Schneider EGR-20UFCM Protection Relay

Schneider EGR-20UFCM Digital Earth Leakage Fault Protection Relay (Exclusive for EOCR) Schneider EGR-20UFCM is a dual-signal embedded relay designed for earth leakage fault protection. It features a wide measuring range of 0.03~20A, built-in filter and Modbus communication. Widely applied in low-voltage power distribution and motor protection. Match current range, detection type and mounting mode during ...

  • Dettagli del prodotto

Schneider EGR-20UFCM Digital Earth Leakage Fault Protection Relay (Exclusive for EOCR)

Schneider EGR-20UFCM is a dual-signal embedded relay designed for earth leakage fault protection. It features a wide measuring range of 0.03~20A, built-in filter and Modbus communication. Widely applied in low-voltage power distribution and motor protection. Match current range, detection type and mounting mode during selection. Strictly follow ZCT polarity and earthing specifications for reliable system operation.

  1. Definizione del codice modello
Segmento di codiceSensoDescrizione
EGRSerie di prodottiDigital earth leakage & fault protection relay, Schneider EOCR series, manufactured by SAMWHA Korea
20Intervallo correnteMax detection current 20A, coverage 0.03~20A
UFDetection TypeDual-signal mode: U=Voltage(mV), F=Current(mA), compatible with ZCT zero-sequence current transformer
CMTipo di montaggioConsole panel mounting, equipped with digital display and protective cover

Quick Recognition: EGR-20UFCM = 20A range dual-signal embedded earth leakage protection relay, exclusive for EOCR

  1. Parametri tecnici fondamentali
ParametroSpecificaRemark
Detection TypeAttuale(mA) + Voltaggio(mV)Doppio ingresso, compatible with ZCT
Measuring Current Range0.03~20AWide coverage for diverse applications
Instant Fault Protection30mA, 30SMFast response for personal safety
Caratteristica operativaInverse / Definite time optionalFlexible for various protection demands
Alimentazione elettricaAC/DC 24V or 100~240VWide voltage, global power grid adaptation
DisplayLED digital displayReal-time leakage current indication
Fault Record5 historical faults + RTC clockConvenient fault analysis and tracing
ComunicazioneModBus RTU (RS-485)Remote monitoring and data acquisition
Contatto ausiliarioSPDT (1C/O)Rated load AC 250V/3A resistive
Anti-interferenzaBuilt-in noise filterSuitable for high harmonic environment like inverter & UPS
Classe di protezioneIP52Dustproof and splash-proof
MontaggioPanel embeddedCompatibile con guida DIN standard da 35 mm
DimensioneW45×H90×D110mmDimensioni compatte, salvaspazio
Temperatura operativa-20~60℃Stable operation under harsh industrial conditions
Temperatura di conservazione-30~80℃Adapt to extreme storage environment
CertificazioneCE, UL508, EN61010Comply with international safety standards
Numero d'ordineEGR-20UFCMOfficial unique part number
  1. Full EGR Series Models
ModelloDetection TypeIntervallo correnteMontaggioCaratteristiche principali
EGR-20UFCMDual current & voltaggio0.03~20APanel embeddedDisplay digitale, harmonic resistance
EGR-20USAMCurrent signal0.03~20AMontaggio su baseStandard base, easy wiring
EGR-10USVMVoltage signal0.03~10AMontaggio su baseVoltage input, fit dedicated ZCT
EGR-20RY7MCurrent signal0.05~20APanel embeddedComunicazione RS-485, ampia gamma
EGR-05UFCMDual current & voltaggio0.03~5APanel embeddedSmall range, alta precisione
  1. Cross-brand Replacement Comparison
MarcaModelloDetection TypeIntervallo correnteComunicazioneCompatibilità
Schneider

(SAMWHA)

EGR-20UFCMDual signal0.03~20AModBus RTUPerfect match with EOCR and ZCT
Siemens3UG4615-1CR20Attuale0.03~30AModBus RTUGeneral type, adaptation test required
ABBCM-IW20Attuale0.05~20ANo communicationHigh load capacity, compatible with standard ZCT
CintoND-63Attuale0.03~30AOptional RS-485Cost-effective alternative
DeliziosoDZL-20Attuale0.05~20ANo communicationSostituzione domestica, slight dimension difference

Note di sostituzione

  1. Confirm ZCT compatibility for third-party products to guarantee detection accuracy
  2. Dual U+F signal is exclusive to EGR-20UFCM, evaluate working condition before replacement
  3. Select filtered model for high harmonic occasions to avoid false tripping
  4. Risoluzione dei problemi & Manutenzione
Fenomeno di guastoPossibili causeInspection StepsSoluzioni
Frequenti falsi interventiHarmonic interference, excessive earthing resistance, low setting valueCheck interference sources; measure earthing resistance ≤4Ω; verify parameter settingActivate filter; optimize earthing system; adjust protection threshold
No display under normal statusPower failure, wrong wiring, display damageTest power voltage; inspect ZCT wiring; check LED statusRestore power circuit; correct S1/S2 polarity; replace display module
No response upon faultExcessive setting value, defective auxiliary contact, damaged ZCTCheck action parameter; test contact continuity; measure ZCT secondary resistanceLower protection setting; replace contact parts; renew ZCT transformer
Errore di comunicazioneMismatched parameters, wrong wiring, faulty moduleVerify baud rate, indirizzo e parità; check A/B wire connection; test port voltageUnify communication parameters; cablaggio corretto; replace communication module

Troubleshooting Rules

  1. Conduct leakage simulation test after installation to verify performance
  2. Enable filter function to reduce false action in high harmonic environment
  3. F01=Earth fault, F02=Overcurrent fault for quick positioning
  4. Applicazione & Cases

Scenari applicabili

Distribuzione dell'energia a bassa tensione: Earth fault protection for circuits below AC 600V

Centro di controllo motorio: Combined leakage and overload protection with EOCR relay

Automatic production line: Inverter-driven motors and UPS power supply equipment

Chimico & petroleum industry: Safety protection for flammable and explosive sites, meet ATEX standard

Centro dati: Precision equipment protection to ensure power continuity

Building electrical system: Civil leakage protection complying with GB 13955

Unsuitable Scenarios

High voltage system above 1kV without step-down transformer

Pure DC circuit with declined detection accuracy

Strong electromagnetic field without shielding measures

Operation without matched ZCT zero-sequence transformer

Casi tipici

Caso 1: Inverter Motor Protection in Automobile Workshop

10 sets of 75kW variable frequency motors equipped with ZCT-120. EGR-20UFCM adopts dual signal detection and filter design. It realizes 300mA/500ms leakage protection and fault record, improving system reliability by 50%.

Caso 2: Operating Room Power Renovation in Hospital

Meet IEC 61557-8 medical leakage protection standard. Combine EGR-20UFCM and ZCT-35 with 30mA instant protection setting, reaching Class B protection level and securing personnel safety.

  1. Selezione & Linee guida per l'installazione

Three-step Selection

  1. Confirm measuring range based on maximum system leakage current (0.03~20A)
  2. Choose dual UF signal for inverter occasions, single US signal for general use
  3. Select CM panel mounting for cabinet installation, SA base type for fast wiring

Precauzioni per l'installazione

Thread three-phase four-wire cable through ZCT, neutral wire shall not be omitted

Connect ZCT S1 to EGR I+, S2 to I-, reversed connection causes detection failure

Single-point earthing for relay and ZCT, earthing resistance ≤4Ω

Turn on filter function under variable frequency working condition

Use shielded twisted pair for RS-485, avoid reversed A/B wiring

Programma di manutenzione

ArticoloCicloStandard
Visual inspectionMensileNo crack, looseness or overheating
Functional testTrimestraleNormal action via leakage simulation
Earthing resistance testSemestraleResistance ≤4Ω
Prova di comunicazioneSemestraleStable data transmission without packet loss
Parameter verificationYearlySettings conform to site safety requirements

Application Scenarios of EGR-20UFCM

Campi applicabili

  1. Protezione dei motori industriali

Suitable for variable frequency motors and heavy-duty three-phase motors. Cooperate with EOCR relay for comprehensive leakage and fault protection on production lines, tifosi, water pumps and air compressors.

  1. Low-voltage Distribution Circuit

Monitor earth fault of factory power cabinets, MCC control cabinets and branch circuits below AC 600V, prevent fire risks caused by leakage.

  1. Special Industry Power Consumption

Safety protection for flammable and explosive sites in chemical, oil and mining industry; electric control protection for port cranes and construction machinery.

  1. Medical Building Power Supply

Precise power distribution for operating rooms and diagnosis rooms, satisfy medical leakage safety standards.

  1. Data Center Room

Monitor feeder lines of UPS and server cabinets, avoid power outage induced by earth fault.

  1. HVAC & Water Treatment Equipment

Leakage protection for central air conditioning, circulating water pumps and sewage treatment control systems.

  1. Intelligent Monitoring Power Distribution

Connect to industrial control system via Modbus RTU, remotely check leakage data and trace fault history.

Inapplicable Fields

  1. Cannot be directly used on circuits over 1kV without step-down transformer
  2. Poor detection performance on pure DC power loop
  3. Prone to false tripping without shielding in strong electromagnetic environment
  4. Unable to work normally without matched ZCT zero-sequence transformer