DPSN250A-Honeywell Air Differential Pressure Switch

  Code Segment Meaning Remarks DPSN Product series code Honeywell Air Differential Pressure Switch series 250 Range identifier The actual standard model is 200 (20~200Pa); 250 is likely a typo A Version code Standard version, no special functions HONEYWELL Brand Honeywell (NOI. industrial automation giant) Core Specification Parameters Basic Parameters Parameter Value Description Product Type Air Differential ...

  • Dettagli del prodotto

 

Segmento di codiceSensoOsservazioni
DPSNCodice serie prodottoHoneywell Air Differential Pressure Switch serie
250Range identifierThe actual standard model is 200 (20~200Pa); 250 è probabilmente un errore di battitura
UNCodice della versioneVersione standard, no special functions
HONEYWELLMarcaHoneywell (NOI. industrial automation giant)
  1. Parametri delle specifiche principali

Parametri di base

ParametroValoreDescrizione
Tipo di prodottoAir Differential Pressure SwitchUsed for monitoring duct filters, fan operation and airflow status
Intervallo di pressione20~200 PaStandard DPSN200A adjustable range
Switch Differential Pressure10 Pa (average)Pressure difference between actuation and reset
Max Working Pressure10,000 Pa (10 kPa)Ultimate withstand pressure
Precisione≤±15%Measurement accuracy
Measured MediumAir, non-flammable and non-corrosive gasNot applicable for other media

Parametri Elettrici

ParametroValoreDescrizione
Switch Rating1.5 UN (0.4 UN)/250 VCARated electrical load capacity
Collegamento elettricoAMP connector or screw terminalTwo optional connection methods
Protezione dall'ingressoIP54Dustproof and splashproof, adatto per ambienti industriali
CertificazioneCECompliant with European safety standards

Meccanico & Parametri Ambientali

ParametroValoreDescrizione
Pressure Port Connection2 plastic tubes, 6 mm diameterFor connecting pressure sampling tubes
Cable Gland SizeCM = M20 × 1.5Cable interface dimension
Diaphragm MaterialSiliconeSensing element material
Vita meccanica>1,000,000 cicliHigh durability
Temperatura operativa-20℃ to 85℃Ampio intervallo di temperature
Temperatura di conservazione-40℃ to 85℃Storage ambient condition
Dimensione complessivaØ85.5 mm × 107 mmRound structure for easy installation
Mounting Holes4-ϕ3.6 mmFixing mounting holes
  1. Elenco degli accessori
Nome dell'accessorioQuantitàScopo
PVC Pressure Hose2 metriConnect differential pressure switch to air duct
Pressure Sampling Tube2 pzConnect pressure ports
Mounting Screws5 pzFix mounting bracket and main unit
L-type Mounting Bracket1 pcSupport multiple installation angles
Installation Manual1 copyGuide correct installation and commissioning
  1. Concorrente & Cross-Brand Replacement Comparison
MarcaModelloDifferenza principaleScenario applicativo
HoneywellDPSN200A (Modello standard)Original genuine, ±15% accuracy, IP54 protectionAll applications requiring DPSN250A
HoneywellDPS200Same series standard type, slight structural differenceGeneral air duct monitoring
Johnson ControlsP74JA-1Pressure range 15~200Pa, ±10% accuracyHVAC systems with high precision requirements
SiemensQBM81-3Adjustable range 0~500Pa, IP54Matching Siemens building automation systems
Schneider ElectricA9F7220020~200Pa range with LED indicatorApplications requiring status visualization
  1. Linee guida per la selezione & Soluzioni sostitutive
  2. Parametri di selezione chiave

Confirm Pressure Range: Select according to actual duct differential pressure (20~200Pa for general filter monitoring)

Electrical Load Matching: Ensure switch rating meets control loop current requirement (≤1.5A/250VAC)

Ambiente di installazione: IP54 suitable for non-humid industrial environments; additional protection required for outdoor use

Metodo di connessione: Choose AMP connector or screw terminal based on site wiring requirements

  1. Soluzioni sostitutive consigliate

Sostituzione diretta dell'OEM: Prioritize DPSN200A (modello standard) to avoid model confusion

Range Expansion: For higher pressure requirements, select DPSN400A (40~400Pa) or DPSN1000A (200~1000Pa)

Function Upgrade: Choose alternative models with LED status indicator for convenient on-site diagnosis

Cost-Effective Alternative: Domestic brands such as Chint and Delixi, price about 1/3~1/2 of OEM, performance meets general applications

  1. Precauzioni per l'installazione
  2. Vertical mounting is standard; range value increases by 20Pa when mounted horizontally
  3. Avoid bending pressure sampling tubes; maximum length no more than 2 metri
  4. Connect pressure port +P1 to high-pressure side, -P2 to low-pressure side
  5. Electrical wiring shall comply with safety regulations to prevent short circuit

Honeywell Air Differential Pressure Switch Model List & Guida alla selezione

  1. Product Series Overview

Honeywell air differential pressure switches are mainly divided into 4 core series, covering general HVAC to heavy-duty industrial applications. All feature high reliability, long service life and IP54 ingress protection, suitable for duct filter monitoring, fan status detection and airflow control.

SeriePosizionamentoCaratteristiche strutturaliApplicazioni tipiche
DPS SeriesGeneral Air Differential Pressure SwitchStandard round design, manually adjustableCommercial building HVAC, filter monitoring
DPSN SeriesEconomy Air Differential Pressure SwitchSimplified design, cost optimizedOrdinary ventilation systems, basic filter monitoring
DPSP SeriesHigh Precision Air Differential Pressure SwitchPrecision adjustment, low hysteresisCamere pulite, laboratori, strutture mediche
AFS SeriesAirflow Proof SwitchUsed with sampling tubes, measures positive/negative pressureFire smoke exhaust system, damper status monitoring
  1. Detailed Model List by Series
  2. DPS Series (Standard Air Differential Pressure Switch)

Caratteristiche principali: Manually adjustable setpoint with Pa scale dial, 180° rotatable pipe inlet, CE certified, IP54 protection

ModelloIntervallo di pressione (Pa)Switch Differential (Pa)Max Working Pressure (Pa)Scenario applicativo
DPS 20020~2001010,000General filter, small fan
DPS 40040~4002010,000Medium filter, fan status
DPS 1000200~10005010,000Large air duct, high wind speed system
DPS 2500500~250015010,000High differential pressure system, industrial ventilation
DPS 200A20~2001010,000Standard type with AMP connector
DPS 400A40~4002010,000Standard type with AMP connector
DPS 1000A200~10005010,000Standard type with AMP connector
DPS 2500A500~250015010,000Standard type with AMP connector
  1. DPSN Series (Economy Air Differential Pressure Switch)

Caratteristiche principali: Simplified structure, conveniente, manual adjustment and IP54 protection, ideal for budget-sensitive projects

ModelloIntervallo di pressione (Pa)Switch Differential (Pa)Collegamento elettricoOsservazioni
DPSN 200A20~20010AMP / Screw TerminalMost common model, replaces DPSN250A
DPSN 400A40~40020AMP / Screw TerminalMedium system application
DPSN 1000A200~100050AMP / Screw TerminalLarge air duct monitoring
DPSN 2500A500~2500150AMP / Screw TerminalHigh differential pressure industrial use
  1. DPSP Series (High Precision Air Differential Pressure Switch)

Caratteristiche principali: Maggiore precisione (≤±10%), lower switch differential pressure, suitable for strict pressure control scenarios

ModelloIntervallo di pressione (Pa)PrecisioneSwitch Differential (Pa)Scenario applicativo
DPSP 10010~100≤±10%5Camere pulite, laboratori
DPSP 20020~200≤±10%8Medical facilities, precision air conditioning
DPSP 50050~500≤±10%15Pharmaceutical industry, electronic workshops
  1. AFS Series (Airflow Proof Switch)

Caratteristiche principali: Detects positive / negative / differential pressure; used with sampling tubes for fire protection and energy management systems

ModelloIntervallo di pressione (Pa)Reset ModeApplication Features
AFS 10025~100Manuale / AutoDamper status monitoring
AFS 20050~200Manuale / AutoFire smoke exhaust system
AFS 500100~500Manuale / AutoAirflow proof for large ventilation systems
  1. Special Application Series

DPSL Series: Liquido & Gas dual-purpose differential pressure switch, suitable for neutral / slightly corrosive liquids and non-flammable gases, can be used as flow switch

ModelloIntervallo di pressioneMedium TypeProtezione dall'ingresso
DPSL 060.2~6 barLiquido / GasIP65
DPSL 160.5~16 barLiquido / GasIP65
DPSL 401~40 barLiquido / GasIP65
  1. Spiegazione della regola di denominazione del modello

Honeywell air differential pressure switch model consists of Series Code + Allineare + Version Code, clearly reflecting core parameters:

Segmento di codiceSensoEsempio
DPS/DPSN/DPSP/AFSCodice della serieDPS=Standard, DPSN=Economy, DPSP=High Precision, AFS=Airflow Proof
200/400/1000/2500Range identifier200=20~200Pa, 400=40~400Pa, 1000=200~1000Pa, 2500=500~2500Pa
UNCodice della versioneStandard version with AMP connector, screw terminal optional
Numeric SuffixFunzione specialeper esempio. 06 in DPSL 06 means max 6 bar range
  1. Core Specification Comparison Table

General Electrical Parameters (All Series)

ParametroValoreDescrizione
Switch Rating1.5 UN (0.4 UN)/250 VCARated electrical load capacity
Collegamento elettricoAMP connector or screw terminalTwo optional connection methods
Protezione dall'ingressoIP54Dustproof and splashproof for industrial environments
Temperatura operativa-20℃ to 85℃Ampio intervallo di temperature
Temperatura di conservazione-40℃ to 85℃Storage ambient condition
Vita meccanica>1,000,000 cicliHigh durability
Pressure Port Connection2 plastic tubes, 6 mm diameterFor pressure sampling tube connection
Cable Gland SizeCM = M20 × 1.5Cable interface dimension

Series Range & Accuracy Comparison

SerieTypical Range (Pa)PrecisioneSwitch Differential (Pa)Scenario applicabile
DPS20~2500≤±15%10~150General HVAC systems
DPSN20~2500≤±15%10~150Economy HVAC systems
DPSP10~500≤±10%5~15High precision control occasions
AFS25~500≤±15%10~30Airflow proof & fire protection systems
  1. Linee guida per la selezione & Soluzioni sostitutive
  2. Parametri di selezione chiave

Pressure Range Matching: Select based on actual duct differential pressure (20~200Pa for filter monitoring; 40~400Pa for large fans)

Accuracy Requirement: ≤±15% for general use (DPS/DPSN); ≤±10% for high precision (DPSP)

Electrical Load: Ensure switch rating meets control loop current (≤1.5A/250VAC)

Ambiente di installazione: IP54 for non-humid industrial areas; extra protection required for outdoor installation

Metodo di connessione: Select AMP connector or screw terminal according to site wiring

  1. Recommended Replacement Table
Modello originaleSostituzione direttaFunction Upgrade ModelBudget Alternative
DPSN250ADPSN200A (Standard)DPSP200 (Alta precisione)Domestic Chint / Delizioso
DPS200DPS200A (With AMP Connector)DPSP200 (Alta precisione)Johnson Controls P74JA-1
DPS400DPS400ADPSP500Siemens QBM81-3
DPS1000DPS1000ADPSP500Schneider A9F72200
  1. Precauzioni per l'installazione
  2. Vertical mounting is standard; horizontal mounting will increase range value by 20Pa
  3. Avoid bending sampling tubes; length shall not exceed 2 metri
  4. Connect +P1 to high-pressure side, -P2 to low-pressure side
  5. Electrical wiring must comply with safety standards to avoid short circuit
  6. Adjust setpoint only after system runs stably to ensure accurate measurement
  7. Domande frequenti
  8. Difference between DPSN250A and DPSN200A: DPSN250A is non-standard; the actual standard model is DPSN200A (20~200Pa), 250 è un errore di battitura.
  9. How to choose the correct range: 20~200Pa for filter monitoring; 40~400Pa for fan status; 200~1000Pa or higher for large industrial ducts.
  10. IP54 Protection Definition: Dust-tight and protected against splashing water, suitable for indoor industrial environments.

Prec:

Lascia una risposta

Lasciate un messaggio