TeSys Deca GV2ME Interruttore automatico del motore (MPCB), push-button operated, terminali con morsetto a vite
✅ Core Technical Specifications
Poli: 3P
Thermal overload setting range: 2.5~4 A
Potenza motore abbinata (400V trifase): 1.5 kW
Tensione operativa nominale Ue: 690V e, 50/60 Hz
Insulation voltage Ui: 690V; Tensione di tenuta ad impulso Uimp: 6kV
Magnetic short-circuit trip: ca. 13×In ≈ 51A (protezione istantanea da cortocircuito)
Rated short-circuit breaking capacity Icu: 100kA a 400 V
Categoria di utilizzo: AC-3 (for direct-on-line motor starting); built-in isolation function + protezione contro la perdita di fase
Controllare: Red STOP pushbutton, black START pushbutton, with TEST position
Montaggio: Norma su guida DIN; IP20 (finger-safe on front face)
✅ Definizione del codice modello
GV2: TeSys GV2 motor circuit breaker series
ME: Push-button version (rotary knob version: GV2P)
08: Codice di valutazione attuale, corresponding to 2.5–4A
C: China version with CCC certification
✅ Protection Functions
- Protezione da sovraccarico termico: Time-delayed tripping for continuous motor overload & rotore bloccato; adjustable within 2.5~4A via the setting dial
- Magnetic short-circuit protection: Instant trip for phase-to-phase short circuit
- Phase-loss protection: Accelerated tripping when one phase is lost, preventing motor burnout
- Built-in start/stop operation: Can be used alone for small-motor direct start, or paired with contactors for star-delta / auto-transformer starting circuits
✅ Compatible Accessories (Field-mountable)
GVAN: Contatto ausiliario (1NA+1NC, for ON/OFF & trip status feedback)
GVAX: Contatto di allarme (differentiates overload trip from short-circuit trip)
GVAD: Viaggio di derivazione / undervoltage trip coil
GV2AF3: Sbarra collettrice, adapter & interlock module
✅ Selection & Riferimento sostitutivo
Same-series knob variant: GV2P08C (identical thermal-magnetic curve & tripping parameters, 2.5–4A)
Alternative domestiche: Delixi CDM6e-M, Cinto NS2-25 08 (2.5~4A motor protector)
Higher frame upgrade: GV3ME series with same current rating
✅ Wiring Guidelines
Line side L1/L2/L3: Collegare l'alimentazione trifase; Load side T1/T2/T3: Collegare il motore
Contatti ausiliari (se montato): Per PLC fault feedback & pilot lamp circuits
Setting rule: Align the dial with the motor rated current on nameplate; avoid long-term setting near the upper limit of the range
✅ Common Troubleshooting
- Trips immediately on startup: Mostly short circuit. Controllare l'avvolgimento del motore & cable insulation; may also be caused by magnetic trip threshold mismatch
- Trips after running for a period: Sovraccarico. Verify actual motor current, load condition and thermal setting; check poor heat dissipation
- Phase-loss tripping: Check three-phase incoming voltage and loose terminal connections
✅ GV2-ME08C (Push-button Type)
Operazione: Push-button start/stop (black START, red STOP)
Gamma attuale: 2.5~4A; same tripping characteristics as GV2P08C
Caratteristiche: Small panel cutout; designed for local cabinet operation; no obvious mid-position trip indication
Applicazione: Standard domestic panel build, ordinary fans & pompe dell'acqua (most widely used model)
✅ GV2P08C (Rotary Knob Type)
Operazione: Maniglia rotante (knob control)
Gamma attuale: 2.5~4A (same as GV2ME08C)
Key feature: Clear trip mid-position; you can distinguish manual opening from fault tripping at a glance; supports external door-mounted extension handle GV2APN
Vantaggi: Compliant with UL508 Type E; higher SCCR short-circuit rating; ideal for export equipment, door-mounted operation and strict safety specifications
📋 Comparison Table
| Articolo | GV2ME08C | GV2P08C |
| Operazione | Push-button start/stop | Rotary knob handle |
| Trip indication | No dedicated mid-position | Locked mid-position after trip |
| Door extension handle | Non supportato | Compatible with GV2APN |
| Tipo di terminale | Morsetto a vite (suffisso C) | Morsetto a vite (suffisso C) |
| Curva di viaggio | Identical thermal-magnetic curve | Same tripping parameters |
| Typical usage | Domestic cabinet local operation | Export machines & door-mounted control |
Step-by-Step MPCB Selection Guide
Applicable to GV2ME / GV2P thermal-magnetic motor circuit breakers, only for three-phase asynchronous DOL motors; NOT for resistive loads, soft starters or inverter output circuits.
Fare un passo 1: Collect 3 key data from motor nameplate
- Corrente nominale In (most critical)
- Tensione nominale (typically 380/400V AC three-phase)
- Potenza nominale (only for reference; never select purely by power)
Common mistake: Two 1.5kW motors with different pole counts have different rated currents; power-only selection frequently leads to mis-setting.
Fare un passo 2: Select the thermal setting range (core rule)
The MPCB adjustment range must fully contain the motor rated current, preferably in the middle third of the range
Formula:
Lower limit of breaker range < Motor rated current < Upper limit of breaker range
Raccomandazione: Place In within 30%~70% of the total range; avoid setting near the upper end
✅ Example: Motor rated current = 3.2A
Select GV2ME08C (2.5~4A); set dial to 3.2A.
❌ If In=3.9A, it still fits but sits close to the upper limit; frequent nuisance tripping will occur under continuous heavy load.
Thermal setting principles
Continuous loads (tifosi, pompe dell'acqua): Set thermal current = motor nameplate rated current
Long starting inertia (grandi tifosi, frantoi): Increase to 1.05~1.1×In; never exceed 1.1×In
Frequent jogging & shock loads: Do not simply raise the setting; use a separate thermal relay + contactor combination instead
Thermal trip: Sovraccarico, rotore bloccato & protezione contro la perdita di fase (time-delayed);
Magnetic trip: Fixed non-adjustable short-circuit protection (13× upper range value, istantaneo).
Fare un passo 3: Choose operation type (Pulsante / Manopola)
GV2MExxC (push-button, per esempio. GV2-ME08C): Basso costo, local cabinet operation, no clear trip mid-position
GV2Pxx (manopola rotante): Visible trip mid-position; add external door handle; suitable for export machines & fault identification
Fare un passo 4: Choose terminal type
Suffix C: Morsetti a vite (standard for domestic projects)
Suffisso 3: Terminali a molla (no-tool fast wiring; preferred for automated panel mass production)
Fare un passo 5: Verify voltage, potere di interruzione & utilization category
- Tensione nominale: Max 690V AC (400V standard)
- Short-circuit breaking capacity Icu: Must exceed the prospective short-circuit current at the installation point
Ordinary end circuits in small control cabinets: 100kA@400V of GV2 is sufficient
Circuits close to transformers with high short-circuit current: Add upstream fuses if Icu is insufficient
- Utilization category AC-3: Only valid for direct-on-line motor starting
❗ Not applicable: Star-delta starters, soft starters, inverter output terminals, Motori CC, resistive heating loads, heavy-duty reversing mechanisms.
Fare un passo 6: Configure accessories based on control scheme
- Local direct start (no PLC): Use MPCB alone with built-in pushbuttons
- Remote PLC control: MPCB only for isolation & protezione, paired with contactors; add GVAN auxiliary contacts (1NA+1NC) for running/fault feedback; add GVAX alarm contacts to separate overload trip from short-circuit trip
Optional extras: Shunt trip GVAD10, undervoltage trip GVAD01, interconnection busbar GV2AF3
Fare un passo 7: Exclude unsuitable applications
❌ Inverter output side
❌ DC motors
❌ Resistive loads (riscaldatori, illuminazione)
❌ Frequent forward/reverse operations (prone to false tripping; use separate thermal relays)
❌ Outdoor / corrosivo / dusty environments (must install inside an IP-rated enclosure)
Riepilogo della selezione rapida
- Read motor rated current from nameplate (primary data; power is only reference)
- Pick a GV2 model whose current range covers In, keep In away from the upper limit
- Select operation: Push-button GV2ME / Rotary knob GV2P
- Select terminals: Screw C / Primavera 3
- Check short-circuit current to confirm breaking capacity is adequate
- Add auxiliary contacts / trip contacts according to control requirements
Esempio pratico
Motore: 3-fase 400V, 1.5kW, rated current = 3.0A
Current range match: 2.5~4A → GV2ME08C
Set dial to 3.0A
Cabinet local operation without door handle → Push-button type
→ Final model: GV2-ME08C