Parameter ItemSpecification
Rated Insulation Voltage690V
Tensione di funzionamento nominaleAC 230/240V, 400/415V, 440V, 500V, 690V
Frequenza nominale50/60Hz
Setting Current Range4~6.3A
Instantaneous Electromagnetic Trip Current78UN (circa 12 times the setting current)
Short-Circuit Breaking CapacityIcu=100kA, Ics=7.5kA (at AC400V)
Protection ClassIP20 (front side)
Operating Frequency≤30 times/hour
Applicable Ambient Temperature-5℃~+40℃
PesoApproximately 313g

  • Dettagli del prodotto

Chint NS2-25/4-6.3A is a starter protection switch specifically designed for three-phase squirrel-cage induction motors. It integrates the functions of a interruttore automatico and a thermal relay, providing overload protection, phase failure protection, protezione da cortocircuito, and infrequent starting control.

Model Interpretation:

NS2: Series code (N stands for Chint, S stands for Starter)

25: Frame current rating (25UN)

4-6.3UN: Rated current range of the trip unit (adjustable within 4-6.3A)

  1. Parametri tecnici fondamentali
Parameter ItemSpecification
Rated Insulation Voltage690V
Tensione di funzionamento nominaleAC 230/240V, 400/415V, 440V, 500V, 690V
Frequenza nominale50/60Hz
Setting Current Range4~6.3A
Instantaneous Electromagnetic Trip Current78UN (circa 12 times the setting current)
Short-Circuit Breaking CapacityIcu=100kA, Ics=7.5kA (at AC400V)
Protection ClassIP20 (front side)
Operating Frequency≤30 times/hour
Applicable Ambient Temperature-5℃~+40℃
PesoApproximately 313g

III. Caratteristiche funzionali

  1. Multiple Protection Functions

Overload Protection: Built-in bimetallic thermal element acts when the current exceeds the setting current for a certain period, preventing motor burnout due to overheating.

Phase Failure Protection: Detects the loss of any phase in the three-phase power supply and immediately cuts off the circuit to protect the motor.

Short-Circuit Protection: Instantaneous electromagnetic trip unit operates rapidly (≤100ms) when the current reaches 78A, preventing the expansion of short-circuit faults.

Isolation Function: Can be used as an isolating switch to ensure maintenance safety.

  1. Control Functions

Integrates start/stop button control with a compact structure.

Supports 35mm standard DIN rail mounting for quick deployment.

Optional accessories available: Undervoltage Trip (UV), Shunt Trip (SH), Auxiliary Contact (AE/AU), Fault Signal Contact (FA).

  1. Scenari applicativi

NS2-25/4-6.3A is suitable for:

Protection and control of three-phase induction motors with a power of approximately 2.2kW (400V).

Control of small and medium-sized motors in factories and workshops, come i tifosi, pompe dell'acqua, trasportatori, compressori, and other equipment.

Motor control cabinets in building automation systems.

Can replace the traditional circuit breaker + thermal relay combination scheme, saving space and costs.

  1. Precauzioni per l'uso
  2. Installation Requirements

Install vertically with an inclination angle ≤±5° to ensure reliable operation.

The tightening torque for the terminal screws (M4) is 1.7N·m; avoid over-tightening to prevent thread damage.

Recommended wire cross-sectional area: 1~6mm², wire stripping length: 10mm.

  1. Parameter Setting

Setting Current: Should be adjusted to 1.05~1.1 times the motor’s rated current to ensure protection sensitivity and avoid false tripping.

When the ambient temperature deviates significantly from 25℃, adjust the setting current according to the temperature compensation characteristic table.

  1. Operating Restrictions

Do not operate beyond the rated voltage or frequency.

The operating frequency shall not exceed 30 times/hour; frequent operation will shorten the service life.

It is strictly prohibited to disassemble or replace parts with live electricity; the power supply must be cut off first and confirmed to be de-energized.

  1. Selection Reference

To select the appropriate NS2 series product for your motor:

  1. First determine the motor’s rated current.
  2. Choose a model whose setting current range includes the motor’s rated current.
  3. Motor power reference: NS2-25/4-6.3A is suitable for motors with a power of approximately 2.2kW (400V).
  4. In systems with high-order harmonics such as inverter power supply, it is recommended to select the specification according to 1.3~1.9 times the motor’s rated current.

Riepilogo

Chint NS2-25/4-6.3A is a reliable-performance motor starter protection switch that integrates protection and control functions. It is particularly suitable for three-phase induction motors of around 2.2kW. Not only can it effectively protect motors from overload, phase failure, and short-circuit damage, but it also simplifies the design of control systems, making it an ideal choice in the field of industrial electrical control.

Prec:

Prossimo:

Lascia una risposta

Lasciate un messaggio