ABB MS116-4.0 Technical Datasheet (Manual Motor Starter / Interruttore automatico di protezione del motore)
Key Overview: 3-palo, rated current 4.0A (adjustable 2.5~4.0A), Class 10A tripping, 50kA/400V breaking capacity, suitable for 1.5kW/400V AC-3 motors, 45mm DIN-rail mounting, Protezione IP20, global order number 1SAM250000R1008.
- Spiegazione del modello
| Parte del modello | Descrizione |
| MS116 | ABB MS116 series compact 3-pole manual motor starter, integrated thermal-magnetic protection (sovraccarico + cortocircuito + mancanza di fase), fuse-free design |
| 4 | Rated operational current Ie = 4.0A, adjustable range 2.5~4.0A |
| 1SAM250000R1008 | Global order code |
| Dimensioni / Montaggio | Larghezza 45 mm, standard 35mm DIN rail mounting, IP20 degree of protection |
- Core Electrical & Mechanical Data
2.1 Di base & Protection Parameters
| Parametro | Valore | Descrizione |
| Numero di poli | 3-palo | For three-phase motor protection |
| Rated current Ie | 4.0UN | Adjustable range 2.5~4.0A |
| Tripping class | Class 10A | Typical motor tripping characteristic; trips in approx. 10 s at 10 overload current |
| Protezione da cortocircuito | 50UN (fisso) | Instantaneous magnetic trip, no extra fuse required |
| Breaking capacity Ics | 50IL (400V e) | Rated service short-circuit breaking capacity |
| Tensione nominale | 690V e, 50/60Hz | Suitable for various voltage systems |
| Applicable power (AC-3) | 1.5kW (400V) / 2 hp (480V) | For standard motor duty |
| Funzioni di protezione | Temperature compensation, fuse-free protection, free tripping mechanism, funzione di isolamento, protezione dalla mancanza di fase | Comprehensive motor protection, IEC compliant |
2.2 Meccanico & Mounting Data
Parametro Valore Larghezza 45mm Altezza 90mm Profondità 85.6mm Peso 0.225kg Montaggio Guida DIN standard da 35 mm (TH35-15/TH35-7.5) Connessione Morsetti a vite, main circuit torque 0.8~1.2Nm Operation Maniglia rotante (clear ON/OFF indication), free tripping mechanism Grado di protezione IP20 (anteriore) Consumo energetico 5.4W Temperatura ambiente -25C≈+55C Guida alla selezione
3.1 Applicazioni tipiche
Direct starting and protection of small three-phase motors (1.5kW/400V)
Control of pumps, tifosi, compressors and industrial automation equipment
Replacement of traditional “fuse + contactor” combinations to save space and cost
Applications requiring manual control and reliable motor protection
3.2 Selection Steps
- Verify motor rated current: within 2.5~4.0A adjustable range
- Check motor power: ≤ 1.5kW (400V AC-3)
- Confirm system voltage: ≤ 690V AC, 50/60Hz
- Evaluate short-circuit current: system short-circuit current ≤ 50kA (400V)
- Installation space: reserve 45mm DIN rail width
- Ambient conditions: temperature -25°C ~ +55°C, no excessive vibration or corrosive gas
3.3 Setting & Note operative
Protezione da sovraccarico: set to 1.0~1.1 × motor rated current (within 2.5~4.0A)
Ensure reliable phase failure protection for all three-phase motor applications
Use isolation function: safe electrical isolation after shutdown for maintenance
Can be used with contactors for remote control and automatic protection
- Cross-Brand Replacement Models
| Marca | Modello | Parametri principali | Differenze |
| Schneider | GV2ME08 | 3-palo, 2.5~4.0A, Classe 10, 50kA/400V | Stessa larghezza (45mm), functionally compatible, sostituzione diretta |
| Siemens | 3RV2011-0JA10 | 3-palo, 2.5~4.0A, Classe 10, 50kA/400V | Matching mounting dimensions, compatible protection characteristics |
| Eaton | PKZM0-4 | 3-palo, 2.5~4.0A, Classe 10, 50kA/400V | Functionally and dimensionally compatible, conveniente |
| ABB Upgrade | MS132-4.0 | 3-palo, 2.5~4.0A, Classe 10, 100kA/400V | Maggiore potere di interruzione, backward compatible mounting |
- Note applicative
- Thermal-magnetic characteristics: Class 10A is intended for standard squirrel-cage motors; not recommended for special loads (per esempio., trasformatori, capacitors)
- Phase failure protection: Trips within 2~5 seconds if any phase is lost, effectively preventing motor burnout
- Fuse-free design: Eliminates external fuses, reduces cost and maintenance; ensure line short-circuit current ≤ 50kA