NV = Earth Leakage Circuit Breaker (BELCB); 250 = 250AF frame size; SV = Standard breaking capacity (Classe S); 3P = 3-pole; In=250A; AC-type electronic residual current circuit breaker
✅ Core Technical Parameters
Dimensioni del telaio: 250DI, rated current 250A
Poli: 3P (3-palo, 3-fase 3 fili)
Tensione operativa nominale Ue: AC100~440V (compatible with AC380/400/415V)
Insulation voltage Ui: 440V; impulse withstand voltage Uimp: 6kV
Potere di interruzione (AC400V): Icu=Ics=36kA
Earth leakage sensitivity: 3 adjustable levels: 100/200/500mA (select Instantaneous / Time-delayed type when ordering)
Unità di sgancio: Viaggio magnetotermico (sovraccarico + protezione da cortocircuito) + electronic residual current protection
Standard: IEC60947-2, GB/T14048.2, Certificato CE
Dimensioni: W105mm × H165mm × D92mm; standard front wiring
Frequenza: 50/60Hz
📌 Model Code Breakdown
NV: Earth Leakage Circuit Breaker (BELCB); NF = non-leakage standard MCCB
250: 250Una dimensione del telaio
SV: S-class Standard breaking capacity; other variants: CV (economic low breaking), alta tensione (elevato potere di interruzione, 50IL)
3P: 3-palo; 4P version available
Suffisso: J = Instantaneous trip; D = Time-delayed trip (for selective protection against upstream tripping)
🧩 Optional Accessories (Interchangeable within the series)
Auxiliary switch (ASCIA), Alarm switch (AL), Viaggio di derivazione (SHT), Intervento per sottotensione (UVT), Maniglia rotativa estesa, Rear terminal blocks, Terminal safety covers
📋 Model Selection & Opzioni di sostituzione
- Upgraded model within the same series: NV250-SEV (new WS-V generation, electronic adjustable overload trip, Certificato CCC, mainstream stock model for domestic projects)
- High breaking capacity same-frame variant: NV250-HV (Icu=50kA @ AC400V)
- Nota: NV250-SV is an older imported model; NV250-SEV is the domestic mainstream stock model. Direct replacement requires verification of leakage current range, mounting dimensions and accessory interfaces.
- Riferimento alternativo domestico: Chint NM1LE-250S, Delixi CDM1LE-250 (similar breaking capacity and leakage logic, but cabinet cutout and accessories are not interchangeable)
⚠️ Application & Suggerimenti per la risoluzione dei problemi
Scenari applicativi: Main incoming feeders in 3-phase power cabinets, tifosi, water pumps and production lines, with integrated overload, short-circuit and earth fault protection.
3P version only detects 3-phase leakage; single-phase 220V loads with neutral wire are not allowed. Select 4P if single-phase loads exist.
Common fault: Intervento immediato dopo la chiusura. First distinguish between earth leakage trip (leakage indicator pops out) and overload/short-circuit trip. Adjust leakage setting to 500mA to avoid tripping caused by normal equipment residual current.
Maintenance test: Press the built-in leakage test button regularly to verify the residual current function.
📎 Complete Ordering Example
NV250-SV 3P 250A 100/200/500mA J (Tipo istantaneo)
Tabella comparativa: NV250-SV / NV250-SEV / NV250-HV (250AF frame, 3P 250A, AC-type ELCB)
All belong to WS-V series; dimensioni di montaggio, cabinet cutouts and accessory interfaces are fully interchangeable for direct in-situ replacement.
Differenze fondamentali: unità di sgancio, breaking capacity and market positioning.
| Articolo | NV250‑SV | NV250‑SEV | NV250‑HV |
| Posizionamento | Older standard breaking model, viaggio magnetotermico | New domestic mainstream model, standard breaking, electronic adjustable overload trip | High breaking model, viaggio magnetotermico |
| Icu/Ics @ AC400V | 36IL / 36IL | 36IL / 36IL | 50IL / 50IL |
Full Model List of Mitsubishi WS-V Series MCCB
- NF (Standard MCCB without earth leakage) & NV (ELCB with earth leakage) — Small & Cornici medie (32~250AF)
(1) 32Cornice AF
NF (MCCB): NF32-SV (only S-class available)
NV (BELCB): NV32-SV
(2) 63Cornice AF
NF: NF63-CV (economico), NF63-SV (standard), NF63-HV (rottura elevata)
NV: NV63-CV, NV63-SV, NV63-HV
(3) 125Cornice AF (Il più utilizzato)
- Thermal-magnetic fixed trip: NF125-CV, NF125-SV, NF125-HV
- Electronic adjustable trip: NF125-SEV, NF125-HEV
- Current-limiting type: NF125-UV, NF125-RV
NV Earth Leakage Breakers: NV125-CV, NV125-SV, NV125-HV, NV125-SEV, NV125-HEV
(4) 250Cornice AF (Your current model frame)
NF Standard MCCB (No leakage protection)
Magnetotermico: NF250-CV, NF250-SV, NF250-HV
Electronic adjustable: NF250-SEV, NF250-HEV
Limitazione di corrente: NF250-RV, NF250-UV
NV Earth Leakage Circuit Breakers (BELCB, including NV250-SV)
NV250-CV (economic version)
NV250-SV (standard general model, your selected type)
NV250-HV (elevato potere di interruzione, 50IL)
NV250-SEV (electronic adjustable overload)
NV250-HEV (viaggio elettronico + elevato potere di interruzione)
Leakage current settings: 100/200/500mA 3-level adjustable; J=Instantaneous, D=Time-delayed.
- Large Current Frames (400~4000AF, Traditional WS Series)
- 400DI: NF400-CW / SW / HW; NV400-CW / SW / HW
- 630DI: NF630-CW / SW / HW; NV630-CW / SW / HW
- 800~4000AF: NF800~NF4000, NV800~NV4000 (only thermal-magnetic trip; suffix = CW/SW/HW, no SV suffix)
III. Universal Accessory Cross Reference (32/63/125/250DI)
| Dimensioni del telaio | Auxiliary Switch AX | Alarm Switch AL | Shunt Trip SHT | Undervoltage Trip UVT | Locking Cover |
| 32DI | ASCIA-05SV | AL-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 63DI | ASCIA-05SV | AL-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 125DI | AX-1SV | AL-1SV | SHT-1SV | UVT-1SV | LC-1SV |
| 250DI | ASCIA-05SV | AL-05SV | SHT-05SV | UVT-05SV | LC-2SV |
Conclusione: All accessories for NV250-SV are fully compatible with NF250-CV/SV/HV/SEV/HEV and can be retrofitted on site without factory modification.
- UL Export Models (Suffix U)
NF125-SVU / HVU; NF250-CVU / SVU / HVU
NV125-SVU / HVU; NV250-CVU / SVU / HVU
- Full Ordering Format
- Tipo standard: NV250-SV 3P 250A J 100/200/500mA (Viaggio istantaneo)
- Selective protection type: NV250-SV 3P 250A D (Time-delayed leakage trip)
- Full set with accessories: NV250-SV 3P 250A + AX+AL+SHT(AC220V)+UVT(AC380V)
- Old-to-New Model Replacement (WS → WS-V Series)
Old model NF250-SGW → New model NF250-SV
Old model NV250-SW → New model NV250-SV
Dimensioni, cutouts and accessories are 1:1 interchangeable with no cabinet modification required
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore



















NH42-63-318x560.png)