 Schneider NT06H2 Air Circuit Breaker - Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore

interruttore automatico/

Schneider NT06H2 Air Circuit Breaker

NT: MasterPact NT series air circuit breaker (ACB, legacy model, interrotto; replacement model MTZ1 06H2) 06: Dimensioni del telaio 06, frame rated current 630A H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1S), Class B selective protection Core Electrical Parameters Item Specification Frame rated current In 630A (a 40 ℃) Rated operational voltage Ue AC ...

  • Dettagli del prodotto

NT: MasterPact NT series interruttore automatico dell'aria (ACB, legacy model, interrotto; replacement model MTZ1 06H2)

06: Dimensioni del telaio 06, frame rated current 630A

H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1S), Class B selective protection

Parametri elettrici principali

ArticoloSpecifica
Frame rated current In630UN (a 40 ℃)
Tensione operativa nominale UeCA 690 V, 50/60Hz
Tensione nominale di isolamento UiAC 1000V
Tensione nominale di tenuta ad impulso Uimp12kV (1.2/50μs lightning impulse)
Potere di interruzione ultimo in cortocircuito Icu50kA@440V; 42kA@690V
Numero di poli3P / 4P opzionale
Tipologia costruttivaFisso / Estrazione
Unità di sgancioFrame supplied without trip unit, MicroLogic trip unit to be ordered separately
StandardCEI 60947-2, with isolating function

Note chiave

  1. Stato di interruzione: NT series scheduled for end-of-sale by the end of 2025. Replacement model MTZ1 06H2, part number LV947203 (draw-out version)
  2. Parameter Clarification

Ue=690V: Maximum normal operating voltage

Ui=1000 V: Tensione di tenuta a frequenza industriale

Uimp=12kV: Lightning impulse withstand voltage. NOT applicable for 12kV high-voltage switchgear, this is an insulation index for low-voltage ACB

  1. Applicazione: Incoming feeder, bus tie and heavy-load outgoing feeder in low-voltage distribution systems, for industrial plants, data centers and marine power distribution; supports selective protection and coordination with upstream/downstream devices
  2. Reference Frame Part Numbers

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

Accessori & Pezzi di ricambio

Trip Units: Micrologica 2.0 / 5.0 / 6.0 / 7.0 (sovraccarico, ritardo di breve durata, instantaneous and earth-fault protection)

Accessori: Motor operating mechanism, contatti ausiliari, fault alarm contacts, closing coil, shunt trip coil, interblocco della porta, phase barriers

Draw-out base: Mandatory independent cradle for draw-out version

Linee guida per la risoluzione dei problemi

  1. Mancata chiusura: Undervoltage coil de-energized, incomplete spring charging, cradle not in connected position, interlock blocking
  2. Unintended tripping: Check trip unit protection curve, guasto a terra, harmonic distortion and temperature rise
  3. Prova di isolamento: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type-test only, no on-site 12kV impulse test

Domestic Alternative Reference

Domestic MT06H2 (Schneider domestic MT series). Compatible breaking capacity and mounting dimensions for direct replacement.

Schneider MasterPact NT06H2 Air Circuit Breaker Technical Manual (Full Engineering Version, per original datasheet 0613CT0001)

Osservazioni: NT series is legacy discontinued ACB, frame size NT06, In=630A; breaking class H2; frame supplied without trip unit, MicroLogic trip unit to be ordered separately; standard IEC 60947-2, isolating function, Class B selective protection

Sommario

  1. Panoramica del prodotto & Spiegazione del codice modello
  2. Rated Electrical Parameters
  3. Parametri meccanici, Dimensioni complessive & Peso
  4. MicroLogic Trip Unit Selection
  5. Elenco degli accessori & Secondary Terminal Definition
  6. Installazione & Requisiti di cablaggio
  7. Operazione, Handling & Interlock Description
  8. Manutenzione, Ispezione & Risoluzione dei problemi
  9. Condizioni ambientali
  10. Replacement Model Information
  11. Original Document Index
  12. Panoramica del prodotto & Spiegazione del codice modello

1.1 Panoramica

MasterPact NT series low-voltage air circuit breakers for incoming feeders, bus ties and high-current outgoing feeders in 400/690V low-voltage distribution systems. NT06H2 maximum frame rating 630A, available in draw-out or fixed construction, spring charged operation, configurable with intelligent MicroLogic protection unit, supports remote signalling, metering and communication.

Promemoria importante: Ui=1000 V (tensione nominale di isolamento), Uimp=12kV (lightning impulse withstand voltage). NOT 12kV high voltage circuit breaker, only for AC ≤690V low-voltage distribution.

1.2 Ripartizione del modello

NT: MasterPact NT series air circuit breaker

06: Dimensioni del telaio 06, frame rated current 630A

H2: Breaking class H2; Icu=50kA@440VAC, Icw=50kA 1s, Class B selective

Numeri di parte:

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

1.3 Stato del prodotto

NT series scheduled end-of-sale by end of 2025; replacement model MTZ1 06H2, part number LV947203 (estrazione). Mounting dimensions and secondary interfaces fully compatible for direct replacement.

  1. Rated Electrical Parameters
ArticoloValore
Frame rated current In630UN (at 40℃ ambient)
Tensione operativa nominale UeCA 50/60 Hz, max 690V
Tensione nominale di isolamento Ui1000V
Tensione nominale di tenuta ad impulso Uimp12kV (1.2/50μs lightning impulse)
Potere di interruzione ultimo in cortocircuito Icu50kA@440V; 42kA@690V
Rated short-time withstand current Icw50IL, 1S
Potere di interruzione nominale del servizio Ics100% dell'Icu
Selectivity classClasse B (with short-time delay selective protection)
Isolating functionComplies with IEC60947-2 isolation requirement
Numero di poli3P / 4P opzionale
  1. Parametri meccanici, Dimensioni complessive & Peso

3.1 Resistenza meccanica

Vita meccanica: 20,000 operazioni (no-load make/break)

Vita elettrica (400V, In): 10,000 operazioni

Spring charging: Manual charging / motor charging MCH optional

3.2 Dimensioni complessive (3P, unità: mm)

Tipo fisso: W300 × H415 × D266

Tipo estraibile (with cradle): W300 × H415 × D376

4P version width 360mm, height and depth unchanged

3.3 Peso

Fixed frame only: ≈32kg

Draw-out frame + cradle: ≈52kg

3.4 Three positions for draw-out version

  1. Connected Position: Main circuit and secondary circuit fully connected, normal operation
  2. Test Position: Main circuit disconnected, secondary circuit remains connected for protection test
  3. Disconnected Position: Main and secondary circuits fully disconnected, breaker can be withdrawn for maintenance
  4. MicroLogic Trip Unit Selection (Deve essere ordinato separatamente, not included with frame)
Modello unità di viaggioFunzioni di protezioneApplicazione tipica
Micrologica 2.0Long-time overload protection onlyIsolator, overload-only protection
MicroLogic 5.0ALong-time Ir, short-time delay Isd, instantaneous IiIncoming feeder, cravatta dell'autobus (più comune)
MicroLogic 6.0AAll functions of 5.0A + protezione dai guasti a terraCritical incoming feeder requiring earth fault protection
MicroLogic 7.0A6.0UN + protezione corrente residua + monitoraggio armonicoCentri dati, sensitive loads

Protection setting range: E (a lungo) 0.4~1×In; Isd short-time delay 0.5~10×In, delay 0.1/0.2/0.4s; Ii instantaneous 1~15×In.

  1. Elenco degli accessori & Secondary Terminal Definition

5.1 Accessori opzionali

  1. MCH: Charging motor AC220V / DC24V
  2. XF: Closing solenoid AC220V / DC24V
  3. MX: Bobina a lancio di corrente (apertura remota)
  4. MN: Sganciatore di minima tensione (MNu time-delayed undervoltage for auto-transfer application)
  5. DI: Contatti ausiliari (CB on/off status feedback)
  6. SDE: Fault trip contacts (signal for overload/short-circuit/earth fault trip)
  7. PF: Cradle position contacts (connected / test / disconnected position)
  8. Phase barriers, interblocco della porta dell'armadio, mechanical interlock cables, padlock device
  9. ULP communication module: Modbus-RTU, remote signalling & misurazione

5.2 Secondary Terminal Definition

CodiceNomeTerminaliDescrizione
MCHCharging motorB1, B2Auto charging upon power-up; B1-B3 charged ready CH contact
XFClosing coilA1, A2Closing actuation
MXViaggio di derivazioneC1, C2Remote opening
MNSganciatore di minima tensioneD1, D2Trip on loss of voltage, core component for auto-transfer
DIAuxiliary position contact11-12 NC /11-13 NOOn/off status feedback
SDEFault trip contact81,82Protection action signal
PFCradle position contact251/252/254Draw-out position signal
  1. Installazione & Requisiti di cablaggio
  2. Montaggio: Vertical upright installation, ±5° tilt allowed; inverted mounting prohibited
  3. Collegamento al circuito principale: Collegamento frontale / rear horizontal / rear vertical connection; apply specified tightening torque for copper busbars to avoid overheating
  4. Secondary control wiring: 0.75~1.5mm² multi-core shielded cable; independent AC220V/DC24V control power supply for secondary circuit
  5. Prova di isolamento: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type test only, no on-site 12kV impulse test
  6. Draw-out operation: Use dedicated crank for rack-in / rack-out; prohibit racking out breaker from connected position under live condition
  7. Operazione, Handling & Interlock Description

7.1 Operation Procedure

  1. Charging: Manual charging handle or MCH motor auto charging; charging complete, charged indicator lights on
  2. Chiusura: Local front panel close pushbutton / XF remote close; verify interlock conditions before closing
  3. Apertura: Local open pushbutton / MX remote opening / automatic protection tripping; after fault trip, fault reset button must be manually reset before re-closing

7.2 Interlock (Two-incoming one bus tie scheme)

Interblocco meccanico: Steel cable mechanical interlock, physically prevents simultaneous closing of three ACBs

Interblocco elettrico: Close circuit wired in series with normally closed contacts of other breakers for double protection

Cradle position interlock: Closing circuit blocked when not in connected position, closing prohibited

Fault trip interlock: Auto-transfer closing logic blocked upon SDE contact activation

  1. Manutenzione, Ispezione & Risoluzione dei problemi

8.1 Manutenzione periodica

Semi-annual: Check charging status, on/off indication, contact temperature rise, tightness of secondary wiring

Annuale: Dust cleaning, insulation inspection, trip unit test (using MicroLogic test cable)

Overhaul (ogni 5 anni): Disassemble to inspect main contacts and arc chamber, mechanical lubrication, mechanical life verification

8.2 Risoluzione dei problemi tipici

  1. Mancata chiusura

Incomplete charging; undervoltage MN coil de-energized; cradle not in connected position; interlock blocked; fault trip not reset

  1. Unintended tripping

Verify protection curve; guasto a terra; harmonic overload; loose wiring with overheating; voltage dip triggering MN undervoltage trip

  1. Charging failure

No power supply to MCH motor; jammed charging mechanism; damaged charged-ready contact

  1. No fault signal output

Wrong SDE auxiliary contact wiring, burnt contacts

  1. Condizioni ambientali

Temperatura ambiente operativa: -5℃ ~ +70 ℃; declassamento richiesto sopra i 40 ℃

Temperatura di conservazione: -40℃ ~ +85 ℃

Umidità relativa: ≤95% (senza condensa)

Altitudine: ≤2000m; derating and insulation correction required above 2000m

Grado di protezione: Device IP30; IP40 with cabinet door closed

Grado di inquinamento: 3

  1. Replacement Model Information

NT06H2 → MTZ1 06H2

Telaio 630A, Icu=50kA, compatible MicroLogic trip unit

Dimensioni di montaggio, primary busbar and secondary terminals fully compatible, no cabinet modification required for in-panel retrofit

Supports ECOSTRUXURE Power software commissioning, upgraded communication interface

Schneider MasterPact NT Full Series Model List (IEC Version, Discontinued ACB, Frame 630~1600A)

Regola di denominazione: NT + Frame Code + Classe di rottura

Frame Code: 06=630A; 08=800A; 10=1000A; 12=1250A; 16=1600A

Classe di rottura: N1 / H1 / H2 / L1; Costruzione: Fisso / Estrazione; Poles 3P/4P; Frame without trip unit, MicroLogic to be ordered separately

Common Base Parameters: Ui=1000 V, Uimp=12kV, Ue max AC690V, Class B selective protection

Breaking Class Definition (440V, Icu ultimate breaking capacity)

N1: 35IL

H1: 42IL

H2: 50IL (same class as NT06H2)

L1: 130IL (tipo a limitazione di corrente, application for high short-circuit capacity)

NT Full Model List

TelaioFrame InClasse di rotturaModello completoIcu@440VIcw(1S)Typical 3P Fixed Part No.
NT06630UNN1NT06N135IL35IL47111
NT06630UNH1NT06H142IL42IL47112
NT06630UNH2NT06H250IL50IL47113
NT06630UNL1NT06L1130IL50IL47114
NT08800UNN1NT08N135IL35IL47121
NT08800UNH1NT08H142IL42IL47122
NT08800UNH2NT08H250IL50IL47123
NT08800UNL1NT08L1130IL50IL47124
NT101000UNN1NT10N135IL35IL47131
NT101000UNH1NT10H142IL42IL47132
NT101000UNH2NT10H250IL50IL47133
NT101000UNL1NT10L1130IL50IL47134
NT121250UNN1NT12N135IL35IL47141
NT121250UNH1NT12H142IL42IL47142
NT121250UNH2NT12H250IL50IL47143
NT121250UNL1NT12L1130IL50IL47144
NT161600UNN1NT16N135IL35IL47151
NT161600UNH1NT16H142IL42IL47152
NT161600UNH2NT16H250IL50IL47153
NT161600UNL1NT16L1130IL50IL47154

Draw-out part number: add 10 to the last digit. Example NT06H2 3P Draw-out:47203; 4P fixed part number +6 (NT06H2 4P Fixed 47119)

Derivative Isolator Models (HA version)

NTxxHA: Isolator (without trip unit, IEC60947-3)

NT06HA / NT08HA / NT10HA / NT12HA / NT16HA

Compatible Trip Unit List (Universal for full NT series)

Micrologica 2.0: Long-time overload only

MicroLogic 5.0A: A lungo + ritardo di breve durata + istantaneo (preferred for incoming / cravatta dell'autobus)

MicroLogic 6.0A: 5.0UN + protezione dai guasti a terra

MicroLogic 7.0A: 6.0UN + protezione corrente residua + harmonic measurement

Replacement Cross Reference Table (NT → MTZ1)

Legacy NT ModelReplacement MTZ1 Model
NT06N1MTZ1 06N1
NT06H1MTZ1 06H1
NT06H2MTZ1 06H2
NT06L1MTZ1 06L1
NT08~NT16 follow same ruleMTZ1 08 /10 /12 /16 + breaking class

Selection Remarks

  1. NT series fully discontinued, non consigliato per nuovi progetti; MTZ1 can be used for spare parts replacement for existing projects with compatible primary and secondary interfaces.
  2. L1 current-limiting type for systems with extremely high short-circuit current, costo più elevato; H2 is preferred for normal incoming feeder and bus tie.
  3. Rated current can be derated within the same frame by changing current sensor inserts, per esempio. NT06 frame available with 400A/500A/630A sensors.

Prec: