT2024-1BB40) |
| Structural Specification | 3-pôle, Size S0, Screw Termination, IP20 Protection Class |
| Tension de bobine | DC24V (24 Volt DC) |
| Main Contact Configuration | 3 Normalement ouvert (3NON) |
| Application Category | AC-3 (Three-Phase Motor Load) 12UN, 5.5kW/400V |
- Core Parameters of Thermal Current (Ith)
- Thermal Current of Main Contacts
| Current Type | Rated Value | Applicable Conditions | Remarques |
| AC-1 (Resistive Load) Thermal Current | 40UN | 690V et, 50/60HZ | Maximum allowable current for long-term operation |
| AC-3 (Motor Load) Courant nominal | 12UN | 400V et, 50/60HZ | Corresponding to 5.5kW three-phase motor |
| DC-1 (DC Resistive Load) Thermal Current | 12UN | 24À DC | Long-term operating current for DC circuits |
| DC-3 (DC Motor Load) Courant nominal | 8UN | 24À DC | Starting and operating current for DC motors |
- Thermal Current of DC24V Coil
| Paramètre | Valeur | Calculation Basis |
| Rated Coil Power | 5.9W | Siemens official data |
| Coil Thermal Current | 0.246UN | I = P/U = 5.9W/24V |
| Coil Resistance | Approx. 97.5 | R = U/I = 24V/0.246A |
| Coil Pick-Up/Holding Power | 5.9W for both | DC coil has the same pick-up and holding power |
III. Key Technical Characteristics
- Load Adaptation: Suitable for controlling ≤12A resistive load or ≤8A DC motor load in DC24V circuits
- Température de fonctionnement: -25°C ~ 60°C, adaptable to industrial environments
- Durée de vie mécanique: 3×10⁷ operations, Durée de vie électrique (AC-3): 1×10⁶ operations
- Insulation Voltage: 690V, reliable electrical isolation performance
- Replacement Models and Compatibility
Preferred Replacement Model: 3RT2024-1BB40 (Siemens SIRIUS 3RT2 Series)
Identical main contact and coil parameters, with an additional 1NO+1NC auxiliary contact
Compatible mounting dimensions for direct replacement
Other Compatible Models:
Schneider: LC1D12BD (DC24V, 12UN, 3NON)
ABB: A12-30-0124VDC (12UN, 3NON, DC24V)
- Usage Notes
- DC Circuit Application: When controlling DC24V circuits, derate the main contacts for use (≤12A resistive load) and install a surge suppressor (freewheeling diode) to protect the contacts
- Heat Management: Ensure adequate ventilation for the contacteur, avoid enclosed installation, and further derate the load when the ambient temperature exceeds 40°C (10% derating for every 10°C rise)
- Coil Protection: For the DC24V coil, pay attention to power supply fluctuations (allowable range: 21.6V~26.4V DC) to avoid burnout due to overvoltage
- Méthode de montage: Prend en charge le montage sur rail DIN standard de 35 mm ou le montage sur panneau, with no restriction on mounting direction
Résumé
For Siemens 3RT1024-1BB40 in DC24V circuits, the thermal current of the main contacts is 12A (charge résistive) and the thermal current of the DC24V coil is approximately 0.246A. This model has been discontinued, and it is recommended to use the replacement model 3RT2024-1BB40 as the first choice, which features better performance and an added auxiliary contact function.
Siemens 3RT1024-1BB40 Selection Quick Reference Table (DC24V/Thermal Current Special)
Scénarios applicables: Procurement Verification / On-Site Installation / Model Replacement / Parameter Review
| Module | Item | Rated Parameter/Core Information | Remarks/Applicable Conditions |
| Informations de base | Modèle de produit | 3RT1024-1BB40 | Siemens SIRIUS 3RT1 Series (Discontinué) |
| Tension de bobine | DC24V (Direct Current) | Consistent pick-up/holding power | |
| Configuration des contacts | 3-pole main contacts (3NON), no auxiliary contacts | IP20 protection, screw termination | |
| Structural Specification | Size S0, 35mm standard DIN rail mounting | No mounting direction restriction, panel/rail mountable | |
| Main Contact Current Parameters | AC-1 (Resistive Load) Thermal Current | 40A@690V AC/50/60Hz | Maximum allowable current for AC long-term operation |
| AC-3 (Motor Load) Courant nominal | 12A@400V AC/50/60Hz (5.5kW three-phase motor) | Rated for AC motor starting/operation | |
| DC-1 (Resistive Load) Thermal Current | 12A@24V DC | Core parameter for DC24V long-term operation (Key Point) | |
| DC-3 (Motor Load) Courant nominal | 8A@24V DC | Adapted for DC24V motor load | |
| DC24V Coil Parameters | Rated Power | 5.9W | Siemens official rating |
| Coil Thermal Current | 0.246UN | Calculation formula: I=P/U=5.9W/24V | |
| Coil Resistance | Approx. 97.5Ω | Calculation formula: R=U/I=24V/0.246A | |
| Allowable Voltage Range | 21.6V~26.4V DC (±10%) | Avoid coil burnout from over/undervoltage | |
| Life/Insulation | Durée de vie mécanique | 3×10⁷ operations | Industrial-grade durability |
| AC-3 Electrical Life | 1×10⁶ operations | Adapted for frequent motor start/stop | |
| Insulation Voltage | 690V CA/CC | Reliable electrical isolation performance | |
| Preferred Replacement Model | Modèle | 3RT2024-1BB40 (Siemens 3RT2 Series) | Original factory upgraded model, direct compatible replacement |
| Core Compatibility Points | Same main contact/coil/mounting dimensions as 3RT1024-1BB40 | No rewiring cost, direct replacement | |
| Upgrade Points | Added 1NO+1NC auxiliary contacts, improved protection/durability | First choice for cost performance | |
| Cross-Brand Compatible Models | Schneider | LC1D12BD | DC24V, 3NO main contacts, 12A@400V AC-3 |
| ABB | A12-30-01*24VDC | DC24V, 3NO main contacts, 12A@400V AC-3 | |
| Installation/Usage Key Points | Exigences d'installation | 35mm standard DIN rail, ventilated installation, avoid enclosure | Reduce temperature rise, ensure heat dissipation |
| DC Protection | Install a freewheeling diode on main contacts when controlling DC24V circuits | Suppress surges, prevent contact erosion | |
| Temperature Derating | 10% load current derating for every 10°C rise when ambient temperature >40℃ | par ex., DC24V resistive load ≤10.8A at 50℃ | |
| Température de fonctionnement | -25℃ ~ 60℃ | Adapted for industrial high/low temperature environments |
Key Highlighted Points: DC24V resistive load thermal current 12A, coil thermal current 0.246A, preferred replacement model 3RT2024-1BB40
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires