Ordine n.: 2864794, Modello sostitutivo: 2905025 MINI MCR-2-UNI-UI-2UI-C
Tipo: 4-way isolated analog signal duplicator / isolation amplifier (collegamento a vite, custom configuration version)
Funzione fondamentale
It accepts 1 channel of standard analog input signal and replicates it into 2 mutually independent current outputs after galvanic isolation. It realizes signal isolation, conversion, amplification, filtering and 1-in-2-out signal duplication. The measuring range is configured via DIP switches, with 4-way isolation (ingresso / produzione 1 / produzione 2 / power supply isolated from each other).
Suitable for splitting transmitter signals to PLC + paperless recorder, anti-interference isolation and instrument loop distribution.
📌 Specifiche elettriche principali
Alimentazione elettrica: 19.2–30 VCC, nominal 24VDC; power consumption <600mW, current <30mA @24V (including load)
Ingresso (selectable via DIP switch): 0…20mA / 4…20mA / 0…10V / 1…5V
Input impedance for voltage signal ≈100kΩ; input impedance for current signal ≈50Ω
Produzione: 2 independent current outputs, 0…20mA /4…20mA; massimo. output ≈22mA; load ≤250Ω@20mA
Precisione: Massimo. transmission error ≤0.2%FS, typical <0.1%FS; temperature drift <0.01%/K
Larghezza di banda (-3dB): ≈35Hz; step response (0–99%) ≈10ms
Isolation test voltage: 1.5kV AC 60s between input, uscita e alimentazione, basic insulation per EN61010
Classe di protezione: IP20; temperatura operativa -20 ~ +60℃, storage temperature -40~85℃, senza condensa
📐 Mechanical Data
Montaggio: 35Guida DIN da mm (EN60715), any mounting orientation
Larghezza: 6.2 mm (ultra-slim design for dense installation); 93.1(H) ×102.5(D) mm
Connessione: Morsetti a vite M3, conductor 0.2–2.5mm² (AWG26–12), stripping length 12mm
Alloggiamento: PBT, RAL6021 green; net weight 73.3g, gross weight 89.7g
📋 Certificazioni
CE, UL508, Classe I Div.2, Omologazione marina GL, II 3G Ex nA IIC T4 Gc X (explosion protection)
🧩 Series Identification & Pezzi di ricambio
2864794: MINI MCR-SL-UI-2I made-to-order configuration, non-returnable
2864176: MINI MCR-SL-UI-2I-NC standard pre-configured version
2864804: MINI MCR-SL-UI-2I-SP special version
Matching bus base: 2869728 ME 6,2 TBUS-2 (DIN rail power bus connector)
Matching power terminal: 2864134 MINI MCR-SL-PTB
The original part number 2864794 is no longer available for regular supply. Per nuovi progetti, use the replacement 2905025 MINI MCR-2-UNI-UI-2UI-C (new-generation MINI MCR-2 series, fully compatible with upgraded performance).
Application Scenarios for 2864794 (MINI MCR-SL-UI-2I)
Posizionamento centrale: 1 ingresso analogico, galvanically isolated duplication into 2 independent 4/0–20mA current signals, 4-way isolation (Ingresso / Uscita1 / Uscita2 / Energia), signal conversion + immunità al rumore. Ultra-slim 6.2mm width for dense cabinet layout, certified for installation in Zone 2 aree pericolose.
- Split One Sensor Signal into Two Outputs (Most Common Use Case)
- PLC + Paperless Recorder / Data Logger
Pressione, temperatura, level and flow transmitters with only one 4–20mA output can feed the PLC for control meanwhile send a copy to the recorder for data archiving and traceability. The two outputs are galvanically isolated; a fault on the recorder side will not drag down the transmitter loop or affect control.
- DCS Main System + Independent SIS Safety Interlock
One process measurement point sends one signal to DCS for monitoring and the isolated second signal to the independent SIS safety loop. Physical signal separation meets the independence requirement for functional safety.
- Dual PLC / Dual Controller Redundant Acquisition
Primary and backup controllers acquire the same field instrument signal at the same time. Isolated dual outputs prevent cross-interference caused by ground potential difference between controllers.
- SCADA Host Collection + HMI locale / Secondary Indicator
One channel feeds the PLC for SCADA upload, the other goes to local digital indicator or analog pointer meter for on-site display.
Input compatibility: 0/4–20mA, 0–10 V, 1–5 V; both outputs are current-only (0/4–20mA). Measuring ranges are freely combined via DIP switches.
- Ground Loop Elimination & Noise Isolation
When transmitters are installed near high-power motors, frequency converters or medium-frequency furnaces, long cable runs introduce ground potential difference and common-mode interference, resulting in signal jumping and drift. This module breaks ground loops and stabilizes analog signals.
Cross-cabinet signal transmission between cabinets with different potential (LV cabinet, VFD cabinet, DCS cabinet). It isolates potential offset and protects PLC analog channels from common-mode overvoltage damage.
- Signal Type Conversion
Field transmitters output voltage signals (0–10V/1–5V), while the two downstream receiving devices only accept 4–20mA current input. This unit converts the voltage input into two isolated current outputs.
- Applicazioni specifiche del settore
Chimico, Trattamento delle acque & Municipal Wastewater: Livello, pH, torbidità, flusso e pressione. Many projects require simultaneous control and data logging; adatto per Zona 2 installazione dell'armadio (Zona 2 soltanto, NOT intrinsic safety barrier).
Energia & Nuova energia (PV / Stoccaggio dell'energia / Distribuzione dell'energia): Bus voltage, transducer signals, temperatura dell'acqua di raffreddamento, split to PLC and waveform recording device.
HVAC, Automazione degli edifici & Camere bianche: Temperatura, humidity and differential pressure transmitters, split for BA controller and independent monitoring system.
Marino & Ferrovia (GL Marine Certificate): Cabin pressure and temperature monitoring. Ultra-slim footprint saves cabinet space for marine control cabinets.
Confezione, Gomma & Plastica, Macchine utensili & Automazione personalizzata: Tension, pressure and displacement sensors. One output for motion control PLC, the other for quality inspection recording system.
- Limitazioni alla selezione & Note
- Both outputs are current only, voltage output is not supported. Do not select this model if one current + one voltage split is required.
- It is an isolated duplication amplifier, not an intrinsically safe barrier. It cannot directly connect to IS instruments in Zone 0 / Zona 1; it may only be fitted inside Zone 2 hazardous-area cabinets.
- Excellent for slim cabinets and high-density I/O layouts. TBUS bus bases support daisy-chain rail power supply to reduce wiring work.
Fenice Contact Analog Signal Duplicator (1-in-2-out Signal Repeater) Order List
Two major series: Legacy MINI MCR-SL (6.2mm ultra-slim, compreso 2864794, eliminazione graduale) and New MINI MCR-2 / MINI Analog Pro (replacement series, freely configurable current/voltage output, NFC configuration supported)
Definizione: Signal Duplicator (1-in-2-out isolated repeater). Pure 1-in-1-out isolators are excluded from this table.
- Legacy MINI MCR-SL Series | UI-2I (UI Input, Dual Current Output 4/0–20mA)
| Ordine n. | Modello completo | Descrizione | Stato |
| 2864794 | MINI MCR-SL-UI-2I | Configurazione personalizzata, non-returnable | Obsoleto, consigliare 2905025 |
| 2864176 | MINI MCR-SL-UI-2I-NC | Standard pre-configured, regular stock | Obsoleto |
| 2864804 | MINI MCR-SL-UI-2I-SP | Configurazione personalizzata, non-returnable | Obsoleto, consigliare 2905027 |
| 2864189 | MINI MCR-SL-UI-2I-SP-NC | Standard pre-configured | Obsoleto |
Common limitation for legacy models: dual outputs are current only, voltage output unavailable; 4-way isolation (Ingresso / Uscita1 / Uscita2 / Power isolated).
- New MINI MCR-2 Universal Duplicator UNI-UI-2UI (UI Universal Input, Two Outputs Independently Configurable for Voltage or Current)
| Ordine n. | Modello completo | Tipo di connessione | Descrizione |
| 2905026 | MINI MCR-2-UNI-UI-2UI | Vite | Standard pre-configured NC |
| 2905025 | MINI MCR-2-UNI-UI-2UI-C | Vite | Custom configuration C (replaces legacy 2864794) |
| 2905028 | MINI MCR-2-UNI-UI-2UI-PT | Push-in | Standard pre-configured NC |
| 2905027 | MINI MCR-2-UNI-UI-2UI-PT-C | Push-in | Custom configuration C (replaces legacy 2864804) |
Upgrade highlights for new series: each output independently configurable as current or voltage, IMMERSIONE + NFC + software configuration, diagnostica dei guasti, improved accuracy.
- Additional 1-in-2-out Duplicators in Family (Loop-Powered Version)
| Ordine n. | Modello completo | Descrizione |
| 2905628 | MINI MCR-2-RPSS-I-2I | Alimentato dal loop, 1 current input, 2 current outputs, collegamento a vite |
| 2905629 | MINI MCR-2-RPSS-I-2I-PT | Alimentato dal loop, 1 current input, 2 current outputs, Push-in |
- Accessori coordinati (Bus Power Base for Duplicators)
| Ordine n. | Nome | Scopo |
| 2869728 | ME 6,2 TBUS-2 1,5/5-ST-3,81 GN | TBUS rail bus connector for parallel power supply, compatible with slim MINI MCR-SL |
| 2864134 | MINI MCR-SL-PTB | Power terminal block |
Quick Cross Reference for Replacement
2864794 (vite, costume) → 2905025
2864176 (vite, standard) → 2905026
2864804 (spring-cage, costume) → 2905027
2864189 (spring-cage, standard) → 2905028
MINI MCR-SL-UI-UI-NC (2864150): 1-in-1-out isolator, NOT a duplicator, excluded
MACX series are mostly high-withstand, SIL functional safety or explosion-proof isolators, not general signal duplicators.
Phoenix MINI MCR-2 / MINI Analog Pro Analog Signal Duplicator (1-in-2-out Isolated Repeater) Order List
Note: MINI MCR-2 belongs to the MINI Analog Pro platform; supports NFC / software / DIP configuration, diagnosi dei guasti, 4-way isolation. Split into universal UI input duplicator and loop-powered HART RPSS-I-2I. PT = Push-in quick connection; no PT suffix = screw connection; suffix -C = made-to-order custom configuration (non-returnable).
- Universal Multi-Range Type: MINI MCR-2-UNI-UI-2UI (Universal UI Input, Two Outputs Independently Selectable for Current / Voltaggio)
| Ordine n. | Modello completo | Descrizione | Sostituzione legacy |
| 2905026 | MINI MCR-2-UNI-UI-2UI | Standard pre-configured NC, regular stock | 2864176 |
| 2905025 | MINI MCR-2-UNI-UI-2UI-C | Custom configuration C, parameters specified on order, non-returnable | 2864794 (your original part) |
| 2905028 | MINI MCR-2-UNI-UI-2UI-PT | Standard pre-configured NC | 2864189 |
| 2905027 | MINI MCR-2-UNI-UI-2UI-PT-C | Custom configuration C, non-returnable | 2864804 |
Caratteristiche: Input accepts 0/4–20mA, 0–10 V, 1–5 V; OUT1 and OUT2 can be independently set to current or voltage, mixed output allowed. Supports HART pass-through, Configurazione mobile NFC, allarme guasto, Zona 2 Ex certification.
- Loop-Powered Type: MINI MCR-2-RPSS-I-2I (4–20mA Loop Powered, HART Transparent, 1-in-2-out Current)
| Ordine n. | Modello completo | Tipo di connessione | Descrizione |
| 2905628 | MINI MCR-2-RPSS-I-2I | Vite | Alimentato dal loop, HART transparent, dual current output |
| 2905629 | MINI MCR-2-RPSS-I-2I-PT | Push-in | Alimentato dal loop, HART transparent, dual current output |
Caratteristiche: Powered directly from transmitter loop, independent 24V supply not required. Two passive 4–20mA outputs. Ideal for 2-wire HART transmitters, shared measurement points for DCS/SIS. Massimo. load per channel up to 500Ω.
- Accessori coordinati (General for MINI Analog Pro Platform)
| Ordine n. | Nome | Scopo |
| 2902066 | MINI MCR-2-PTB | Screw-type power terminal for rail bus daisy-chain power supply |
| 2902067 | MINI MCR-2-PTB-PT | Push-in power terminal |
| 2904504 | MINI MCR-2-FM-RC | Screw fault collective alarm module |
| 2904508 | MINI MCR-2-FM-RC-PT | Push-in fault collective alarm module |
| 2905634 | MINI MCR-2-V8-MOD-RTU | Modbus-RTU communication adapter, supporta fino a 8 modules in network |
| 2905635 | MINI MCR-2-V8-MOD-TCP | Modbus-TCP communication adapter, supporta fino a 8 modules in network |
- Guida alla selezione & Evitare le trappole
- UNI-UI-2UI: Requires separate 24VDC supply, universal voltage/current input, two outputs can mix voltage + attuale. Direct upgrade replacement for legacy MINI MCR-SL-UI-2I.
- RPSS-I-2I: Alimentato dal loop, solo ingresso corrente, dual current output only. Preferred for HART projects; cannot be used for voltage signal splitting.
- 1-in-1-out isolators of the same series (per esempio. MINI MCR-2-UI-UI) are not duplicators and excluded from this list.
- Codice SA: 85437090, Paese di origine: Germania (DI)
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore