Trasduttore di isolamento di tensione CC FRER MCOMV 48VDC

Marca: FRATELLO (Italia) Modello completo: MCOMV, Input 0~48VDC, DIN rail mounted DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition. Parametri fondamentali (MCOMV;48VCC) Ingresso: 0 ~ 48V DC (50% capacità di sovraccarico) Produzione: 0~20mA / 4~20mA (Standard industrial current loop) Max Output Load: 750Ω Auxiliary Supply: 20~60Vac/dc ...

  • Dettagli del prodotto

Marca: FRATELLO (Italia)

Modello completo: MCOMV, Input 0~48VDC, Montaggio su guida DIN DC voltage isolation transducer. It converts DC voltage signal into standard 4-20mA analog signal for PLC/DCS system acquisition.

Parametri fondamentali (MCOMV;48VCC)

Ingresso: 0 ~ 48V DC (50% capacità di sovraccarico)

Produzione: 0~20mA / 4~20mA (Standard industrial current loop)

Max Output Load: 750OH

Auxiliary Supply: 20~60Vac/dc (Wide AC/DC power supply); 220VDC version available as option

Isolamento: Input-Output-Power three-way galvanic isolation

Montaggio: DIN rail snap mounting

Classe di precisione: 0.5

Tempo di risposta: <200SM

Applicazione: DC busbar, battery pack, -48V telecom power cabinet voltage measurement

Definizione del modello

MCOMV: FRER legacy model code for DC voltage transducer; new replacement series MCOVC

;48VCC: Input range 0~48V DC

Other ranges available in same series: MCOMV;60mV DC, MCOMV;60VCC, MCOMV;300VCC

Applicazioni tipiche

  1. -48V battery bank voltage monitoring for telecom base stations
  2. Pannello CC & energy storage cabinet DC bus voltage acquisition
  3. Industrial power supply & electrochemical power source voltage transduction
  4. DC system signal isolation measurement in power plants & fabbriche

Modelli sostitutivi

Original manufacturer upgrade: MCOVC1 (for MCOMV 0~300V), MCOVC2 (Dual retransmission output)

Alternative domestiche: Contatto della Fenice, Pepperl+Fuchs, Suzhou Xunpeng and other DC voltage isolation transducers (0-48Ingresso V, 4-20mA output)

Linee guida per il cablaggio

  1. Input side: DC voltage signal, observe polarity strictly
  2. Output side: 4-20mA current loop, connect to AI module, normally 2-wire connection at PLC side
  3. Potenza ausiliaria: 20~60V AC/DC wide range, compatible with 24V/48V DC panel & AC220V

Distinzione importante: MCOV (SPD maximum continuous operating voltage) ≠ MCOMV (FRER transducer). Abbreviation confusion frequently occurs.

FRER MCOMV;48VDC Complete Datasheet Parameter Table

Prodotto: DC voltage isolation transducer (Obsolete legacy MCOMV, replacement series MCOVC)

Definizione del modello: MCOMV = DC voltage transducer; ;48VDC = Input range 0~48VDC

🔹 Electrical Specifications

ParametroValoreOsservazioni
Intervallo di ingresso0 ~ 48 VCCModel MCOMV;48VCC
Continuous Overload1.5 × Un (50% sovraccarico)Permanent withstand up to 72VDC
Transient Overload2 × UnShort-term max 96VDC
Impedenza di ingresso≥100kΩHigh impedance, minimal loading effect on measured circuit
Segnale di uscita4~20mA DC (Standard current loop); 0~20mA opzionaleSingle analog output
Max Output Load Resistance750 OHHigher load requires more auxiliary power margin
Classe di precisione0.5Max full scale error ≤ ±0.5%FS at 25℃ reference
Linearity Error≤ ±0.2% FS
Deriva della temperatura≤ ±100 ppm/℃Over full operating temperature range
Tempo di risposta<200 SM (95% step response)
Tensione di tenuta dielettrica (Input ↔ Output ↔ Aux. Fornitura)2.5kV CA / 1minThree-way galvanic isolation, safety isolation
Auxiliary Supply20~60V AC/DC wide rangeAC/DC universale; 220V DC customized version available
Consumo energetico≤1.5W

🔹 Environmental Conditions

ParametroValore
Temperatura operativa-20℃ ~ +50 ℃
Temperatura di conservazione-40℃ ~ +80 ℃
Umidità relativa5%~95%, senza condensa
Grado di inquinamentoClasse 2
Overvoltage CategoryCAT III

🔹 Mechanical & Allegato

ParametroValore
MontaggioDIN 35mm rail snap mounting
Enclosure MaterialFlame retardant plastic
Protezione della custodiaIP20 (corpo); Terminal block IP00
Dimensione complessivaW22.5mm × H90mm × D68mm (Narrow standard module)
Pesoca. 80G
TerminaliMorsetti a vite, max conductor cross-section 2.5mm²

🔹 Model Portfolio (Available Ranges of MCOMV Series)

Codice modelloIntervallo di ingresso
MCOMV;60mV DC0~60mV DC
MCOMV;48VCC0~48V DC
MCOMV;60VCC0~60V DC
MCOMV;300VCC0~300V DC

🔹 Safety & Standard

Certificazione: CE, Conforme alla norma EN 61010-1

Protezione: Output current limiting, limited reverse polarity protection for input

Categoria di applicazione: Industrial DC busbar, telecom -48V battery pack, DC panel voltage acquisition

🔹 Wiring Summary

  1. Ingresso + / Ingresso -: Measured DC voltage, strict polarity observation required
  2. Produzione + / Produzione -: 4~20mA current loop, two-wire connection to PLC AI channel
  3. A + / A -: Transducer auxiliary power supply 20~60V AC/DC

🔹 Model Change Note

MCOMV is legacy FRER code, interrotto. Direct OEM replacement: MCOVC1 (single channel DC voltage transducer) with identical specs, pin assignment and mounting dimension.

🔹 Troubleshooting Reference

  1. Nessuna uscita: Check auxiliary power, tenuta terminale, input polarity
  2. Uscita fissa da 4 mA: Ingresso circuito aperto o segnale inferiore al limite inferiore
  3. Uscita bloccata a 20 mA: Cablaggio di ingresso fuori gamma o in cortocircuito
  4. Deriva della lettura: Controllare l'interferenza di terra e verificare l'integrità dell'isolamento

FRER MCOMV;48Descrizione della calibrazione VDC

Conclusione: La calibrazione metrologica è disponibile per la certificazione; Nessun potenziometro di regolazione zero/span esterno sull'unità. Sono vietate l'apertura e la regolazione in loco dello zero/intervallo. È un trasduttore di isolamento analogico calibrato in fabbrica.

  1. Classe di precisione & Differenziazione della calibrazione

Targhetta contrassegnata con Classe 0.5: Errore di fondo scala massimo consentito ±0,5%FS nella condizione di riferimento 25℃.

✅Calibrazione metrologica (Consentito):

Utilizzare una fonte di tensione CC standard + milliamperometro ad alta precisione per test comparativi multipunto a 0%, 25%, 50%, 75%, 100%. Può essere inviato a un laboratorio metrologico di terze parti per il certificato di calibrazione, per verificare se la prestazione rimane all'interno della Classe 0.5.

❌ Rifilatura in loco (Not Supported):

No external Zero / Span access hole on MCOMV legacy housing; PCB trim potentiometers are factory locked. Manufacturer does NOT recommend opening housing for on-site adjustment. Opening voids factory warranty and damages insulation isolation structure, degrading 2.5kV isolation safety rating.

  1. Calibration Test Procedure (Lab / Site Comparison, Test Only, No Adjustment)

DUT: MCOMV;48VCC (0~48VDC Input →4~20mA Output)

  1. Connect auxiliary power 20~60V DC, warm up ≥15 minutes
  2. Apply DC voltage sequentially via standard source: 0V, 12V, 24V, 36V, 48V

0V → Theoretical output 4.000 mA

48V → Theoretical output 20.000 mA

  1. Insert high precision milliammeter in series into current loop, record As-Found error for each point
  2. Pass Criterion: Error ≤ ±0.5%FS for all test points

Full scale span: 16mA corresponds to 48V; 1%FS = 0.16mA

  1. Remedial Actions If Drift Exceeds Tolerance

If calibration shows error out of Class 0.5 tolleranza:

  1. Preferibile la sostituzione (MCOMV interrotto). Aggiornamento consigliato MCOVC1;48VCC, spillo & dimensione compatibile;
  2. Restituire alla fabbrica FRER per la ricalibrazione (costo elevato & lungo tempo di consegna);
  3. Trasduttori alternativi domestici: Dotato di potenziometro Z/S esterno, campo zero & regolazione della portata disponibile.
  4. Funzionalità di calibrazione del nuovo MCOVC (Sostituzione MCOMV)

La serie MCOVC inoltre non dispone di potenziometro zero/span esterno, solo calibrato in fabbrica, verifica metrologica consentita, nessuna rifinitura dell'hardware in loco.

  1. Intervallo di calibrazione consigliato

Per pannello CC, monitoraggio batteria -48V per telecomunicazioni, applicazioni nelle centrali elettriche che richiedono metrologia tracciabile: Calibrazione annuale ogni 12 mesi.

FRER MCOMV;48Precauzioni per la calibrazione della precisione VDC

Riepilogo principale: È consentita solo la verifica metrologica (convalida dell'accuratezza). Nessun potenziometro di trim zero/span esterno. Vietata l'apertura della custodia per la regolazione; Classe 0.5, tolleranza ±0,5%FS fondo scala.

  1. Condizioni ambientali (Calibrazione non valida se non soddisfatta)
  2. Temperatura ambiente: Prefer 25℃±2℃ constant temperature; record actual temperature if test off-nominal. Temperature drift ≤100ppm/℃ will introduce extra error.
  3. Umidità: 5%~95%UR, vietata la formazione di condensa. Condensation reduces isolation voltage, causes leakage error or permanent damage.
  4. EM Environment: Keep away from VFD, contattori, high-power cables and strong magnetic field. Heavy interference leads to 4~20mA jitter and false failure judgement.
  5. Stabilizzazione: Mount transducer on DIN rail, power on and warm up ≥15min until thermal stabilization before reading.
  6. Standard Instrument Requirements (Reference instrument accuracy better than DUT)

For Class 0.5 transducer, follow the 1/3 rule (instrument uncertainty ≤1/3 of DUT allowable error)

  1. Standard DC Voltage Source: Accuracy better than 0.15 classe, 0~48VDC output, low ripple
  2. Standard Milliammeter: DC current measurement accuracy better than 0.15 classe, connected in series in current circuit
  3. General multimeter cannot be primary standard (insufficient accuracy), only auxiliary reference

Instruments must be within valid calibration period with certificate to ensure metrology traceability.

III. Cablaggio & Power Supply Notes

  1. Potenza ausiliaria: Stable 20~60V DC supply with low ripple. Avoid unstable switching power supply for temporary test. Fluctuating supply introduces output drift.
  2. Circuito di ingresso: Strict polarity for input +/-; limited reverse protection exists but long-time reverse energizing not recommended. Keep input wiring short; shielded cable with single-end grounding to reduce common-mode interference.
  3. Output Current Loop

Insert standard ammeter in series within 4~20mA loop

Total loop resistance shall not exceed 750Ω (ammeter internal resistance + cable resistance). Excessive load prevents reaching 20mA full scale and leads to false failure.

Tight wiring terminals; loose contact causes reading fluctuation.

  1. Messa a terra: Avoid multiple grounding for transducer, standard source and meters to prevent ground loop and common-mode voltage measurement error.
  2. Calibration Points & Linee guida operative

Recommended test points: 0V, 12V, 24V, 36V, 48V (0%, 25%, 50%, 75%, 100%FS)

  1. Upscale test: Ramp input from 0V up to full scale 48V, record output for each point
  2. Downscale test: Ramp down from 48V to 0V for return test and hysteresis error inspection
  3. Wait 3~5 seconds at each test point for reading stabilization before recording
  4. Do not continuously apply full 48V for long duration. Though 50% continuous overload is supported, long overvoltage accelerates aging. Transient 2× overload only for impulse test and not used for accuracy calibration.
  5. Error Calculation: FS =16mA full scale span. Error=(Measured Value − Theoretical Value)/FS ×100%. Criterion ±0.5%FS.
  6. Sicurezza & Protezione delle apparecchiature
  7. Isolamento a tre vie: Ingresso, uscita e potenza isolata a 2,5kV. NON cortocircuitare input e output durante il test, la struttura di isolamento verrà danneggiata.
  8. Apertura dell'involucro vietata: Potenziometro PCB interno bloccato in fabbrica. L'apertura distrugge l'isolamento, invalida la garanzia e compromette il grado di isolamento con rischi per la sicurezza. Anche se tagliato, La fabbrica FRER non riconosce la regolazione sul campo, e il certificato metrologico non accetterà modifiche hardware in loco.
  9. Coppia moderata sulle viti dei terminali; evitare un serraggio eccessivo che spela le filettature e danneggia il PCB.
  10. Registrazione dei dati, Sentenza & Disposizione
  11. Registra elementi: Temperatura ambiente & umidità, ID dello strumento/numero di certificato, tensione di alimentazione ausiliaria, letture avanti/indietro di tutti i punti ed errore calcolato
  12. Pass Criterion: Tutti avanti & restituire errori del punto di prova ≤ ±0,5%FS da qualificare; errore di isteresi registrato insieme
  13. Gestione fuori tolleranza: Nessuna correzione in loco possibile per questo dispositivo. Opzioni: Sostituirlo con MCOVC1;48Modello compatibile VDC o restituzione in fabbrica per la ricalibrazione. NON utilizzare la compensazione dell'offset software del canale AI del PLC in sostituzione della calibrazione del trasduttore (solo compensazione tecnica temporanea e non accettata come prova di conformità metrologica).

VII. Insidie ​​​​comuni

❌ Utilizza la lettura AI integrata nel PLC come riferimento per la calibrazione: Il modulo AI PLC presenta un errore intrinseco e non può fungere da standard metrologico

❌ Trascurare la resistenza al carico: Resistenza totale del circuito>750Ω, il fondo scala non può raggiungere 20 mA e si verifica un falso guasto

❌ Leggi i dati senza riscaldamento: Componenti termicamente instabili, introdotto errore di deriva termica

❌ Messa a terra multipla, interferenze del circuito di terra e fluttuazioni dell'uscita

❌ Aprire l'alloggiamento e regolare il potenziometro interno: Not accepted by metrology and isolation invalidated

Cross-Brand Model Comparison Table for MCOMV;48VCC (FRATELLO)

Original Spec: Montaggio su guida DIN, 0~48VDC input /4~20mA output, 3-modo isolamento galvanico (Input/Output/Power), Classe 0.5, A. Supply 20~60VAC/DC, Max Load 750Ω, No external zero/span adjustment

Priorità di selezione: OEM Upgrade Import Equivalent Domestic Industrial Grade (Field Z/S adjustable, preferred for engineering replacement)

Brand Recommended Model Key Matching Points Differences Application Scenario
FRATELLO (OEM) MCOVC1;48VDC Fully compatible;0~48VDC,4-20mA,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;Spillo & dimension match Still no external potentiometer, factory calibrated, no field trimming Retrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
Phoenix MACX MCR-VAC (Config: DC 0~48V,4-20mA) 3-way isolation, Class0.5, Guida DIN, wide supply Module width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special order PLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+Fuchs KFD2-VR4-EX1.20 (Custom input 0~48VDC) 3-way isolation,4-20mA output, high industrial noise immunity Standard model defaults to 0~10V, factory customized input range required;Class0.5;Higher price Explosion-proof area, accumulo di energia, telecom -48V monitoring
Acrel BM-DV/I, 0~48VDC input,4-20mA output 3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometer Domestic brand, campo zero & span adjustable;Vantaggio in termini di costi;2.5kV isolation same as FRER Telecom -48V battery,Pannello CC,batch replacement,field calibration required
Suzhou Xunpeng WP-V,0~48VDC,4-20mA 3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometer Domestic, conveniente, metrology certifiable,short procurement lead time Factory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC) 1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5 Programmable range,externally adjustable;Strong EMC 12.5mm slim DIN module;Default 24VDC supply,wide voltage optional DCS cabinet,multi-signal centralized acquisition

MarcaModello consigliatoPunti chiave di corrispondenzaDifferenzeScenario applicativo
FRATELLO (OEM)MCOVC1;48VCCPienamente compatibile;0~48VDC,4-20mA,3-way isolation,22.5mm narrow DIN rail,20~60V AC/DC supply,Class0.5;Spillo & dimension matchStill no external potentiometer, factory calibrated, no field trimmingRetrofit cabinet where terminal layout cannot be modified, projects requiring metrology certification
FeniceMACX MCR-VAC (Config: DC 0~48V,4-20mA)3-way isolation, Class0.5, Guida DIN, wide supplyModule width12.5mm, software configurable range, field calibration available. Default 24VDC supply, wide voltage version on special orderPLC/DCS cabinet, high EMC environment, power station DC panel
Pepperl+FuchsKFD2-VR4-EX1.20 (Custom input 0~48VDC)3-way isolation,4-20mA output, high industrial noise immunityStandard model defaults to 0~10V, factory customized input range required;Class0.5;Prezzo più altoZona a prova di esplosione, accumulo di energia, telecom -48V monitoring
AcrelBM-DV/I, 0~48VDC input,4-20mA output3-way isolation,Class0.5,DIN rail,22.5mm,20~60V AC/DC supply,built-in Zero/Span trim potentiometerMarchio nazionale, campo zero & span adjustable;Vantaggio in termini di costi;2.5kV isolation same as FRERTelecom -48V battery,Pannello CC,batch replacement,field calibration required
Suzhou XunpengWP-V,0~48VDC,4-20mA3-way isolation,Class0.5,DIN rail,wide supply,external zero/span potentiometerDomestico, conveniente, metrology certifiable,short procurement lead timeFactory technical renovation,bulk transducer replacement
CZ3076 (Custom range 0~48VDC)1in1out voltage isolation transducer,3-way isolation,4~20mA output,Class0.5Programmable range,externally adjustable;Strong EMC12.5mm slim DIN module;Default 24VDC supply,wide voltage optionalDCS cabinet,multi-signal centralized acquisition

Selection Priority Description

  1. Minimum modification replacement (no terminal rewiring recommended)

FRER MCOVC1;48VCC, direct plug-in replacement for MCOMV;48VCC, identical housing width, assegnazione dei terminali e parametri elettrici; Limitazione: ancora nessun ritaglio dello zero/span del campo, solo verifica metrologica di laboratorio.

  1. Preferito per la manutenzione sul campo (Consigliato Acrel BM-DV/I)

Specifiche corrispondenti, potenziometro zero/span integrato, calibrazione in loco disponibile quando fuori tolleranza, risoluzione della limitazione MCOMV di nessuna regolazione del campo; 2.5L'isolamento kV incontra il pannello DC & requisiti di metrologia dell'energia per le telecomunicazioni.

  1. Applicazione Premium importata ad alta compatibilità elettromagnetica

SISTEMA M, Serie Phoenix MACX con prestazioni EMC superiori, ma diversa disposizione dei terminali e larghezza del modulo, è necessario ricablare i terminali dell'armadio, non è possibile collegarlo & giocare.

Riepilogo delle differenze chiave (Per il confronto delle specifiche tecniche)

  1. Capacità di calibrazione

FRER MCOMV / MCOVC: Nessuna Z/S esterna, solo verifica metrologica, Nessuna regolazione dell'hardware sul campo

Acrel/Xunpeng/CZ: Zero esterno & potenziometro di intervallo, Calibrazione sul campo disponibile

Phoenix/M-SISTEMA: Calibrazione della configurazione del software

  1. Alimentazione elettrica

FRATELLO: 20~60V AC/DC wide range; La maggior parte importata & domestic standard models default to 24VDC, wide voltage version must be specified at order.

  1. Larghezza del modulo

FRER original unit: 22.5mm; Fenice & CZ slim type:12.5mm, less DIN rail slot consumption.

Mandatory Order Remarks (Prevent Wrong Range Shipment)

Must specify below items on PO for all replacement models:

DC Voltage Input:0~48VDC; Produzione:4~20mA; 3-modo isolamento galvanico; Montaggio su guida DIN; Classe di precisione 0.5; Potenza ausiliaria:20~60VAC/DC

Prec: