This is a standard interruttore automatico scatolato (MCCB) from the Meta-MEC / ABS series, with a frame size of 100AF, rated current of 100A, 3 poli, and a breaking capacity of 25kA, used for power distribution and motor protection.
- Spiegazione del modello
ABS: LS standard MCCB series (economic version: ABE)
103: Frame size 100AF + 3P (3 poli)
B: Standard thermal-magnetic trip
100UN: Rated current In = 100A
3P: 3 poli (three-phase)
- Key Specifications (ABS103B-100A-3P)
Marca: LS ELECTRIC (formerly LG ELECTRIC)
Serie: ABS (Meta-MEC)
Frame size: 100DI
Number of poles: 3P
Corrente nominale: 100UN
Rated operational voltage: AC 415V (compatible with 380V)
Tensione di isolamento nominale: 690V
Potere di interruzione:
Ultimate short-circuit breaking capacity Icu = 25kA @ 415V
Service short-circuit breaking capacity Ics = 12.5kA
Trip type: Magnetotermico (non-adjustable)
Protezione da sovraccarico: Bimetallic strip
Protezione da cortocircuito: Magnetic instantaneous trip (ca. 10–12×In)
Protection functions: Sovraccarico, short-circuit; optional undervoltage / shunt / earth-leakage protection
Montaggio: Tipo fisso (front wiring)
Dimensioni: ca. 155 × 90 × 60 mm
Certificazioni: CCC, CE
Mechanical endurance: 8,500 operazioni; Electrical endurance: 150,000 operazioni
- Common Specifications in the Same Series (100DI)
| Modello | Poli | Corrente nominale | Capacità di interruzione |
| ABS103B-63A-3P | 3P | 63UN | 25IL |
| ABS103B-80A-3P | 3P | 80UN | 25IL |
| ABS103B-100A-3P | 3P | 100UN | 25IL |
| ABS102B-100A-2P | 2P | 100UN | 25IL |
- Caratteristiche principali
Compact structure, high flame-retardant housing, silver alloy contacts
Thermal-magnetic trip, economical and reliable, suitable for general power distribution and motor protection
Can be equipped with auxiliary contacts, alarm contacts, shunt / undervoltage releases
Applicazioni: Distribuzione dell'energia industriale, controllo motorio, distribuzione dell’energia nell’edificio, marine use, ecc.
- Equivalent / Reference Models
Schneider: NSX100N 100A 3P
Siemens: 3VL1710-1DA33-0AA0
ABB: T1N100 TMD100/1000 3P
LS ELECTRIC molded case circuit breakers (MCCB) are mainly divided into three major series: Meta-MEC (ABS / ABE / ABN / ABL), Metasol (TS / TSG / TSD), and Susol (TSE), covering frame sizes from 30AF to 1600AF, suitable for power distribution and motor protection.
- Meta-MEC Series (Economic / Tipo standard)
1.1 Regole di denominazione dei modelli
ABE: Economic type (thermal-magnetic, 18–25kA)
ABS: Standard type (thermal-magnetic, 25–36kA)
ABN: High breaking capacity type (thermal-magnetic, 36–50kA)
ABL: Extra-high breaking capacity type (thermal-magnetic, 50–65kA)
Frame sizes: 30 / 60 / 100 / 125 / 200 / 250 / 400 / 630 / 800DI
Poli: 2P / 3P / 4P (3rd digit: 2=2P, 3=3P, 4=4P)
Trip: B = thermal-magnetic, C = electronic
1.2 Common Model List (3P)
| Frame AF | Economic ABE | Standard ABS | High Breaking ABN | Extra-High ABL | Rated Current In |
| 30 | ABE33b | ABS33b | ABN33c | ABL33c | 10/15/20/30UN |
| 60 | ABE63b | ABS63b | ABN63c | ABL63c | 40/50/60UN |
| 100 | ABE103b | ABS103b | ABN103c | ABL103c | 63/80/100UN |
| 125 | ABE123b | ABS123b | ABN123c | ABL123c | 100/125UN |
| 200 | ABE203b | ABS203b | ABN203c | ABL203c | 125/150/175/200UN |
| 250 | ABE253b | ABS253b | ABN253c | ABL253c | 200/225/250UN |
| 400 | ABE403b | ABS403b | ABN403c | ABL403c | 250/300/350/400UN |
| 630 | ABE633b | ABS633b | ABN633c | ABL633c | 400/500/630UN |
| 800 | ABE803b | ABS803b | ABN803c | ABL803c | 630/700/800UN |
- Metasol Series (Di fascia alta / Electronic Type)
2.1 Regole di denominazione dei modelli
TS: Standard type (electronic trip, E/N/H/L)
TSG: Generator protection type
TSD: DC dedicated type
Frame sizes: 100 / 160 / 250 / 400 / 630 / 800 / 1000 / 1250DI
Potere di interruzione: E=25kA, N=36kA, H=50kA, L=65kA
2.2 Common Models (3P)
TS100E/N/H/L, TSG100N/H/L
TS160E/N/H/L, TSG160N/H/L
TS250E/N/H/L, TSG250N/H/L
TS400E/N/H/L, TSG400N/H/L, TSD400N
TS630E/N/H/L, TSG630N/H/L
TS800N/H/L, TS1000N/H/L, TS1250N/H/L
- Susol TSE Series (Modulare / Compact Type)
3.1 Regole di denominazione dei modelli
TSE: Modulare, double-break, Ics = 100% terapia intensiva
Frame sizes: 100 / 160 / 250 / 400 / 630DI
Potere di interruzione: N=36kA, H=50kA, L=65kA
3.2 Common Models (3P)
TSE100N/H/L, TSE160N/H/L
TSE250N/H/L, TSE400N/H/L
TSE630N/H/L
- DC Dedicated Series (PV / Energy Storage)
TS250V, TS400V, TS600V (DC 1500V, 20IL)
- Selection Guide
Economic power distribution: ABE
Standard power distribution / motor protection: ABS
High short-circuit locations: ABN / ABL
High-end intelligent / electronic trip: TS / TSG
Compatto / automation applications: TSE
DC PV / energy storage: TSV
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari